TAB Report 12-21-22 22-723FIRM:
MTI - Mechanical Testing, Inc.
4 Chelsea Place, Suite 102
Clifton Park NY 12065
PHONE:
(518) 450-7292
FAX:
(518) 450-7295
CUSTOMER:
Eastern Heating & Cooling
PROJECT #:
22-723
PROJECT ADDRESS:
578 Aviation Mall Road
Queensbury NY
DATE:
2022-12-21
CONTACT:
Kevin Greenwood
Planet Fitness Queensbury: Functional
Training Room
4 Chelsea Pl, Suite 102 Clifton Park, NY 12065 Phone: 518-450-7292 Fax: 518-450-7295 Design Review - Commissioning - Fire Life Safety - Test And Balance - ASHRAE 110 -Drone Sales/Inspections
Terms and Abbreviations
ACH- Air Changes per Hour
AHU- Air Handling Unit
AK- Free Area of Duct
AVG- Average
BHP- Brake Horsepower
BV- Ball Valve (Shut Off Valve)
CB- Circuit Breaker
CBV- Calibrated Balance Valve
CD-Ceiling Diffuser
CFM- Cubic Feet per Minute
CHWS- Chilled Water System
CRAC- Computer Room Air Conditioner
CS- Circuit Setter
CUH- Cabinet Unit Heater
DAT- Discharge Air Temperature
DD- Direct Drive (motor)
Des.- Design
Disch.- Discharge
DNE- Does Not Exist
DP- Discharge Pressure of Pump/Pressure Drop
EA- Exhaust Air
EAV- Exhaust Air Valve
EAT- Entering Air Temperature
EF- Exhaust Fan
EG- Exhaust Grille
ERU- Energy Recovery Unit
E.S.P.- External Static Pressure
EWT- Entering Water Temperature
FCU- Fan Coil Unit
FD- Fire Damper
FLA- Full Load Amperage
Flow Coeff. –Correction Factor for Flow to VAV
Flow Hood- Instrument that measures airflow
FPM- Feet per Minute GPM- Gallons Per Minute
HEPA- High Efficiency Particulate Arrestance
HP- Horsepower
HVAC- Heating Ventilation and Air Conditioning
HWS- Hot Water System
HX- Heat Exchanger
Hz- Hertz
In.- Inches
In. w.g.- Inches of Water Gauge
ISDFT- Insufficient Straight Duct for Traverse
Kfactor- Correction factor to the free area
needed to calculate CFM.
LAT- leaving Air Temperature
LWT- Leaving Water Temperature
MAU- Make Up Air Handling Unit
MAX- Maximum set point/flow
MIN- Minimum set point/flow
NI-Not Installed
NIS-Not in Scope
O/A- Outside Air
OBD- Opposed Blade Damper
OD- Outside Diameter Measurement of Sheave
PH- Phase
PSI- Pounds per Square Inch
RA- Return Air
RAT- Return Air Temperature
RF- Return Fan
RHC- Reheat Coil
RPM- Revolutions per Minute
RTU- Roof Top Unit
SA- Supply Air
SAV- Supply Air Valve
SAT- Supply Air Temperature
S.F.- Service Factor
SF- Supply Fan
SP- Suction Pressure of Pump/ Static Pressure
Sq. ft.- Square Feet
TAB- Test, Adjust and Balance
TDV- Triple Duty Valve
TP- Thermally Protected
TSP- Total Static Pressure
UH- Unit Heater
V- Volts
VAV- Variable Air Volume Box
VD- Volume Damper
VFD- Variable Frequency Drive
VVT- Variable Volume Terminal
WC- Water Column
3
3
4
4
Table of Contents
Instruments Used*
Instruments Used
RTU-4
RTU-4*
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
Page 2 of 8 2022-12-21
Instruments Used
Instruments Used*
Instruments Used
INSTRUMENTS USED
Name Instrument Manufacturer Model #Serial #Calibration Date Measures Tech Name
Instruments Used Air Data Evergreen Telemetry S-PVF-1 2100097 9/8/22 Airflow Kevin Greenwood
IMAGES:
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
Instruments Used Page 3 of 8 2022-12-21
Design Actual %Design Actual %
RTU-4
RTU-4*
UNIT DATA
Equipment Location Roof Filter Type Throwaway
Area Served Functional Training Filter Quantity 2
