Loading...
Mezzanine Framing Calculations 8-21-22 September 2, 2022 Gross Electric, Inc. 27 Silver Circle Queensbury, N.Y. 12804 Attn: Ai Gordon Project Manager SUBJECT: Brookfield Power HVAC Mezzanine Access Framing Analysis Dear Ai, I have reviewed the light gage framing for the HVAC access mezzanine recently installed at the new Brookfield Power building in Queensbury, New York. Based on my structural analysis of the light gage framing members, the mezzanine framing, as provided on the reference drawings, is adequate to support the project design load. The mezzanine platform design loads used for this project are 10 psf. dead and 60 psf. live. For the mezzanine support studs I used a 5 psf. wind load in addition to the mezzanine framing design loads. I have attached the backup calculations and support documentation for the mezzanine analysis as the Town of Queensbury has been asking for this type of documentation for other types of projects I have worked on in this town. I trust this information will satisfy your needs. Please call with any questions. Yours truly, Michael Hutsenpiller, P.E. President Cc: File MRH Engineering, P.C. 20 Bayberry Drive Queensbury, N.Y. 12804 Project Gross Electric Job Ref. 22-54 Section Brookfield Mezzanine Light Gage Sheet no./rev. 1 Calc. by MRH Date 9/3/2022 Chk'd by MRH Date 9/3/2022 App'd by MRH Date 9/3/2022 Design Loads Mezzanine Dead Load; Rd = 15 psf Mezzanine Live Load = 60.00 psf Joist 1 Light Gage Design (Use 8” 16 Ga x 13’-0” long light gage joist) Uniform dead load =; 10 * 1.33 = 13.300; plf Uniform floor live load =; 60 * 1.333 = 79.980; plf Total uniform dead + live + snow load = 13.33 plf dead + 79.98 plf live From the printout “Joist 1 Mezzanine Framing” use an 800S162-54 @ 16” c-c End reaction = 607 lbs. Joist 2 Light Gage Design (Use 6” 16 Ga x 11’-6 1/4” long light gage joist) Uniform dead load =; 15 * 1.33 = 19.950; plf Use 20 plf. dead Uniform floor live load =; 60 * 1.33 = 79.800; plf Use 80 plf live Total uniform dead + live + snow load = 20 plf dead + 80 plf live From the printout “Joist 2 Mezzanine Framing” use an 600S162-54 @ 16” c-c End reaction = 538 lbs. Exterior Wall Stud Design (Use 3 1/2” 16 Ga wall studs with spazzer bridging at 4’-0” c-c) Wall stud dead load =; 13.33 * 13 /2 = 86.645; lbs dead Use 87 lbs. dead Add 100 plf dead for wall stud load above the mezzanine. Total wall stud dead load =; 87 + 100 =187.000; dead Wall stud live load =; 80.00 * 13 /2 = 520.000; lbs dead Use 520 lbs. live Total wall stud load =; 187 + 520 = 707.000; lbs. Wall stud wind load =; 5 * 1.33 = 6.650; Use 7.0 plf From the printout “Wall Stud 1” use an 350S162-54 @ 16” c-c Header 1 Design (Use (2) 8” 16 Ga x 4’-0” long light gage joist with a 4’-8” span) Uniform dead load =; 10 * 4.67/2 = 23.350; plf Use 24 plf. Add 100 plf for wall load above Total dead load =; 24 + 100 = 124.000; plf dead MRH Engineering, P.C. 20 Bayberry Drive Queensbury, N.Y. 12804 Project Gross Electric Job Ref. 22-54 Section Brookfield Mezzanine Light Gage Sheet no./rev. 2 Calc. by MRH Date 9/3/2022 Chk'd by MRH Date 9/3/2022 App'd by