Memorandum
To: Craig Brown
From: Mike Shaw
Date: July 11, 2005
Re: Turnberry — SB 4-2005 Sanitary Sewer Plan Review
Sheet SP2
Residential buildings are connected to Towns' Sanitary Sewer. Building
laterals need to be cut and capped and inspected by Wastewater personnel
prior to demolition.
Sheet SP3
Pocket pond must stay outside Sanitary Sewer easement. Also, the easement
area cannot be fenced in.
Sheet SP4
Storm sewer piping must stay outside of the Sanitary Sewer easement.
Sheet SP6
Each building will need a backwater valve and main line "U" trap'in the
buildings interior plumbing.
The developer must provide for a daily sanitary sewer inspector. NYSPE must