Signed Inspection Report (05-21-2021) (7).pdfINSPECTION WORKSHEET (RPLUM-010547-2021)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0255-2020 Case Module:Permit
Inspection Date:Fri May 21, 2021 Inspection Status:Passed
Inspector:Dyer, Charles Inspection Type:Rough Plumbing
Job Address:Parcel Number:12 HALL RD EXT
Queensbury, NY, 12804
289.11-1-17
Contact Type Company Name Name
Primary Owner Leonardo, Rebecca
Contractor Rosewood Home Builders
Applicant Leonardo, Rebecca
Granted Permission Rosewood Home Builders
Engineer VanDeLoo, Walter
Primary Owner Leonardo, Adam
Applicant Leonardo, Adam
Checklist Item Status
Building Inspector Notes Failed
Plumber not onsite, follow checklist, call for recheck/when ready 9/18/20
10/1/20 partial approval for plumbing, 4" pvc sanitary plumbing will need to be isolated where it exits the
foundation and rechecked.
3/4 supplies need to be insulated.
Plumbing Under Slab Failed
Rough Plumbing / Nail Plates Passed
May 21, 2021 Page (1)
INSPECTION WORKSHEET (RPLUM-010547-2021)
Checklist Item Status
Plumbing Vent Vents in Place Passed
3" Vent Through Roof Passed
1 ½ inch minimum Drain Size Passed
Washing Machine Drain 2 inch minimum Passed
Washing Machine Trap: 18"-42" discharge Passed
Cleanout every 100 feet change of direction Passed
Pressure Test Passed
Sanitary plumbing tested with water
5 psi or 10 ft. above highest conn. for 15 minutes Passed
Holding water for 15 minutes,
4" pvc at foundation will need to be isolated and rechecked
Checked for leaks via water through foundation, 4" SCHD 40 verified 5/21/21
Water Supply Piping Passed
Air Head Passed
50 P.S.I for 15 minutes Passed
Hold 70 psi for 15 minutes
May 21, 2021 Page (2)
INSPECTION WORKSHEET (RPLUM-010547-2021)
Checklist Item Status
Air Test Gas Piping 10 psi for 10 Minutes Passed
Propane
All Return Air Hard Duct Work Passed
Duct work not completed at this time
Verified sealing of registers at floor
Duct work sealed properly Passed
Duct work not completed at this time
Verified
May 21, 2021 Page (3)