ResCheck C"
Compliance Certificate
e jl G DEC 0 7 2020
Project ranch
Energy Code: 2018 IIECC
Location: West Glens Falls, New York
Construction Type: Single-family
Project Type: New Construction
Conditioned Floor Area: 1#703 ft2
308.14-1-26 RC-0765-2020
Glazing Area 26%
Climate Zone: 6 (7377 HDD) Monsour Enterprises LLC
Permit Date: 3 Amethyst Dr
Permit Number: SFD w/gas f p 1703 SJ., Gar. 576 s.f.
Construction Site: Owner/Agent: Designer/contractor:
Compliance: 0.7%Better Than Code Maximum UA: 289 Your UA: 287
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy Use or cost relative to a minimum-code home.
A s Ceiling: Flat Ceiling or Scissor Truss 1,703 49.0 0.0 0.026 44
Wall:Wood Frame, 16"o.c. 1,731 21.0 0.0 0.057 80
Door: Solid Door(under 50%glazing) 20 0.190 4
Door 1:Solid Door(under 50%glazing) 20 0.150 3
Door 3:Glass Door(over 50%glazing) 23 0.300 7
Door 3: Glass Door(over 50%glazing) 23 0.300 7
Window:Vinyl Frame 238 0.270 64
Basement:Solid Concrete or Masonry 1,703 0.0 15.0 0.046 78
Wall height:8.0'
Depth below grade:7.3'
Insulation depth: 7.7'
Compliance Statement. The proposed building design described here is consistent with the building plans,specifications, and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2018 IECC requirements in
REScheck Version : REScheck-Web and to comply with the mandatory req . nts listed in the REScheck Inspection Checklist.
No 0 AIAACAU a Z-6 I.),\
Name-Title Signature Date
Project Title: ranch Report date: 12/03/20
Data filename: Pagel of 9
17E 5 c, e c a ii:
b,C. D G,C at ki. U a 1, a ie S a E.
Inspection Checklist
Energy Code: 2018 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section Plans Verified Field Verified
# Pre-inspection/Plan Review Value Value Complies? Comments/Assumptions
Req.113
103.1, Construction drawings and ElComplies
103.2 documentation demonstrate 0Does Not
[PR1]1 energy code compliance for the E]Not Observable
building envelope.Thermal
envelope represented on ONot Applicable
construction documents.
103.1, Construction drawings and OComplies
103.2, documentation demonstrate ElDoes Not
403.7 energy code compliance for E]Not Observable
[PR3]1 lighting and mechanical systems. ElNot Applicable
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1' Heating and cooling equipment is Heating: Heating: OComplies
403.7 sized per ACCA Manual S based Btu/hr Btu/hr []Does Not
[PR2]2 on loads calculated per ACCA Cooling: Cooling: ONot Observable
Manual J or other methods Btu/hr Btu/hr
approved by the code official. ONot Applicable
Additional Comments/Assumptions:
I I High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 2 of 9
Section Plans Verified Field Verified
# Foundation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1 Conditioned basement wall R- R- ❑Complies See the Envelope Assemblies
[FO4]1 insulation R-value.Where interior R- R- ❑Does Not table for values.
insulation is used,verification []Not Observable
may need to occur during
Insulation Inspection. Not []Not Applicable
required in warm-humid locations
in Climate Zone 3.
303.2 Conditioned basement wall ❑Complies
[FO5]1 insulation installed per ❑Does Not
manufacturer's instructions.
[]Not Observable
❑Not Applicable
402.2.9 Conditioned basement wall ft ft ❑Complies See the Envelope Assemblies
[FO6]1 insulation depth of burial or ❑Does Not table for values.
distance from top of wall.
❑Not Observable
❑Not Applicable
303.2.1 A protective covering is installed ❑Complies
[F011]z to protect exposed exterior []Does Not
insulation and extends a
minimum of 6 in. below grade. ❑Not Observable
❑Not Applicable
403.9 Snow-and ice-melting system ❑Complies
[FO12]2 controls installed. ❑Does Not
[]Not Observable
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 3 of 9
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, Door U-factor. U- U- ❑Complies See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[FR111 []Not Observable
❑Not Applicable
402.1.1, Glazing U-factor(area-weighted U- U- ❑Complies see the Envelope Assemblies
402.3.1, average). []Does Not table for values.
