CC-0572-2022 Office Use Only
ADDITION/ALTERATION PERMIT Permit#: CC-G 5-72— Zc12`z.
Town ofQneensbury A Permit Fee:$
742 Bay Road,Queensbury,NY 12804 D H V E ^��
P:518-761-8256 www. ueensbu .ne SEP Invoice#:—.:� ' —
�Q
14 ZOZZ Flood Zone? Y No Reviewed By:
TOWN OF QUEENSgU
1N
Project Location: a� l 01-x BUIL C SR4 "L1(Oct wcurre- CV';4/ , 1V V
Tax Map ID#: 303a%5-1-9 Subdivision Name:
PROJECT INFORMATION:
TYPE: ❑ Residential R" Commercial, Proposed Use: Wi'bt6-c&1t-(-1WorJ%ov&<-
❑ Single-Family ❑ Two-Family ❑ Multi-Family (#of units_) ❑ Townhouse
-❑ Business Office ❑ Retail Industrial/Warehouse ❑ Garage (#of cars )
❑ Other(describe )
ADDITION SQUARE FOOTAGE: ALTERATION SQUARE FOOTAGE:
1st floor: 1st floor: ,
2nd floor: 2nd floor:
3rd floor: 3rd floor:
Basement (habitable space): Basement (habitable space):
Total sq ft: Total sq
Scope of work to be done: 5-e- "4t'j� Sk"
Addition/Alteration Application Revised June 2022
ADDITIONAL PROJECT INFORMATION:
1. Estimated Cost of Construction: $ 33,S Sy
2. Source of Heat (circle one): E(Gas ❑ Oil ❑ Propane ❑ Solar ❑ Other:
Fireplaces/inserts need a separate Fuel Burning Appliances & Chimney Application
3. Are there any structures not shown on the plot plan? ❑ YES CN 0 Explain:
4. Are there any easements on the property? ❑ YES E? NO
SITE INFORMATION:
• Is this a corner lot? ❑ YES ZNO
• Will the grade be changed as a r sult of the construction? ❑ YES 2 NO
• What is the water source? 19 PUBLIC ❑ PRIVATE WELL
• What type of wastewater system is on the parcel? 21SEWER ❑ PRIVATE SEPTIC
DECLARATION:
1. 1 acknowledge that no construction shall be commenced prior to the issuance of a valid permit and will be
completed within a 12 month period.Any changes to the approved plans prior to/during construction will require
the submittal of amended plans,additional reviews and re-approval.
2. If,for any reason,the building permit application is withdrawn,30%of the fee is retained by the Town of
Queensbury.After 1 year from the initial application date, 100%of the fee is retained.
3. If the work is not completed by the 1 year expiration date the permit may be renewed, subject to fees
and department approval.
4. 1 certify that the application, plans and supporting materials are atrue and a complete statement and/or description
of the work proposed,that all work will be performed in accordance with the NYS Building Codes, local building laws
and ordinances, and in conformance with local zoning regulations.
5. 1 acknowledge that prior to occupying the facilities proposed I, or my agents, will obtain a certificate of
occupancy.
6. 1 also understand that I/we are required to provide an as-built survey by a licensed land surveyor of all newly
constructed facilities prior to issuance of certificate of occupancy.
I have read and agree to the above:
PRINT NAME:
r�5 (1e.-�MCLL
SIGNATURE: DATE:
Addition/Alteration Application Revised June 2022
CONTACT INFORMATION: PLEASE PRINT LEGIBLY OR TYPE, PLEASE INCLUDE AN EMAIL
• Applicant:
Name(s): Sup& Co �^c.
