Mechanical Testing ^�Z1
MAT"i E1013
Sustainable Solutions for
Efficient Environments
Ste warts Quaker Road Queensbury
Addition
FIRM: CUSTOMER:
MTI -Mechanical Testing, Inc. Hilltop Construction
PROJECT#:
4 Chelsea Place,Suite 102 22-244
Clifton Park NY 12065
PROJECT ADDRESS:
PHONE: 777 Quaker Road
(518)450-7292, Queensbury NY
FAX: DATE:
(518)450-7295 2022-05-06
CONTACT:
Jeff Paro
Cal Testlq
OpJP��C W
;/'`:MEN"m
O
OWNED0
dJ�F � CERTIFIED BY I NAT INSBUSI NSS ENTERPRISE
This is to certify that Mechanical Testing, Inc. has balanced the systems described herein to
their optimum performance capabilities. The testing and balancing has been performed in
accordance with the standard requirements of the Associated Air Balance Council and the
results of these tests are herein recorded.
m
MANTi
Sustainable Solutions for
Efficient Environments
4 Chelsea PI,Suite 102 Clifton Park,NY 12065
Phone:518-450-7292 Fax:518-450-7295
Design Review-Commissioning-Fire Life Safety-Test And Balance-ASHRAE 110-Drone Sales/Inspections
Terms and Abbreviations In:Inches
In.w.g.-Inches of Water Gauge
ACH-Air Changes per Hour ISDFT-Insufficient Straight Duct for Traverse
AHU-Air Handling Unit Kfactor-Correction factor to the free area
AK-Free Area of Duct needed to calculate CFM.
AVG-Average LAT-leaving Air Temperature
BHP-Brake Horsepower LWT-Leaving Water Temperature
BV-Ball Valve(Shut Off Valve) MAU-Make Up Air Handling Unit
CB-Circuit Breaker MAX-Maximum set point/flow
CBV-Calibrated Balance Valve MIH-Minimum set point/flow
CD-Ceiling Diffuser HI-Not Installed
CFM-Cubic Feet per Minute HIS-Not in Scope
CHWS-Chilled Water System 0/A-Outside Air
CRAC-Computer Room Air Conditioner OBD-Opposed Blade Damper
CS-Circuit Setter OD-Outside Diameter Measurement of Sheave
CUH-Cabinet Unit Heater PH-Phase
DAT-Discharge Air Temperature PSI-Pounds per Square Inch
DD-Direct Drive(motor) RA-Return Air
Des.-Design RAT-Return Air Temperature
Disch:Discharge RF-Return Fan
DHE-Does Not Exist RHC-Reheat Coil
DP-Discharge Pressure of Pump/Pressure Drop RPM-Revolutions per Minute
EA-Exhaust Air RTU-Roof Top Unit
EAV-Exhaust Air Valve SA-Supply Air
EAT-Entering Air Temperature SAV-Supply Air Valve
EF-Exhaust Fan SAT-Supply Air Temperature
EG-Exhaust Grille S.F.-Service Factor
ERU-Energy Recovery Unit SF-Supply Fan
E.S.P.-External Static Pressure SP-Suction Pressure of Pump/Static Pressure
EWT-Entering Water Temperature Sq.ft.-Square Feet
FCU-Fan Coil Unit TAB-Test,Adjust and Balance
FD-Fire Damper TOV-Triple Duty Valve
FLA-Full Load Amperage TP-Thermally Protected
Flow Coeff.—Correction Factor for Flow to VAV TSP-Total Static Pressure
Flow Hood-Instrument that measures airflow UH-Unit Heater
FPM-Feet per Minute GPM-Gallons Per Minute V-Volts
HEPA-High Efficiency Particulate Arrestance VAV-Variable Air Volume Box
HP-Horsepower VD-Volume Damper
HVAC-Heating Ventilation and Air Conditioning VFD-Variable Frequency Drive
HWS-Hot Water System VVT-Variable Volume Terminal
HX-Heat Exchanger WC-Water Column
Hz-Hertz
MT1 0 Lq 13
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road Queensbury Addition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
Table of Contents
Instruments Used 3
Instruments Used 3
...I. ... ............... . .......... . ... ............
Bard Unit O/A* 5
_. . ... . ...... ..... ... .
Traverse Summary 5
Exhaust Inlets* 6
Exhaust Inlet summary,.. 6
Blower Door Test 7
3/24/2022-Blower Door Test 7
.... . .......... .......... .I.. .. ......... ............ _....... . ...... ..... .... .
