IM Inspection Worksheet_24-08-2023_14-01-49INSPECTION WORKSHEET (COMFIN-027376-2023)
CC-0494-2023Case Number:Case Module:Permit Management
08/24/2023 FailedInspection Status:Inspection Date:
Commercial Final InspectionInspection Type:Inspector:John O'Brien
Job Address:Parcel Number:1135 Ridge Rd
Queensbury, NY 12804
279.18-1-6
Company Name NameContact Type
Applicant Jennifer Islas
Contractor Herm Delsignore
Granted Permission Jennifer Islas
Primary Owner Jennifer Islas
Checklist Item CommentsPassed
Low flow toilet 1.3 gal/flushing cycle True
Handicapped Ramps True
Building Inspector Notes False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
Bldg Access All Sides 20ft Drivable Surface True
H/C rear grab bar 36" with 24" to open side True
Public Toilet Room Handicapped Accessible True
Handicap parking striping False - Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
Int/Ext Balusters 4 inch Spacing Platform Decks True
Bldg Num or Tenant Address on Bld or Drive False - Need to verify 911 address on building facing road.
As-built Septic System Layout Required True
12" beyond top & bottom False
Int/Ext Guardrails 42 inch Platform Decks True
August 24, 2023 Page 1 of 3
INSPECTION WORKSHEET (COMFIN-027376-2023)
Checklist Item CommentsPassed
H/C side & rear grab bars 36" above floor True
H/C sinks 34" above floor True
H/C 18" minimum vertical grab bar True
H/C grab bar: 42" side, 12" from center True
OK to Issue C/O False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
Universal Symbol of Access displayed False
Final Electrical / Flex Gas Piping Bonded False - Submit Final Electrical Inspection for any additional wiring and
for heating and cooling system to be installed.
Plumbing Vent Through Roof/Roof complete True
Relief Valve ,Heat Trap/Water Temp 110 deg or less False
Handicapped Bath/Parking Lot Signage False - Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
Exits At Grade Or Platform 36 (w) x 44 (l)True
H/C mirrors 40" above floor False - Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
H/C toilet flush handle on open side True
August 24, 2023 Page 2 of 3
INSPECTION WORKSHEET (COMFIN-027376-2023)
Checklist Item CommentsPassed
OK to Issue Temporary C/O False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
H/C vertical grab bar 39" from floor and corner True
Site Plan Variance required False
Ext Finish /Grade Complete/6 in 10ft or Equivalent True
Step risers: riser 7" & treads 11"True existing to remain
Stair rail 34"–38": both sides of stairway False - Rear exit stairs from the stage needs handrail extended down
past last tread nosing by 12". The handrail is required to extend
12" passed top and bottom of stairs so dead end top just before
office door trim and ends of handrail must return into the wall at
the top and bottom of the stairs. Please make the handrail a
continuous height of 36" from edge of tread nosings the full length
of stairs.
Special Inspections False - Submit third party inspection report for wheelchair lift.
Doors 36 inch wLever Hand Panic Hardware, if req True
Floor Bathroom Watertight Other Floors Okay False - Seal around pipe penetrations through the handicapped
bathroom floor for a watertight seal.
August 24, 2023 Page 3 of 3