Mailing Address, C/S/Z: a?5 Rif M`( . 11-14Y
Cell Phone:(_) Land Line: ((Pal ) 7P-7700
Email: me'cer-,Svo�kV .CV-1
• Primary Owner(s):
Name(s): ,
Mailing Address, C/S/Z: XY3�- z ColorJet P-4-!.y w.40w, AIV, 13_�IK
Cell Phone: ( Land Line: fo( 0-7 ) `747-7700
EmaiL. teQ t r ear
❑ Check if all work will be performed by property owner only
• Contractor(s): (List all additional contractors on the back of this form)
Contact Name(s): MP -eCAr-%c of
Contractor Trade: Bli-P_4 '1cu l
Mailing Address, C/S/Z: Q.c). box `i30`A, Ali, 1.)-80LI
Cell Phone:_( Land Line: ( 519 ) 'N I -t989
Email: d4;ce Co►^^
"Workers' Comp documentation must be submitted with this application"
• Architect(s)/Engineer(s):
Business Name:
Contact Name(s):
Mailing Address, C/S/Z:
Cell Phone:_�) Land Line: � )
Email:
Contact Person for Compliance in regards to this project: S '0,aWm\o�l(
Cell Phone: b4!5 ) '7Lt l -4Ooo Land Line: (o0_)
Email: VAotke4 . Q
Addition/Alteration Application Revised June 2022
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contractor Name(s):Cr s—fQil` 1;ra�-
Contractor Trade: wAr--
Mailing Address, C/S/Z: 9-5 ►.�� nul P,/L'j- A\&-`'y NY taacl(o
Cell Phone: Land Line: S«S- u4Q-PfSa
Email: t7iavd-11Ie..y®cr:Sbredee��,
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contractor Name(s):L o"
Contractor Trade: RSR\104 /a1"Y'*OP
Mailing Address, C/S/Z: 70 Tlvo1, s} wtb°`�y aa��
Cell Phone: Land Line: 51
Email: 5ato t Coe'\
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contractor Name(s): !1Ae: "Peky
Contractor Trade: 4VAC-
Mailing Address, C/S/Z: aZ5' (Q—meNe- coc'pocll.� kfiL*4� 00*"O``\J"IY 137�tS
Cell Phone: Land Line: &07`747-17700
Email: i��I1�n c�rne �P1Y, coc+-%
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contractor Name(s): -r=XecA\-Z Cf "`"� '`�e� e f- Almo-y,^C
Contractor Trade: r--r'e-`\7 ju'c
Mailing Address, C/S/Z: 9,0 . �aX (oOV C"k`m"' I �` ��Z7
Cell Phone: Land Line: :;'1fS
�o►,.-� � aScoa�C'Y,Xec1�i h35e„er„c�4 ,c��►'►
• Contractor(s): Workers' Comp documentation must be submitted with this application
Contractor Name(s):
Contractor Trade:
Mailing Address, C/S/Z:
Cell Phone: Land Line:
Email:
Addition/Alteration Application Revised June 2022
Scope Of Work
• Clean HVAC System in offices,training, and showroom areas.
• HVAC Ai.r Balancing Test will be performed by a certified mechanical air balancer. Please provide
name of certified company.
• All existing and new electrical work will be inspected by a certified electrical inspector approved
by the Town of Queensbury.
• Overhead garage fire doors at firewalls will be inspected and a new fusible link installed. Provide
inspection from certified inspector.
• All required exit doors to pavement need to be asphalt paved to existing pavement due to
tripping hazard.
• All existing and new doors will have lever handle hardware installed.
• Handicapped parking space and access aisle in front of main door will be striped in blue.The
parking space will have the wheelchair emblem and the access aisle will have blue stripes. Each
space must be 8'wide.
• Install a handicapped parking sign on wall in front of parking space. 60" high from pavement to
bottom of sign
• Install a no parking sign on wall of building in front of access aisle in front of main door. 60" high
from pavement to bottom of sign.
• Install handicapped unisex bathroom sign on wall lever handle side of bathroom door.Sign
should be 60"to center of sign to finish floor.
• Repair any ceiling grid that needs attention and replace damaged ceiling tile.
• Install an ADA compliant counter in showroom.
• Install Slot Wall in the showroom.
• Replace any broken floor tiles.
• ADA approved bathroom conversion.
• Spackle and paint showroom and training room.
• Replace dual doors (1 in showroom & 1 in training room)
• Strip and rewax flooring
°� Lo
FIRE DOOR MO .. TEST
WOO..M�R:
APD`tESS:
T62�e�,� a
-DOOR: 90DEL .
SIZE x
DRIVE LH RH r
FE183UILDING
Eo' W
DIXON'SERIAL NUMBER: .�—' -, ' - SEP 1 k 2022
LABEL OR CERTIFICATE'NUMBERWN OF`QUEENSBURY& CODES
NAME:
DROP TEST'CHECK POINTS: k
1. Fire door desoeri'ded-to the fully cjggq4,.pqsltlon.
. Fire door recharged-after test.