MRH Date 9/3/2022 Uniform floor live load =; 60 * 4.67/2 = 140.100; plf Use 141 plf live Total uniform dead + live + snow load = 124 plf dead + 141 plf live = 265 plf total From the printout “Header 1” use an (2) 800S162-54 @ 16” c-c End reaction = 530 lbs. Header 2 Design (Use (2) 8” 16 Ga x 13’-9” long light gage joist with a 6’-0” span) Uniform dead load =; 10 * 13.75/2 = 68.750; plf Use 69 plf dead Add 100 plf for wall load above Total dead load =; 69 + 100 = 169.000; plf dead Uniform floor live load =; 60 * 13.75/2 = 412.500; plf Use 413 plf live Total uniform dead + live + snow load =; 169 plf dead + 413 plf live = 582 plf total From the printout “Header 2” use an (2) 800S162-54 @ 16” c-c End reaction = 1746 lbs. Connection Design (Use #10-16 Hilti Screws) Joist 1 end reaction = 607 lbs. Allowable shear load per ICC report ESR-3332 = 395 lbs per screw (see page 5 of 9 per the ICC report) Number or scews required =; 607 / 395 = 1.537; screws Use (3) #10-16 Hilti screws Hat Channel Column Design (Model Hat Channel as a 1 ½ x 1 ½ x 16 ga column x 4’-0” long (maximum wind girt spacing) Maximum hat channel column load = 538 lbs. This is the end reaction for Joist #2 1 ½ x 1 ½ x 16 ga column x 4’-0” long modeled for the hat channel used for this project. From the printout “Hat Channel” the use of the 1 ½ x 1 ½ x 16 ga column x 4’-0” long model supports the 538 lbs design load. The interaction value = .49 Section : 800S162-54 (50 ksi) Single C Stud Maxo =3065.9 Ft-Lb Fy =50 ksi 2091.3 lbVa =Moment of Intertia, I =5.600 in^4 Joist Spacing = Total Load - 240 Live Load - 240 1. DL + LL All spans 2. DL + LL Even spans 3. DL + LL Odd spans 4. LL All spans 5. LL Even spans 6. LL Odd spans Deflection Limits: Load Cases: 16 in Mmax Ft-Lb K-phi lb-in/in Lm in Ma-dist Ft-Lb Mmax/Ma (Min) Load Case Total Ld Defl Load Case LL Defl Load Case Joist Flexural and Deflection Summary Span 1972 0.0 52.0 2734.3 0.721 1 L/430 1 L/501 4 Rxn Load (lb) Bearing (in) Pa (lb) Pn (lb) Max Intr. Load Case Stiffeners Required Joist Bending and Web Crippling Summary Load Case R1 606.7 1.25 614.9 1076.1 0.51 1 NO1 R2 606.7 1.25 614.9 1076.1 0.51 1 NO1 Rxn Vmax (lb) Load Case Va Factor V/Va M/Ma Intr. Unstiffened Intr. Stiffened Joist Bending and Shear Summary Load Case Load Case R1 606.7 1 0.29 0.00 0.29 N/A1.000 1 N/A R2 606.7 1 0.29 0.00 0.29 N/A1.000 1 N/A www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Joist 1 Model:Joist 1 Mezzanine Framing 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Section : 600S162-54 (50 ksi) Single C Stud Maxo =2527.1 Ft-Lb Fy =50 ksi 2822.9 lbVa =Moment of Intertia, I =2.860 in^4 Joist Spacing = Total Load - 240 Live Load - 240 1. DL + LL All spans 2. DL + LL Even spans 3. DL + LL Odd spans 4. LL All spans 5. LL Even spans 6. LL Odd spans Deflection Limits: Load Cases: 16 in Mmax Ft-Lb K-phi lb-in/in Lm in Ma-dist Ft-Lb Mmax/Ma (Min) Load Case Total Ld Defl Load Case LL Defl Load Case Joist Flexural and Deflection Summary Span 1548 0.0 46.1 2158.3 0.717 1 L/315 1 L/368 4 Rxn Load (lb) Bearing (in) Pa (lb) Pn (lb) Max Intr. Load Case Stiffeners