Signed Inspection Report (Mon Apr 12, 2021 at 326 PM)INSPECTION WORKSHEET (FRM-009593-2021) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:RC-0789-2020 Case Module:Permit Inspection Date:Mon Apr 12, 2021 Inspection Status:Failed Inspector:O'Brien, John Inspection Type:Building Framing Job Address:Parcel Number:88 MAIN ST Queensbury, NY, 12804 309.14-1-19 Contact Type Company Name Name Contractor Burke, Corey Primary Owner RAIMO, JUSTIN Granted Permission RAIMO, JUSTIN Applicant RAIMO, JUSTIN Checklist Item Status Building Inspector Notes Failed 3/5/21 Building Framing Not Approved - 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both sides of floor joist. The plywood must be be glued and screwed every 3" oc. APPROVED 4/12/21 4/12/21 Building Framing Not Approved - Install steel column under notched out beam where previous plumbing was installed. Framing Failed 3/5/21 Building Framing Not Approved - 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both sides of floor joist. The plywood must be be glued and screwed every 3" oc. APPROVED 4/12/21 4/12/21 Building Framing Not Approved - Install steel column under notched out beam where previous plumbing was installed. Apr 12, 2021 Page (1) O'Brien, John