3. Fusible Ilnlcs and release levers Installed and reset. ; ''•
���FeCATION
1,#%understgned,witnessed the drop test of the above fire door The fire ddor,when released,did-descend fothb fully
closed.position.
Looal pafe
Title:
lnatallerg Signature Data n
I
303.15-1-4 CC-0572-2022
Meier Supply Co., Inc. gsra
281 Dix Ave. i1
Commercial Alterations
1• II
ME DOOR -DROP TEST
CU5'IQ:MI=R:
ADD�IESS:
/tit G1 �. -7y o
°
-DOOR: MODELEC CS 0. V `'
SIZE X D
DRIVE •LH RH 'SEP 14 2022
TOWN OF QUEENSBURY ......
-BUILDING&CODES
DIXON"SERIAL NUMBER:
I_AB�L OR.CERTiFICATE'NUMBER:.`
�$ NAME: lt(
• ' . •� a rr���r!�LLLLLL •
DROP TEST CHECK POINTS:
1. Fire door desoeridetl to the fully clgsgd,.pgsitlon.
2. Fire door recharged'after test.
3. Pusfble links and release lever8 Installed and reset,
ctBir pATI®N
I,thb;undersigned,witnessed the drop test of the above fire door The fire ddor,when released;did•desbend fo thb fully
olosi%.positlon.
- •`- 22
•t.00al Date
Title:
Installer's Signature Date t
303.15-1-4 CC-0572-2022
11e1.87 5s7b2�z
Meier Supply Co., Inc. ;P
h
281 Dix Ave. I�
Commercial Alterations
FIRE MARSHAL'S OFFICE
Town of Queensbunj
742 Bay Road, Queensbury, NY 12804
"Home of Natural Beauty ... A Good Place to Live "
PLAN REVIEW
Meier Supply
281 Dix Avenue
CC-0572-2022 F1Lt COPY
9/20/2022
The following comments are based on a review of submittals:
• Verify fire extinguisher location and inspection
• Verify paths of egress
• Verify storage
• Verify clearances to electrical service panel
• CO detection is required
• Verify function of Exit/ emergency lighting
• Install Knox Box and provide entry key
• Provide disposition on existing fire alarm panel and smoke detectors in
whse
• FM to provide Emergency Contact Form
Michael J Palmer
Fire Marshal
742 Bay Road
Queensbury NY 12804
firemarshal@queensbury.net
Fire Marshal 's Office ■ Phone: 518-761-8206 Fax: 518-745-4437
flremarshal@queensbunl.net - 7MMqueensburil net
FIRM:
MTI - Mechanical Testing, Inc.
4 Chelsea Place, Suite 102
Clifton Park NY 12065
PHONE:
(518) 450-7292
FAX:
(518) 450-7295
CUSTOMER:
Meier Supply Company
PROJECT #:
22-495
PROJECT ADDRESS:
281 Dix Avenue
Queensbury NY 12804
DATE:
2022-09-08
CONTACT:
Kevin Greenwood
Meier Supply-Airflows
4 Chelsea Pl, Suite 102 Clifton Park, NY 12065 Phone: 518-450-7292 Fax: 518-450-7295 Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections
Terms and Abbreviations
ACH- Air Changes per Hour
AHU- Air Handling Unit
AK- Free Area of Duct
AVG- Average
BHP- Brake Horsepower
BV- Ball Valve (Shut Off Valve)
CB- Circuit Breaker
CBV- Calibrated Balance Valve
CD-Ceiling Diffuser
CFM- Cubic Feet per Minute
CHWS- Chilled Water System
CRAC- Computer Room Air Conditioner
CS- Circuit Setter
CUH- Cabinet Unit Heater
DAT- Discharge Air Temperature
DD- Direct Drive (motor)
Des.- Design
Disch.- Discharge
DNE- Does Not Exist
DP- Discharge Pressure of Pump/Pressure Drop
EA- Exhaust Air
EAV- Exhaust Air Valve
EAT- Entering Air Temperature
EF- Exhaust Fan
EG- Exhaust Grille
ERU- Energy Recovery Unit
E.S.P.- External Static Pressure
EWT- Entering Water Temperature
FCU- Fan Coil Unit
FD- Fire Damper
FLA- Full Load Amperage
Flow Coeff. –Correction Factor for Flow to VAV
Flow Hood- Instrument that measures airflow
FPM- Feet per Minute GPM- Gallons Per Minute
HEPA- High Efficiency Particulate Arrestance
HP- Horsepower
HVAC- Heating Ventilation and Air Conditioning
HWS- Hot Water System
HX- Heat Exchanger
Hz- Hertz
In.- Inches
In. w.g.- Inches of Water Gauge
ISDFT- Insufficient Straight Duct for Traverse
Kfactor- Correction factor to the free area
needed to calculate CFM.
