HVAC air balancing reportMJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
Date:
Prepared by:
Engineer:
Contractor:
Queensbury, New York 12845
DPCE
Shapel General Contracting, Inc.
1424 US Rt 9
Project:
HVAC SYSTEMS TESTING:
Air Balance Report
for
American Eagle Outfitters
Michael J. Lucarelli
May 11, 2021
The Outlets at Lake George
1301 Solona Boulevard, Building 1 Suite 1420
Westlake, Texas 76262
20 East Main Street
Carnegie, Pennsylvania 15106
Location:
Project:
Address:
DATE:
PROJECT # :M9029
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND
WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES
FROM DESIGNED QUANTITIES WHICH EXCEEDS NEBB TOLERANCES ARE NOTED THROUGHOUT
THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS
HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING
AND BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
THE WATER DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL
ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS
FOR TESTING AND BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT
SPECIFICATIONS.
CERTIFICATION
1424 US Rt 9
Queensbury, New York 12845
American Eagle Outfitters
The Outlets at Lake George
MJL ADTEK Enterprises, LLC.TESTING AND BALANCING FIRM:
BALANCED BY:
SIGNATURE:
May 11, 2021
Michael J. Lucarelli
Michael J. Lucarelli
CD - Ceiling Diffuser
CS - Circuit Setter
DD - Direct Drive
ER - Exhaust Register
LD - Linear Diffuser
NA - Not Accessible
ND - No Volume Damper
NG - No Gauges
NI - Not Installed
NR - Not Required
NS - Not Specified
OBD - Opposed Blade Damper
OD - Open Duct
RG - Return Grille
SR - Supply Register
SD - Supply Diffuser
TP- Thermally Protected
EP-Electronically Protected
WMS - Wire Mesh Screen
NN - Diffuser, Register or Grille Noisy: All available
adjustments made to correct condition. Additonal
Dampers, sound lining or duct change required to
correct condition.
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
Following are code definitions as used in a balancing report:
TYPE SIZE Ak FPM CFM TEST 1 TEST 2 TEST 3 FPM CFM
EVAV-1
1 SALES AREA SG-1 15.25"x7.25"0.61 615 375 326 285 NR 467 285
2 SALES AREA SG-1 15.25"x7.25"0.61 615 375 337 278 NR 456 278
3 SALES AREA SG-1 15.25"x7.25"0.61 656 400 296 304 NR 498 304
4 SALES AREA SG-1 15.25"x7.25"0.61 656 400 251 307 NR 503 307
5 ENTRY CD-1 6"RD 1.0 HOOD 100 71 77 NR HOOD 77
6 SALES AREA SG-1 15.25"x7.25"0.61 451 275 231 211 NR 346 211
7 STOCK ROOM SG-1 15.25"x7.25"0.61 369 225 191 178 NR 292 178
8 STOCK ROOM SG-1 15.25"x7.25"0.61 287 175 143 141 NR 231 141
9 SALES AREA SG-1 15.25"x7.25"0.61 615 375 251 289 NR 474 289
10 SALES AREA SG-1 15.25"x7.25"0.61 533 325 243 253 NR 415 253
11 SALES AREA SG-1 15.25"x7.25"0.61 451 275 207 212 NR 348 212
12 SALES AREA SG-1 15.25"x7.25"0.61 328 200 126 158 NR 259 158
13 SALES AREA SG-1 15.25"x7.25"0.61 328 200 131 153 NR 251 153
TOTAL 3700 TOTAL 2846
EVAV-2
1 SALES AREA SG-1 15.25"x7.25"0.61 451 275 236 205 NR 336 205
2 SALES AREA SG-1 15.25"x7.25"0.61 615 375 301 273 NR 448 273
3 SALES AREA SG-1 15.25"x7.25"0.61 738 450 317 321 NR 526 321
4 SALES AREA SG-1 15.25"x7.25"0.61 533 325 207 230 NR 377 230
5 SALES AREA SG-1 15.25"x7.25"0.61 738 450 306 315 NR 516 315
6 SALES AREA SG-1 15.25"x7.25"0.61 738 450 312 327 NR 536 327
7 SALES AREA SG-1 15.25"x7.25"0.61 738 450 131 318 NR 521 318
8 SALES AREA SG-1 15.25"x7.25"0.61 533 325 255 234 NR 384 234
9 FITTING ROOM SG-1 15.25"x7.25"0.61 533 325 201 229 NR 375 229
10 FITTING ROOM SG-1 15.25"x7.25"0.61 328 200 186 148 NR 243 148
11 STOCK ROOM CD-1 6"RD 1.0 HOOD 75 20 58 NR HOOD 58
TOTAL 3700 TOTAL 2658
Remarks: EVAV-1 Fan Box speed is set at 100%.
EVAV-2 Fan Box speed is set at 100%.
PAGE NUMBER:
TOTAL PAGES:
1
3
FINAL
AIR DISTRIBUTION TEST SHEET
TERMINAL
NUMBER ROOM NUMBER TERMINAL DESIGN TEST-FPM or CFM
ADDRESS:
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
PROJECT NAME: American Eagle Outfitters
The Outlets at Lake George
Queensbury, New York 12845
1424 US Rt 9
PROJECT NUMBER:M9029
5/11/2021DATE:
PROJECT NAME:
ADDRESS:
ACTUAL
Remarks:
SYSTEM EF-1
EXHAUST FAN DATA SHEET
EQUIPMENT LOCATON CEILING
AREA SERVICED RESTROOM
DIRECT DRIVE
DIRECT DRIVE
SERIAL NUMBER
SPECIFIED SPECIFIED ACTUAL
EQUIPMENT MANUFACTURER PENN
MODEL
NS
TOTAL CFM-FAN 100
TOTAL CFM-OUTLET 100
INLET PRESSURE
TOTAL STATIC PRESSURE 0.25
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
BELTS
MOTOR SERVICE FACTOR NS
STARTER HEATER ELEMENTS NS
DIRECT DRIVEMOTOR SHEAVE & NO. GROOVES
FAN SHEAVE & NO. GROOVES
VOLTAGE 115
AMPERAGE
MOTOR RPM NS
MOTOR MANUFACTURER NS
MOTOR HP/BHP NS
PROJECT
NUMBER:M9029
5/11/2021DATE:
Queensbury, New York 12845
American Eagle Outfitters
The Outlets at Lake George
1424 US Rt 9 PAGE NUMBER:
TOTAL PAGES:3
2
PHASE 1
DISCHARGE PRESSURE NS
FAN RPM NS
TYPE SIZE Ak FPM CFM TEST 1 TEST 2 TEST 3 FPM CFM
EF-1
1 RESTROOM EG-1 6"RD 1.0 HOOD 100 0 0 NR HOOD 0
Remarks:
FINAL
Queensbury, New York 12845 TOTAL PAGES:3
AIR DISTRIBUTION TEST SHEET
TERMINAL
NUMBER ROOM NUMBER TERMINAL DESIGN TEST-FPM or CFM
The Outlets at Lake George DATE:5/11/2021
ADDRESS: 1424 US Rt 9 PAGE NUMBER:3
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
PROJECT NAME: American Eagle Outfitters PROJECT NUMBER:M9029