19 MANOR DRIVE UNIT D - Blower DoorDate:
City: Queensbury State: NY Zip: 12804
Phone #518-793-7277 Email:
City: QUEENSBURY State: NY Zip: 12804
Phone # Email:
1336 square ft.
Volume =
Blower Door Diagnostics: Ring
Inside Temp: 65 Baseline Pressure -50 Pa.A
Outside Temp: 35 Fan Pressure Pa.B
C8
475 cfm@50
New York State Requires builders run a blower door test on new residential
buildings to ensure a maximum air leakage of three air changes per hour (ach50).
*ACH test results are considerably lower than building standards. Mechanical
Ventilation is highly recommended.
Blower Door testing performed by:
Jack Hall Home Energy Services
165 Bay St
Glens Falls, NY 12801
518-412-7505 ID: 1015618
Ventilation requirements:
Building has a HRV installed.YES NO
2/27/2023Contractor: Clute Enterprises, Inc
Maximum CFM 50 to achieve less than 3 ACH = 561
Volume: 11220 x 3 = 33660 /60 = 561 CFM @ 50
CFM@50 x 60 / Volume = 2.54 ach
Open
Actual Flow @ CFM50 =
(Height x Living) + (Height x Basement) X 3 / 60 = ACH per Hour
BLOWER DOOR TEST FORM