LAT- leaving Air Temperature
LWT- Leaving Water Temperature
MAU- Make Up Air Handling Unit
MAX- Maximum set point/flow
MIN- Minimum set point/flow
NI-Not Installed
NIS-Not in Scope
O/A- Outside Air
OBD- Opposed Blade Damper
OD- Outside Diameter Measurement of Sheave
PH- Phase
PSI- Pounds per Square Inch
RA- Return Air
RAT- Return Air Temperature
RF- Return Fan
RHC- Reheat Coil
RPM- Revolutions per Minute
RTU- Roof Top Unit
SA- Supply Air
SAV- Supply Air Valve
SAT- Supply Air Temperature
S.F.- Service Factor
SF- Supply Fan
SP- Suction Pressure of Pump/ Static Pressure
Sq. ft.- Square Feet
TAB- Test, Adjust and Balance
TDV- Triple Duty Valve
TP- Thermally Protected
TSP- Total Static Pressure
UH- Unit Heater
V- Volts
VAV- Variable Air Volume Box
VD- Volume Damper
VFD- Variable Frequency Drive
VVT- Variable Volume Terminal
WC- Water Column
3
3
5
5
12
Table of Contents
Instruments Used
Instruments Used
Roof Top Units
RTU-001*
RTU-002*
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
Page 2 of 18 2022-09-08
Instruments Used
Instruments Used
AIR
Manufacturer Evergreen Telemetry Calibration Date 11/5/21
Model No.S-PVF-1 Tech Name Kevin Greenwood
Serial No.1600243
WATER
Manufacturer Not Applicable Calibration Date Not Applicable
Model No.Not Applicable Tech Name Kevin Greenwood
Serial No.Not Applicable
ALTERNATE METER
Meter Type Not Applicable Serial No.Not Applicable
Manufacturer Not Applicable Calibration Date Not Applicable
Model No.Not Applicable
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
Instruments Used Page 3 of 18 2022-09-08
Air
IMAGES:
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
Instruments Used Page 4 of 18 2022-09-08
Design Actual %Design Actual %
Roof Top Units
RTU-001*
UNIT DATA
Equipment Location Roof Filter Type Pleated
Area Served Showroom/Training Filter Quantity 4
Unit Manufacturer Lennox Filter Size (inches)16x20x2
Unit Model No.TGA150S2BH1Y Performed By KG
Unit Serial No.5608F06508 Pass/Fail Survey
RTU-001* / Test Data*
TEST DATA
Total Unit CFM Not Listed
CFM 4580 CFM O/A Damper Position 10 %
Outlet CFM Not Listed
CFM 4580 CFM R/A Damper Position 90 %
Outside Air CFM Not Listed
CFM 335 CFM Discharge Air temp 68.4 deg F
Return Air CFM Not Listed
CFM 4245 CFM Hertz at Design CFM 60 Hz
Fan RPM Not Listed
RPM 1211 RPM Test Date 9/7/22
RTU-001* / Motor Data*
MOTOR DATA
Motor Manufacturer Baldor Volts T1 210 Volts
Motor Frame 184T Volts T2 210 Volts
Motor RPM 1750 RPM Volts T3 210 Volts
Motor Horsepower 5 HP Plate Amps 14.3 Amps
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 5 of 18 2022-09-08
Design Actual %Design Actual %
Motor Phase 3 Amps T1 12.80 Amps
Motor Hertz 60 Hz Amps T2 12.30 Amps
Service Factor 1.15 Amps T3 12.80 Amps
Efficiency 0.875 Starter Heater CB
Power Factor 0.780 Brake Horsepower 4.254
Plate Volts 208 Volts
MOTOR DATA
RTU-001* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 6” OD Fan Bore 1 in
Motor Bore 1 1/8 in No. of Belts 1
Motor Sheave % Closed 25 %Belt Size A51
Fan Sheave/OD Size 7 1/2” OD Center Distance 17 in
RTU-001* / Test Pressures*
TEST PRESSURES
Total Static Pressure Not Listed in.