Unit Manufacturer Bryant Filter Size (inches)16x24x2
Unit Model No.582KE05A110A2A0AAA Performed By KG
Unit Serial No.2622C06915 Pass/Fail Pass
RTU-4* / Test Data*
TEST DATA
Total Unit CFM 1600 CFM 1626 CFM 102 O/A Damper Position 20 %
Outlet CFM 1600 CFM 1609 CFM 101 R/A Damper Position 80 %
Outside Air CFM 400 CFM 422 CFM 106 Discharge Air temp 134.2 deg F
Return Air CFM 1200 CFM 1204 CFM 100 Hertz at Design CFM High 7.0 volts Hz
Fan RPM Not Listed
RPM
Direct Drive
RPM Test Date 12/20/22
RTU-4* / Motor Data*
MOTOR DATA
Motor Manufacturer See note Volts T1 460 Volts
Motor Frame See note Volts T2 460 Volts
Motor RPM See note RPM Volts T3 460 Volts
Motor Horsepower 2.0 HP Plate Amps 1.5 Amps
Motor Phase 3 Amps T1 0.90 Amps
Motor Hertz 60 Hz Amps T2 0.90 Amps
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
RTU-4*Page 4 of 8 2022-12-21
Design Actual %Design Actual %
Service Factor 1.0 Amps T3 0.90 Amps
Efficiency 0.850 Starter Heater Electronically Protected
Power Factor 0.850 Brake Horsepower 0.694
Plate Volts 460 Volts
MOTOR DATA
NOTES:
Motor Data
Motor Manufacturer
There is no motor tag located on motor.
Efficiency
The Efficiency and Power Factor are not listed on the motor tag. MTI used the industry standard of 0.85 for each to determine an ESTIMATED BHP.
RTU-4* / Drive Data*
DRIVE DATA
Motor Sheave/OD Size Direct Drive Fan Bore Direct Drive in
Motor Bore Direct Drive in No. of Belts Direct Drive
Motor Sheave % Closed Direct Drive %Belt Size Direct Drive
Fan Sheave/OD Size Direct Drive Center Distance Direct Drive in
RTU-4* / Test Pressures*
TEST PRESSURES
Total Static Pressure Not Listed in.
H2O 1.02 in. H2O Pre-Filter DP Not Listed in.
H2O 0.17 in. H2O
External Static Pressure 0.75 in. H2O 0.85 in. H2O 113 Pre-Heat DP Not Applicable
in. H2O
Not Applicable
in. H2O
Discharge Static 0.43 in. H2O Cooling Coil DP Not Listed in.
H2O 0.17 in. H2O
Suction Static -0.59 in. H2O Static at Furthest VAV Not Applicable in. H2O
Mix Box/Pre-Filter SP Not Listed in.
H2O -0.42 in. H2O Sys. Operational Static Not Applicable in. H2O
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
RTU-4*Page 5 of 8 2022-12-21
Photo's
RTU-4* / Photos
PHOTO'S
Unit Photo
IMAGES:
RTU-4* / Static Profile
STATIC PROFILE
Static Profile
IMAGES:
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
RTU-4*Page 6 of 8 2022-12-21
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
RTU-4*Page 7 of 8 2022-12-21
RTU-4* / Traverse Summary
TRAVERSE SUMMARY
Name System Location Size Area Design FPM Design CFM Average FPM Actual CFM Static Pressure
Return Air RTU-4 Main RA 17x17 2.000 600 1200 602 1204 -0.030
Outside Air RTU-4 Intake 24x23 3.840 104 400 110 422 Not Applicable
Totals 1600 1626
RTU-4* / Supply Outlet Summary
SUPPLY OUTLET SUMMARY
Name Room No.Type Size AK Factor Design FPM Design CFM Reading 1 Reading 2 Final CFM % of Design
SO-1 Functional Training S-2 18x10 1.000 400 400 451 388 388 97
SO-2 Functional Training S-2 18x10 1.000 400 400 522 412 412 103
SO-3 Functional Training S-2 18x10 1.000 400 400 499 407 407 102
SO-4 Functional Training S-2 18x10 1.000 400 400 590 402 402 101
Totals 1600 1609
PROJECT NUMBER:
22-723
CONTACT:
Kevin Greenwood
LOCATION:
Planet Fitness Queensbury: Functional Training Room
578 Aviation Mall Road
Queensbury NY
RTU-4*Page 8 of 8 2022-12-21