blower door test
Envelope Leakage Test Testing Company: Technician: Name: LoCascio Energy Solutions Name: Anthony LoCascio Address: 20 Ogden Rd. Credentials: HERS Rater#4242961 Queensbury,, NEW YORK 12804 Phone: 5188573144 Email: tony@locascioenergysolutions.com Building Information: Customer Information: Project ID: 12 Shore. Name: J. Clarke Construction Address: 12 Shore Acres Address: Queensbury, NY 12804 Geo-Tag Data: Latitude: 43.466729 E C 9 W F -Longitude: -73.640709 p Timestamp: 2021-07-13 11:57:18F 1111 14 0-1 Measured Leakage: 197.8 CFM50 W -- TOWN OF QUEENSBURY Test ID: 12 BUILDING&CODES Purpose of Test: 50 Pa Env. Leakage Measured ACH50: 1.43 Effective Leakage Area: 10.9 in Building Volume: 8,300.0 ft- Enclosure Surface Area: 500.0 ft2 Coefficient(C): 15.6 Exponent(n): 0.650(assumed) Test Standard: RESNET 380 One-Point Test Mode: Depressurize Test Characteristics: Indoor Temp: 68 °F Outdoor Temp: 72 °F Altitude: 320.0 ft Time Average Period: 10 seconds Test Date and Time: 2021-07-13 13:05:14 300 • Depressurize)— ' { 260 - - --i coo QQ - - 50 40 _- ---- - ---' 30`-- i F 4 5 6 7 8 -9 10 20 30 40 50 60 Building Pressure(Pa) Envelope Leakage Test Test Readings: Target(Pa). Bldg-(Pa) Adj Blda(Pa) Fan (Pa) Flow(cfm) Confia Baseline 0.4 -50.0 -48.5 -49.0 -73.3 193.6 Ring C Test Equipment: Flow Device: Model 3 110V Fan Serial#: 3173 Custom Calibration Date:2021-02-10 Pressure Gauge: DG1000 Serial#: 3173 Calibration Date: 2019-02-18 s Deviations from Standard: • None Comments: None Report by TEC Auto Test 1.8.0 (210),©2021 The Energy Conservatory, Inc. Page 2 of 2