H2O 2.20 in. H2O Pre-Filter DP Not Listed in.
H2O 0.90 in. H2O
External Static Pressure Not Listed in.
H2O 1.30 in. H2O Pre-Heat DP Not Applicable
in. H2O
Not Applicable
in. H2O
Discharge Static + 0.68 in. H2O Cooling Coil DP Not Listed in.
H2O 0.90 in. H2O
Suction Static -1.52 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O -0.62 in. H2O Sys. Operational Static Not Applicable in. H2O
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 6 of 18 2022-09-08
Photo's
NOTES:
Test Pressures
Pre-Filter DP
Filters and coil are back to back.
RTU-001* / Photos*
PHOTO'S
Unit Photo
IMAGES:
RTU-001* / Static Profile*
STATIC PROFILE
Static Profile
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 7 of 18 2022-09-08
IMAGES:
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 8 of 18 2022-09-08
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 9 of 18 2022-09-08
RTU-001* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Outside Air OA Intake 28x23 4.470 Not Listed 75 335 Not Applicable
Totals 0 335
RTU-001* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-001 Showroom SD 24x24 1.000 Not Listed 298 298 298
SO-002 Showroom SD 24x24 1.000 Not Listed 417 417 417
SO-003 Showroom SD 24x24 1.000 Not Listed 366 366 366
SO-004 Showroom SD 24x24 1.000 Not Listed 338 338 338
SO-005 Showroom SD 24x24 1.000 Not Listed 382 382 382
SO-006 Showroom SD 24x24 1.000 Not Listed 392 392 392
SO-007 Showroom SD 24x24 1.000 Not Listed 239 239 239
SO-008 Showroom SD 24x24 1.000 Not Listed 308 308 308
SO-009 Showroom SD 14x6 1.000 Not Listed 105 105 105
SO-010 Bathroom SD 24x24 1.000 Not Listed 30 30 30
SO-011 Bathroom SD 6 0.196 Not Listed 105 105 21
SO-012 Office SD 24x24 1.000 Not Listed 88 88 88
SO-013 Training SD 24x24 1.000 Not Listed 245 245 245
SO-014 Training SD 24x24 1.000 Not Listed 236 236 236
SO-015 Training SD 24x24 1.000 Not Listed 225 225 225
SO-016 Training SD 24x24 1.000 Not Listed 156 156 156
SO-017 Training SD 24x24 1.000 Not Listed 329 329 329
SO-018 Training SD 24x24 1.000 Not Listed 405 405 405
Totals 0 4580
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 10 of 18 2022-09-08
RTU-001* / Return Inlet Summary
RETURN INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
RI-001 Showroom RR 24x24 1.100 Not Listed 620 620 682
RI-002 Showroom RR 24x24 1.100 Not Listed 462 462 508
RI-003 Showroom RR 24x24 1.100 Not Listed 443 443 487
RI-004 Showroom RR 24x24 1.100 Not Listed 426 426 469
RI-005 Showroom RR 24x24 1.100 Not Listed 49 49 54
RI-006 Office RR 24x24 1.100 Not Listed 168 168 185
RI-007 Training RR 24x24 1.100 Not Listed 414 414 455
RI-008 Training RR 24x24 1.100 Not Listed 431 431 474
RI-009 Training RR 24x24 1.100 Not Listed 374 374 411
RI-010 Training RR 24x24 1.100 Not Listed 450 450 495
Totals 0 4220
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-001*Page 11 of 18 2022-09-08
Design Actual %Design Actual %
RTU-002*
UNIT DATA
Equipment Location Roof Filter Type Pleated
Area Served Offices Filter Quantity 2
Unit Manufacturer Carrier Filter Size (inches)16x24x2
Unit Model No.48HJE006-541 Performed By KG
Unit Serial No.3605G20334 Pass/Fail Survey
RTU-002* / Test Data*
TEST DATA
Total Unit CFM Not Listed
CFM 1417 CFM O/A Damper Position 10 %
Outlet CFM Not Listed
CFM 1417 CFM R/A Damper Position 90 %
Outside Air CFM Not Listed
CFM 310 CFM Discharge Air temp 68.3 deg F
Return Air CFM Not Listed
CFM 1107 CFM Hertz at Design CFM 60 Hz
Fan RPM Not Listed
RPM 1250 RPM Test Date 9/7/22
NOTES:
Test Data
Total Unit CFM
There was insufficient straight duct for accurate Supply and return main traverses. Supply total calculated by total of outlets. Return total calculated by subtracting the OA from SA.