Required Joist Bending and Web Crippling Summary Load Case R1 537.6 1.25 641.0 1121.8 0.44 1 NO1 R2 537.6 1.25 641.0 1121.8 0.44 1 NO1 Rxn Vmax (lb) Load Case Va Factor V/Va M/Ma Intr. Unstiffened Intr. Stiffened Joist Bending and Shear Summary Load Case Load Case R1 537.6 1 0.19 0.00 0.19 N/A1.000 1 N/A R2 537.6 1 0.19 0.00 0.19 N/A1.000 1 N/A www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Joist 2 Model:Joist 2 Mezzanine Framing 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Section : 350S162-54 (50 ksi) Single C Stud Maxo =1061.7 Ft-Lb 3371.6 lbVa =I =0.80 in^4 Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations Flexural and Deflection Check Span Mmax Ft-Lb Mmax/ Maxo Mpos Ft-Lb Bracing (in) Ma(Brc) Ft-Lb Mpos/ Ma(Brc) Deflection (in)Ratio Span 87.5 0.082 87.5 60.0 884.9 0.099 0.046 L/2583 Span Distortional Buckling Check K-phi lb-in/in Lm Brac in Ma-d Ft-Lb Mmax/ Ma-d Span 0.00 120.0 1087.2 0.080 Reaction or Pt Load Load P(lb) Bearing (in) Pa (lb) Pn (lb) Mmax (Ft-Lb) Intr. Value Stiffeners Required? Combined Bending and Web Crippling R2 35.0 --Shear Connection w/ clip-- NO R1 35.0 --Shear Connection w/ clip-- NO www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Wall Stud Model:Mezzanine Wall Stud 2012 NASPEC [AISI S100-2012]Code: Page 1 of 2 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Reaction or Pt Load Vmax (lb) Mmax (Ft-Lb) Va Factor V/Va M/Ma V + M Intr. Combined Bending and Shear R1 35.0 0.0 0.04 0.00 0.040.28 R2 35.0 0.0 0.04 0.00 0.040.28 Combined Bending and Axial Load Details Span Axial Ld (lb)KyLy KtLt Max KL/r K-phi (lb-in/in) Lm Bracing (in) Allow load(lb)P/Pa Intr. Value Bracing(in) Span 707.0(c)60.0 99 0.0 120.0 2841.8(c)60.0 0.25 0.36 Support Rx(lb)Ry(lb)Simpson Strong-Tie Connector Connector Interaction Anchor Interaction Simpson Strong-Tie Connectors 4.40 %R2 35.00 0 4.61 %SCB45.5(2) & (2) #12 SST X to A36 Steel 58.54 %R1 35.00 707 51.04 %FCB43.5 Min(4#12-14) & (4) #12 SST X to A36 Steel Span/CantiLever Bracing Length (in.) Design Number of Braces Pn(lb.) SUBH (Min)¹ SUBH (Max)¹ MSUBH (Min)¹ Simpson Strong-Tie Wall Stud Bridging Connectors MSUBH (Max)¹ LSUBH (Min)¹ LSUBH (Max)¹ Design Method = AISI S100 Span 60 0.0 No Soln No Soln No Soln2 No SolnNo Soln No Soln 1) Values in parentheses are stress ratios. 2) Bridging connectors are not designed for back-back,box, or built-up sections. 3) Reference Notes: 4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same. 5) If the bracing length is larger than the span length, bridging connectors are not designed. for latest load data, important information, and general notes www.strongtie.com www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Wall Stud Model:Mezzanine Wall Stud 2012 NASPEC [AISI S100-2012]Code: Page 2 of 2 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Section : (2) 800S162-54 (50 ksi) Boxed C Stud Maxo =6131.8 Ft-Lb 4182.6 lbVa =I =11.20 in^4 Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations Flexural and Deflection Check Span Mmax Ft-Lb Mmax/ Maxo Mpos Ft-Lb Bracing (in) Ma(Brc) Ft-Lb Mpos/ Ma(Brc) Deflection (in)Ratio Span 530.0 0.086 530.0 Full 6131.8 0.086 0.003 L/14842 Reaction or Pt Load Load P(lb) Bearing (in) Pa (lb) Pn (lb) Mmax (Ft-Lb) Intr. Value Stiffeners Required? Combined Bending and Web Crippling R2 530.0 1.00 1149.1 2010.9 0.0 0.24 NO R1 530.0 1.00 1149.1 2010.9 0.0 0.24 NO Reaction or Pt Load Vmax (lb) Mmax (Ft-Lb) Va Factor V/Va M/Ma V + M Intr. Combined Bending and Shear R1 530.0 0.0 0.13 0.00 0.131.00 R2 530.0 0.0 0.13 0.00 0.131.00 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Header 1 Model:Beam/Stud –1 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Section : (2) 800S162-54 (50 ksi) Back-To-Back C Stud Maxo =6131.8 Ft-Lb 4182.6 lbVa =I =11.20 in^4 Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations Flexural and Deflection Check Span Mmax Ft-Lb Mmax/ Maxo Mpos Ft-Lb Bracing (in) Ma(Brc) Ft-Lb Mpos/ Ma(Brc) Deflection (in)Ratio Span 2619.0 0.427 2619.0 Full 6131.8 0.427 0.036 L/2002 Span Distortional Buckling Check K-phi lb-in/in Lm Brac in Ma-d Ft-Lb Mmax/ Ma-d Span 0.00 72.0 5468.6 0.479 Reaction or Pt Load Load P(lb) Bearing (in) Pa (lb) Pn (lb) Mmax (Ft-Lb) Intr. Value Stiffeners Required? Combined Bending and Web Crippling R2 1746.0 1.63 3279.5 6559.0 0.0 0.23 NO R1 1746.0 1.63 3279.5 6559.0 0.0 0.23 NO Reaction or Pt Load Vmax (lb) Mmax (Ft-Lb) Va Factor V/Va M/Ma V + M Intr. Combined Bending and Shear R1 1746.0 0.0 0.42 0.00 0.421.00 R2 1746.0 0.0 0.42 0.00 0.421.00 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Header 2 Model:Header 2 2012 NASPEC [AISI S100-2012]Code: Page 1 of 1 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 Section : 150S150_25-51(50 ksi) Single C Stud Maxo =289.2 Ft-Lb 1260.9 lbVa =I =0.10 in^4 Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations If a span has a bracing setting larger than the span, the bracing is set to the span lengthFlexural and Deflection Check Span Mmax Ft-Lb Mmax/ Maxo Mpos Ft-Lb Bracing (in) Ma(Brc) Ft-Lb Mpos/ Ma(Brc) Deflection (in)Ratio Span 14.0 0.048 14.0 48.0 266.1 0.053 0.010 L/4889 Span Distortional Buckling Check K-phi lb-in/in Lm Brac in Ma-d Ft-Lb Mmax/ Ma-d Span 0.00 48.0 307.8 0.045 Reaction or Pt Load Load P(lb) Bearing (in) Pa (lb) Pn (lb) Mmax (Ft-Lb) Intr. Value Stiffeners Required? Combined Bending and Web Crippling R2 14.0 1.00 629.2 1101.0 0.0 0.01 NO R1 14.0 1.00 629.2 1101.0 0.0 0.01 NO Reaction or Pt Load Vmax (lb) Mmax (Ft-Lb) Va Factor V/Va M/Ma V + M Intr. Combined Bending and Shear R1 14.0 0.0 0.01 0.00 0.011.00 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Hat Channel Model:Hat Channel 2012 NASPEC [AISI S100-2012]Code: Page 1 of 2 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5 R2 14.0 0.0 0.01 0.00 0.011.00 Combined Bending and Axial Load Details Span Axial Ld (lb)KyLy KtLt Max KL/r K-phi (lb-in/in) Lm Bracing (in) Allow load(lb)P/Pa Intr. Value Bracing(in) Span 538.0(c)48.0 91 0.0 48.0 1253.7(c)48.0 0.43 0.49 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC. Project Name:Hat Channel Model:Hat Channel 2012 NASPEC [AISI S100-2012]Code: Page 2 of 2 Date: 09/03/2022 Simpson Strong-Tie® CFS Designer™ 3.2.0.5