JB201133.0150.Concrete Compressive Strength Test.2021-05-03.Rpt.0150Rev1Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
C40R762
CBC
Material Information
0635
624
Plant:
Ticket No.:
Glens Falls, NY
1835947
Field Test Data
Test
Air Content (%):
Result Specification
8
2.0
61
55
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/03/21 0720
Abdulaziz Abdalla
45 and cloudy
10 10
10
0
North end of pour areaSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Slab on grade from lines F-T and
lines 23.2-38
Placement Location:
Laboratory Test Data
Set Avg Diam.Area Weight DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By(lbs)
1 A 4.00 12.57 05/04/21 8.95 05/10/21 7 78,150 2 6,220 ADB
1 B 4.00 12.57 05/04/21 8.95 05/31/21 28 89,820 3 7,150 ADB
1 C 4.00 12.57 05/04/21 8.90 05/31/21 28 93,910 2 7,470 ADB
1 D 4.00 12.57 05/04/21 8.95 05/31/21 28 92,670 3 7,370 ADB
Average (28 days) 7,330
1 E 05/04/21 8.95 Hold
1 F 05/04/21 8.95 Hold
Initial Cure:Final Cure:Onsite Cooler Moist Room
Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit
weight.
Note: Reported air content does not include Aggregate Correction Factor (ACF).
Superplasticizer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Samples Made By: Dente Group - A Terracon Co.
Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services:
Reported To:
Contractor:
Report Distribution:
(1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas
(1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax
(1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin
Stothers
(1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone
BBL
Bobby w/ BBL
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Dente Group - A Terracon Co. Rep.: Abdulaziz Abdalla
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
C40R762
CBC
Material Information
0800
626
Plant:
Ticket No.:
Glens Falls, NY
1935953
Field Test Data
Test
Air Content (%):
Result Specification
8
2.0
61
55
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/03/21 0830
Abdulaziz Abdalla
55 and clear sky
60 10
10
0
Midpoint of pour areaSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Slab on grade from lines F-T and
lines 23.2-38
Placement Location:
Laboratory Test Data
Set Avg Diam.Area Weight DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By(lbs)
2 A 4.00 12.57 05/04/21 9.00 05/10/21 7 73,790 2 5,870 ADB
2 B 4.00 12.57 05/04/21 8.85 05/31/21 28 90,650 3 7,210 ADB
2 C 4.00 12.57 05/04/21 8.90 05/31/21 28 89,630 3 7,130 ADB
2 D 4.00 12.57 05/04/21 8.90 05/31/21 28 93,250 2 7,420 ADB
Average (28 days) 7,260
2 E 05/04/21 8.90 Hold
2 F 05/04/21 8.85 Hold
Initial Cure:Final Cure:Onsite Cooler Moist Room
Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit
weight.
Note: Reported air content does not include Aggregate Correction Factor (ACF).
Superplasticizer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Samples Made By: Dente Group - A Terracon Co.
Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services:
Reported To:
Contractor:
Report Distribution:
(1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas
(1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax
(1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin
Stothers
(1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone
BBL
Bobby w/ BBL
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Dente Group - A Terracon Co. Rep.: Abdulaziz Abdalla
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
C40R762
CBC
Material Information
0900
662
Plant:
Ticket No.:
Glens Falls, NY
1835958
Field Test Data
Test
Air Content (%):
Result Specification
9
1.8
61
55
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:05/03/21 0915
Abdulaziz Abdalla
55 and cloudy
110 10
20
0
South end of pour areaSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Slab on grade from lines F-T and
lines 23.2-38
Placement Location:
Laboratory Test Data
Set Avg Diam.Area Weight DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
Tested
By(lbs)
3 A 4.00 12.57 05/04/21 8.95 05/10/21 7 80,400 2 6,400 ADB
3 B 4.00 12.57 05/04/21 9.00 05/31/21 28 94,140 3 7,490 ADB
3 C 4.00 12.57 05/04/21 8.95 05/31/21 28 96,060 2 7,640 ADB
3 D 4.00 12.57 05/04/21 8.95 05/31/21 28 94,700 2 7,540 ADB
Average (28 days) 7,560
3 E 05/04/21 9.05 Hold
3 F 05/04/21 9.00 Hold
Initial Cure:Final Cure:Onsite Cooler Moist Room
Comments:Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit
weight.
Note: Reported air content does not include Aggregate Correction Factor (ACF).
Superplasticizer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client
Queensbury, NY 12804
Bay Road and Blind Rock Road
Fowler Square SI and CMTRosetti Acquisitions LLC
Attn: Christopher Falvey
427 New Karner Rd
Albany, NY 12205
518-266-0310
Albany, NY 12203-5169
30 Corporate Cir Ste 201
JB201133.0150
05/03/21
06/02/21 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Project
Project Number: JB201133
Samples Made By: Dente Group - A Terracon Co.
Sample fresh concrete at the placement locations, perform required field tests and cast compressive strength samples.Services:
Reported To:
Contractor:
Report Distribution:
(1) Rosetti Acquisitions LLC, Christopher Falvey (1) 260 Structural Engineering, Dan Thomas
(1) BBL Construction Services, Bobby Chatterton (1) BBL Construction Services, Eric Weatherwax
(1) BBL Construction Services, Ryan Etue (1) D.A. Collins Construction Co Inc, Robin
Stothers
(1) Galusha & Sons LLC, Drew Stevens (1) Galusha & Sons LLC, James Campagnone
Jared Hall
Staff Geologist
BBL
Bobby w/ BBL
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Dente Group - A Terracon Co. Rep.: Abdulaziz Abdalla
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 6 of 6CR0001, 11-16-12, Rev.6