402.3.3, []Not Observable
402.5 ❑Not Applicable
[FR2]1 pp
303.1.3 U-factors of fenestration products [ Complies
[FR4]1 are determined in accordance ❑Does Not
with the NFRC test procedure or ❑Not Observable
taken from the default table.
❑Not Applicable
402.4.1.1 Air barrier and thermal barrier ❑Complies
[FR2311 installed per manufacturer's ❑Does Not
instructions.
❑Not Observable
❑Not Applicable
402.4.3 Fenestration that is not site built ❑Complies
[FR20]1 is listed and labeled as meeting ❑Does Not
AAMA/WDMA/CSA 101/I.S.2/A440 []Not Observable
or has infiltration rates per NFRC
400 that do not exceed code ❑Not Applicable
limits.
402.4.5 IC-rated recessed lighting fixtures ❑Complies
[FR16]2 sealed at housing/interior finish []Does Not
and labeled to indicate s2.0 cfm [_-]Not Observable
leakage at 75 Pa.
❑Not Applicable
403.3.1 Supply and return ducts in attics ❑Complies
[FR12]1 insulated >= R-8 where duct is ❑Does Not
>= 3 inches in diameter and >_
R-6 where< 3 inches. Supply and ❑Not Observable
return ducts in other portions of ❑Not Applicable
the building insulated >= R-6 for
diameter>=3 inches and R-4.2
for<3 inches in diameter.
403.3.2 Ducts, air handlers and filter ❑Complies
[FR13]1 boxes are sealed with ❑Does Not
joints/seams compliant with
International Mechanical Code or []Not Observable
International Residential Code,as ❑Not Applicable
applicable.
403.3.5 Building cavities are not used as ❑Complies
[FR15]3 ducts or plenums. ❑Does Not
❑Not Observable
❑Not Applicable
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 4 of 9
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.
ID
403.3.7 Ducts declared to be within the ❑Complies
[FR28]3 conditioned space are either 1) ❑Does Not
completely within the continuous
air barrier and within the building []Not Observable
thermal envelope, 2)buried ❑Not Applicable
within ceiling insulation in
accordance with Section
R403.3.6 and the air handler is
located completely within the
continuous air barrier and within
the building thermal envelope
and the duct leakage is<= 1.5
cfm/100 square feet of
conditioned floor area served by
the duct system, or 3)the ceiling
insulation R-value installed
against and above the insulated
duct>=to the proposed ceiling
insulation R-value, less the R-
value of the insulation on the
403.4 HVAC piping conveying fluids R- R- ❑Complies
[FR17]2 above 105 OF or chilled fluids ❑Does Not
below 55 OF are insulated to >_R-
❑
3 Not Observable
❑Not Applicable
403.4.1 Protection of insulation on HVAC ❑Complies
[FR24]1 piping. ❑Does Not
[]Not Observable
❑Not Applicable
403.5.3 Hot water pipes are insulated to R- R- ❑Complies
[FR18]2 >_R-3. ❑Does Not
[]Not Observable
❑Not Applicable
403.6 Automatic or gravity dampers are ❑Complies
[FR19]2 installed on all outdoor air []Does Not
intakes and exhausts.
❑Not Observable
[]Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 5 of 9
Section Plans Verified Field Verified
# Insulation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
303.1 All installed insulation is labeled ❑Complies
[IN13]2 or the installed R-values ❑Does Not
provided. ❑Not Observable
❑Not Applicable
402.1.1, Wall insulation R-value. If this is a R- R- ❑Complies See the Envelope Assemblies
402.2.5, mass wall with at least Yz of the ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.6 wall insulation on the wall ❑ Mass ❑ Mass ❑Not Observable
[IN3]1 exterior,the exterior insulation
requirement applies(FR10). ❑ Steel ❑ Steel ❑Not Applicable
303.2 Wall insulation is installed per ❑Complies
[IN4]1 manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 6 of 9
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.1, ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.2. ❑ Steel ❑ Steel ❑Not Observable
402.2.E
❑
[FI1]1 Not Applicable
303.1.1.1, Ceiling insulation installed per ❑Complies
303.2 manufacturer's instructions. ❑Does Not
(F12]1 Blown insulation marked every
❑
300 ft2.. Not Observable
❑Not Applicable
402.2.3 Vented attics with air permeable ❑Complies
[FI22]2 insulation include baffle adjacent ❑Does Not
to soffit and eave vents that
extends over insulation. ❑Not Observable
❑Not Applicable
402.2.4 Attic access hatch and door R- R- ❑Complies
[FI3]1 insulation >_R-value of the ❑Does Not
adjacent assembly.
