Signed Inspection Report (Tue May 24, 2022 at 1127 AM)INSPECTION WORKSHEET (PTI-018488-2022)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:PT-0304-2022 Case Module:Permit
Inspection Date:Tue May 24, 2022 Inspection Status:Failed
Inspector:O'Brien, John Inspection Type:Property Transfer Inspections
Job Address:Parcel Number:119 BIG BAY RD
Queensbury, NY, 12804
316.13-1-1
Contact Type Company Name Name
Primary Owner Sung, Steve
Primary Owner Sung, Linda
Applicant Sung, Linda
Contractor Sanitary Sewer Service
Checklist Item Status
Building Inspector Notes Failed
5/24/22 Property Transfer Inspection Not Approved
- One Drywell is completely full and other Drywell is 3/4 full.
- Access risers required on both covers of existing septic tank. Cover is 3-1/2' down from grade.
- A new absorption is required existing drywells have failed. Septic tank is a minimum of a 1000 gallon tank and
can be reused.
- Sewer line from home to tank needs to be replaced. The pipe is thin wall pvc and it appears to pitch back toward
home.
- Replace d-box
Weather Passed
Sunny
Temperature (Fahrenheit)Passed
61 degrees
Test each fixture flow to septic tank Failed
May 24, 2022 Page (1)
INSPECTION WORKSHEET (PTI-018488-2022)
Checklist Item Status
Whirlpool tub add 250 gal Failed
Garbage grinder add 250 gal Failed
Leaking water fixtures Failed
Plumbing fixtures tested & confirmed - for flow and point of discharge Failed
Access riser? (if yes, depth to cover)Failed
Depth below grade to top of tank Failed
3-1/2' risers needed
Septic outlet cover ext - Reg 12"+ below grade Failed
Septic inlet cover ext - Reg 12"+ below grade Failed
Inlet baffle Failed
Liquid level AT/ABOVE/BELOW (one) discharge invert Passed
At
Number of tank compartments Passed
One
May 24, 2022 Page (2)
INSPECTION WORKSHEET (PTI-018488-2022)
Checklist Item Status
Capacity in gallons Passed
1000 gallon may be 1250
D-box material Failed
Recommend replacing
Seepage Pits: Number Failed
2 Drywells one failed and one near failure.
System appears to have functioned adequately Failed
System/components indicate unacceptable Failed
Recommend upgrade/expand/replace 1+ components Failed
Replace Drywells
As-built provided is accurate Failed
On-site as-built req'd before insp is complete Failed
System needs repairs Failed
System passes all function testing Failed
5/24/22 Property Transfer Inspection Not Approved
- One Drywell is completely full and other Drywell is 3/4 full.
- Access risers required on both covers of existing septic tank. Cover is 3-1/2' down from grade.
- A new absorption is required existing drywells have failed. Septic tank is a minimum of a 1000 gallon tank and
can be reused.
- Sewer line from home to tank needs to be replaced. The pipe is thin wall pvc and it appears to pitch back toward
home.
- Replace d-box
May 24, 2022 Page (3)
O'Brien, John