Page 2 of 7 2022-05-06
Ti
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road Queensbury Addition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
Instruments Used
Instruments Used
AIR
Manufacturer Evergreen Calibration Date 7121
Model No: S-PVF-1 Tech Name Jeff Paro
Serial No. 1700220
WATER
Manufacturer Not Applicable Calibration Date Not Applicable
Model No. Not Applicable Tech Name: Not Applicable
Serial No. Not Applicable
ALTERNATE METER
Meter Type Not Applicable Serial No., Not Applicable
Manufacturer Not Applicable Calibration Date, Not Applicable
Model No. Nat Applicable
Instruments Used Page 3 of 7 2022-05-06
MTi 0 Uq 13
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road Queensbury Addition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
IMAGES:
Air
N� ,5� �,'°!Lw..2iu'g,R a w:':-G ,�1.`• .: ',i i«.�<y�'„
Vr+Wawnri k1fR4WE8'tltdiEl�ytt.�,y� �„ie'J .,, ,_ s
1L Yt !}176.1•.,,i� �.� '�"' tWrUegf..lvJiNrsLtlB.L%'.'�,��..�•
awaeww. r6LNr. .• -,,i� aawyros e�.eM
2miMmcbi.Rt'h091 `;'��y,'�Iv4y�; 1':i'am.r.�Mrr�s;' t
ltCsWa Mrv`pvwYe nNw�mwl.wavwgaµwY4+una,•3•"'�''�����
yMNWmuHs?ebbaubrWCVyxanue�lLnppAy�w+r�uatl Wow NMWu "�
ptlTpRm'.y2II+5>7.wmWtaey,e0K1m:p+�}Nammay�ml>afwaWvtur d
IMnmsalMOdppm4� /216MbSt3?2d/10G«»9a zrJ9a.sae E�rrw.11m '.
NN �
.er(p.aseaa.,rpew,n wn+mmrat+as++wfoa+rswn+r,ne+rdrosmpaw�usR.;c
tqa�OM><'u:nbMR�bwrdmjmwO.roNtl#M4+,a1F�igRptimwam n0^'upW
I wwm Rli Atm.",,: ., �rawl.h HAtl NrYppk krWiu'eaf
.. N RNJk'2' � •'y„rp,�y." M' �,:/�fsiiic M+anM�'
nU'Fl- ..:aYR,tmvtcrtlWriFurn+OivYlMiau2.8fCrra,...,., �.9aAAt;'^@�µl�-"_";
.CiaM�'-,�.Mm[.pPi@uvi@'�9sOmbIM,W�MYMi.3-Wf0}R�Fi..t.GbP'A1i!„b>,(,MtM2W�i�
.�:Whv�.:,mT4VrtirA Jl,arolAYe. Mp0.pElk'fi.W6vttt.rt �'M.a1AiS uy,i�T!'1wIDG ,.
',n+rxra r±gapwxrir<",'Mx(iatl 4„'.,', j':mwrilt vv:�0uvpq
v.Crnlat��, urritx�w6nmteHpv:r•.• ••;.,i"�. • t Yls,f��%p'PDJS '
�.A�xr3@.Mr'9✓>IMViIti[r4R'•,'id"'' .
q;,usrma.
mw�cw,tlrinwanter ,�„ ',�;'a,".ft�;.t.roam:x» "no.tm2"me
Mp+2Ga2 .k6 MI .itswlai 0te �A� ^r'�',
Instruments Used Page 4 of 7 2022-05-06
1
MTi 131013
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road QueensburyAddition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
Bard Unit OIA*
Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Bard-1 Bard OA 32x7 1.560 Not'Applicable 66 103 Not Applicable
Totals 0 103
NOTES:
Traverse Summary
Bard-1 f Average FPM
Per the Stewan's HVAC tech on site,the Outside Air is factory set and not manually adjustable.MTI read and recorded the flow.
Traverse Summary Page 5 of 7 2022-05-06
MTi PL-713
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road Queensbury Addition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
Exhaust Inlets*
Exhaust Inlet Summary
EXHAUST INLET SUMMARY
Name Room No: Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM %of Design
EI-001 Toilet EG 12x12 1.100 45 50 42 42 46 92
EI-002 Kitchen EG 12x12 1.100 68 75 62 62 68 91
Totals 125 114
NOTES:
Exhaust Inlet Summary
EI.0011 Room No.
Fan unit appears to be existing.Possibly sized for 50 ctm.
Exhaust Inlet Summary Page 6 of 7 2022-05-06
M v
Ti
CIO
Sustainable Solutions for
Efficient Environments
LOCATION: PROJECT NUMBER: CONTACT:
Stewarts Quaker Road Queensbury Addition 22-244 Jeff Paro
777 Quaker Road
Queensbury NY
Blower Door Test
3/24/2022 - Blower Door Test
TEST INFO
Date of Test 3/24/2022 Leakage Code, 0.40
Technician Name Austin Roggen PasslFail "' Pass
TEST DATA
Floor Plan Area 297 sq.ft No.of TestsPerformed. - 3 CFM
.Enclosed;Volume 2970 Test Average 615 CFM
Envelope Surface Area 1602 sq.ft Air Changes Per Hour 12.42'
Test Pressure -75.00 kPa Leakage Per SF 0.38
IMAGES:
Test Data
V iy�fll �
d
Pti
e. 0
u {{ u
w
d
3/24/2022-Blower Door Test Page 7 of 7 2022-05-06