Signed Inspection Report (Mon Apr 12, 2021 at 326 PM)INSPECTION WORKSHEET (FRM-009593-2021)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0789-2020 Case Module:Permit
Inspection Date:Mon Apr 12, 2021 Inspection Status:Failed
Inspector:O'Brien, John Inspection Type:Building Framing
Job Address:Parcel Number:88 MAIN ST
Queensbury, NY, 12804
309.14-1-19
Contact Type Company Name Name
Contractor Burke, Corey
Primary Owner RAIMO, JUSTIN
Granted Permission RAIMO, JUSTIN
Applicant RAIMO, JUSTIN
Checklist Item Status
Building Inspector Notes Failed
3/5/21 Building Framing Not Approved
- 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These
holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both
sides of floor joist. The plywood must be be glued and screwed every 3" oc. APPROVED 4/12/21
4/12/21 Building Framing Not Approved
- Install steel column under notched out beam where previous plumbing was installed.
Framing Failed
3/5/21 Building Framing Not Approved
- 3 Existing 2nd floor 2"x6" floor joists have existing 3" holes in them from existing plumbing removed. These
holes will have to be gussetted with a minimum of 5/8" plywood 24" passed the hole at each side of hole on both
sides of floor joist. The plywood must be be glued and screwed every 3" oc. APPROVED 4/12/21
4/12/21 Building Framing Not Approved
- Install steel column under notched out beam where previous plumbing was installed.
Apr 12, 2021 Page (1)
O'Brien, John