❑Not Observable
El Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50= ❑Complies
[FI17]1 ach in Climate Zones 1-2, and ❑Does Not
<=3 ach in Climate Zones 3-8.
❑Not Observable
❑Not Applicable
403.3.3 Ducts are pressure tested to cfm/100 cfm/100 ❑Complies
[FI27]1 determine air leakage with ft2 ft2 ❑Does Not
either: Rough-in test:Total
leakage measured with a ❑Not Observable
pressure differential of 0.1 inch ❑Not Applicable
w.g.across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g.across the entire system
including the manufacturer's air
handler enclosure.
403.3.4 Duct tightness test result of<=4 cfm/100 cfm/100 ❑Complies
[FI4]1 cfm/100 f:2 across the system or ft2 ft2 ❑Does Not
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in []Not Observable
tests,verification may need to ❑Not Applicable
occur during Framing Inspection.
403.3.2.1 Air handler leakage designated ❑Complies
[FI24]1 by manufacturer at<=2%of ❑Does Not
design air flow.
[]Not Observable
❑Not Applicable
403.1.1 Programmable thermostats ❑Complies
[FI9]2 installed for control of primary ❑Does Not
heating and cooling systems and
initially set by manufacturer to ❑Not Observable
code specifications. ❑Not Applicable
403.1.2 Heat pump thermostat installed ❑Complies
[F110]2 on heat pumps. ❑Does Not
❑Not Observable
❑Not Applicable
403.5.1 Circulating service hot water ❑Complies
[FI11]2 systems have automatic or ❑Does Not
accessible manual controls.
❑Not Observable
❑Not Applicable
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 7 of 9
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 All mechanical ventilation system ❑Complies
[FI25]2 fans not part of tested and listed ❑Does Not
HVAC equipment meet efficacy
and air flow limits per Table ❑Not Observable
R403.6.1. ❑Not Applicable
403.2 Hot water boilers supplying heat ❑Complies
[FI26]2 through one-or two-pipe heating ❑Does Not
systems have outdoor setback
control to lower boiler water ❑Not Observable
temperature based on outdoor ❑Not Applicable
temperature.
403.5.1.1 Heated water circulation systems ❑Complies
[F128]2 have a circulation pump.The ❑Does Not
system return pipe is a dedicated
return pipe or a cold water supply []Not Observable
pipe.Gravity and thermos- ❑Not Applicable
syphon circulation systems are
not present.Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
403.5.1.2 Electric heat trace systems ❑Complies
[FI29]2 comply with IEEE 515.1 or UL ❑Does Not
515.Controls automatically
adjust the energy input to the ❑Not Observable
heat tracing to maintain the []Not Applicable
desired water temperature in the
piping.
403.5.2 Demand recirculation water ❑Complies
[F130]2 systems have controls that ❑Does Not
manage operation of the pump
and limit the temperature of the ❑Not Observable
water entering the cold water ❑Not Applicable
piping to <= 1042F.
403.5.4 Drain water heat recovery units ❑Complies
[FI31]2 tested in accordance with CSA ❑Does Not
B55.1. Potable water-side
pressure loss of drain water heat []Not Observable
recovery units <3 psi for ❑Not Applicable
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
individual units connected to
three or more showers.
404.1 90%or more of permanent ❑Complies
[F16]1 fixtures have high efficacy lamps. ❑Does Not
❑Not Observable
❑Not Applicable
404.1.1 Fuel gas lighting systems have ❑Complies
[FI23]3 no continuous pilot light. ❑Does Not
❑Not Observable
[]Not Applicable
401.3 Compliance certificate posted. ❑Complies
[F[7]2 ❑Does Not
❑Not Observable
[]Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 8 of 9
Section Plans Verified Field Verified
• # Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
303.3 Manufacturer manuals for ❑Complies
[FI18]3 mechanical and water heating ❑Does Not
systems have been provided.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: ranch Report date: 12/03/20
Data filename: Page 9 of 9
Above-Grade Wall 21.00
Below-Grade Wall 15.00
Floor 0.00
Ceiling / Roof 49.00
Ductwork (unconditioned spaces):
Window 0.27
Door } �� r0.30
Heating System•
Cooling System•
Water Heater•
Name• Date:
Comments