IM Inspection Worksheet_05-09-2023_11-11-01INSPECTION WORKSHEET (COMFIN-027541-2023)
CC-0494-2023Case Number:Case Module:Permit Management
09/05/2023 FailedInspection Status:Inspection Date:
Commercial Final InspectionInspection Type:Inspector:John O'Brien
Job Address:Parcel Number:1135 Ridge Rd
Queensbury, NY 12804
279.18-1-6
Company Name NameContact Type
Applicant Jennifer Islas
Contractor Herm Delsignore
Granted Permission Jennifer Islas
Primary Owner Jennifer Islas
Checklist Item CommentsPassed
Low flow toilet 1.3 gal/flushing cycle True
Handicapped Ramps True
Building Inspector Notes False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Install drain pipe trap wrap protector under handicapped sink.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
9/5/23 Commercial Interior Alteration Final Inspection Not
Approved
- Submit the Final Electrical Inspection for the installation of the
the Mini Split HVAC Units for the Multi-Purpose Room and heat for
the remainder of the main floor area.
- Submit a letter from the installer on their letter head certifying the
installation of the Mini Split HVAC Units were installed in
accordance with the manufacture's catalog cuts and
specifications and were sized to handle the square footage of the
Multi-Purpose Room.
Bldg Access All Sides 20ft Drivable Surface True
H/C rear grab bar 36" with 24" to open side True
September 05, 2023 Page 1 of 4
INSPECTION WORKSHEET (COMFIN-027541-2023)
Checklist Item CommentsPassed
Public Toilet Room Handicapped Accessible True
Handicap parking striping True - Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
Int/Ext Balusters 4 inch Spacing Platform Decks True
Bldg Num or Tenant Address on Bld or Drive True - Need to verify 911 address on building facing road.
As-built Septic System Layout Required True
12" beyond top & bottom True
Int/Ext Guardrails 42 inch Platform Decks True
H/C side & rear grab bars 36" above floor True
H/C sinks 34" above floor True
H/C 18" minimum vertical grab bar True
H/C grab bar: 42" side, 12" from center True
OK to Issue C/O False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
9/5/23 Commercial Interior Alteration Final Inspection Not
Approved
- Submit the Final Electrical Inspection for the installation of the
the Mini Split HVAC Units for the Multi-Purpose Room and heat for
the remainder of the main floor area.
- Submit a letter from the installer on their letter head certifying the
installation of the Mini Split HVAC Units were installed in
accordance with the manufacture's catalog cuts and
specifications and were sized to handle the square footage of the
Multi-Purpose Room.
Universal Symbol of Access displayed True
Final Electrical / Flex Gas Piping Bonded False - Submit Final Electrical Inspection for any additional wiring and
for heating and cooling system to be installed.
Plumbing Vent Through Roof/Roof complete True
September 05, 2023 Page 2 of 4
INSPECTION WORKSHEET (COMFIN-027541-2023)
Checklist Item CommentsPassed
Relief Valve ,Heat Trap/Water Temp 110 deg or less True
Handicapped Bath/Parking Lot Signage True - Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
Exits At Grade Or Platform 36 (w) x 44 (l)True
H/C mirrors 40" above floor True - Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
H/C toilet flush handle on open side True
OK to Issue Temporary C/O False 8/24/23 Commercial Final Inspection Not Approved
Remaining items:
- Rear exit stairs from the stage needs handrail extended down
past last step by 12". The handrail is required to extend 12"
passed top and bottom of stairs so dead end top just before office
door trim and ends of handrail must return into the wall at the top
and bottom of the stairs. Please make the handrail a continuous
height of 36" from front edge of steps the full length of stairs.
- Seal around pipe penetrations through the unisex handicapped
bathroom floor for a watertight seal.
- Install drain pipe trap wrap protector under handicapped sink.
- Lower mirror in handicapped bathroom so the bottom edge is
40" from finished floor.
- Install Unisex Handicapped Bathroom Sign to opposite side on
wall as discussed the height was fine.
- Install handicapped Access Aisle No Parking sign in grass as
discussed and Handicapped Parking sign in grass as discussed
on a pole with bottom of signs to be 60" high from pavement.
- Stripe(blue paint) handicapped access aisle and parking spot as
discussed. Access aisle has blue diagonal stripes and
handicapped parking spot will have wheelchair logo.
- Install electrical heating and cooling system
- Submit Final Electrical Inspection for any additional wiring and
for electrical heating and cooling system to be installed.
- Submit third party inspection report for wheelchair lift.
- Complete all Fire Marshal's Items.
- Need to verify 911 address on building facing road.
9/5/23 Commercial Interior Alteration Final Inspection Not
Approved
- Submit the Final Electrical Inspection for the installation of the
the Mini Split HVAC Units for the Multi-Purpose Room and heat for
the remainder of the main floor area.
- Submit a letter from the installer on their letter head certifying the
installation of the Mini Split HVAC Units were installed in
accordance with the manufacture's catalog cuts and
specifications and were sized to handle the square footage of the
Multi-Purpose Room.
H/C vertical grab bar 39" from floor and corner True
Site Plan Variance required False
Ext Finish /Grade Complete/6 in 10ft or Equivalent True
Step risers: riser 7" & treads 11"True existing to remain
September 05, 2023 Page 3 of 4
INSPECTION WORKSHEET (COMFIN-027541-2023)
Checklist Item CommentsPassed
Stair rail 34"–38": both sides of stairway True - Rear exit stairs from the stage needs handrail extended down
past last tread nosing by 12". The handrail is required to extend
12" passed top and bottom of stairs so dead end top just before
office door trim and ends of handrail must return into the wall at
the top and bottom of the stairs. Please make the handrail a
continuous height of 36" from edge of tread nosings the full length
of stairs.
Special Inspections True - Submit third party inspection report for wheelchair lift.
Doors 36 inch wLever Hand Panic Hardware, if req True
Floor Bathroom Watertight Other Floors Okay True - Seal around pipe penetrations through the handicapped
bathroom floor for a watertight seal.
September 05, 2023 Page 4 of 4