RTU-002* / Motor Data*
MOTOR DATA
Motor Manufacturer GE Volts T1 210 Volts
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 12 of 18 2022-09-08
Design Actual %Design Actual %
Motor Frame 56Y Volts T2 210 Volts
Motor RPM 1725 RPM Volts T3 209 Volts
Motor Horsepower Not Listed HP Plate Amps 5.2 Amps
Motor Phase 3 Amps T1 3.40 Amps
Motor Hertz 60 Hz Amps T2 3.40 Amps
Service Factor 1.15 Amps T3 3.50 Amps
Efficiency 0.850 Starter Heater CB
Power Factor 0.850 Brake Horsepower 1.196
Plate Volts 208 Volts
MOTOR DATA
NOTES:
Motor Data
Efficiency
The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
RTU-002* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size 4” OD Fan Bore 5/8 in
Motor Bore 5/8 in No. of Belts 1
Motor Sheave % Closed 25 %Belt Size A40
Fan Sheave/OD Size AK44 Center Distance 15 in
RTU-002* / Test Pressures*
TEST PRESSURES
Total Static Pressure Not Listed in.
H2O 1.26 in. H2O Pre-Filter DP Not Listed in.
H2O 0.24 in. H2O
External Static Pressure Not Listed in.
H2O 1.02 in. H2O Pre-Heat DP Not Applicable
in. H2O
Not Applicable
in. H2O
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 13 of 18 2022-09-08
Design Actual %Design Actual %
Discharge Static + 0.56 in. H2O Cooling Coil DP Not Listed in.
H2O 0.24 in. H2O
Suction Static -0.70 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP
Not Listed in.
H2O -0.46 in. H2O
Sys. Operational Static Not Applicable in. H2O
TEST PRESSURES
NOTES:
Test Pressures
Pre-Filter DP
Filters and coil are back to back.
RTU-002* / Photos*
PHOTO'S
Unit Photo
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 14 of 18 2022-09-08
Photo's
IMAGES:
RTU-002* / Static Profile*
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 15 of 18 2022-09-08
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 16 of 18 2022-09-08
RTU-002* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Outside Air*OA Intake 24x23 3.830 Not Listed 81 310 Not Applicable
Totals 0 310
RTU-002* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-001 Room 4 SD 24x24 1.000 Not Listed 109 109 109
SO-002 Room 1 SD 14x6 1.000 Not Listed 166 166 166
SO-003 Room 2 SD 14x6 1.000 Not Listed 131 131 131
SO-004 Room 3 SD 14x6 1.000 Not Listed 169 169 169
SO-005 Backroom SD 14x6 1.000 Not Listed 145 145 145
SO-006 Backroom SD 14x6 1.000 Not Listed 184 184 184
SO-007 Backroom SD 14x6 1.000 Not Listed 62 62 62
SO-008 Backroom SD 8 1.000 Not Listed 451 451 451
Totals 0 1417
NOTES:
Supply Outlet Summary
SO-008 / Final CFM
Flex and SD removed, open ended duct.
RTU-002* / Return Inlet Summary
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 17 of 18 2022-09-08
RETURN INLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
RI-001 Room 1 RR 24x24 1.100 Not Listed 86 86 95
RI-002 Room 3 RR 10 0.545 Not Listed 500 500 273
RI-003 Backroom RR 24x24 1.100 Not Listed 82 82 90
RI-004 Backroom RR 24x24 1.100 Not Listed 110 110 121
RI-005 Backroom RR 24x24 1.100 Not Listed 130 130 143
Totals 0 722
NOTES:
Return Inlet Summary
RI-002 / Final CFM
Flex disconnected from tap, open ended duct.
PROJECT NUMBER:
22-495
CONTACT:
Kevin Greenwood
LOCATION:
Meier Supply-Airflows
281 Dix Avenue
Queensbury NY 12804
RTU-002*Page 18 of 18 2022-09-08