IM Inspection Worksheet_06-09-2023_14-41-56INSPECTION WORKSHEET (BINS-027585-2023)
RC-0743-2020Case Number:Case Module:Permit Management
09/06/2023 Partial PassInspection Status:Inspection Date:
Building InsulationInspection Type:Inspector:Mark Smith
Job Address:Parcel Number:23 St James Pl
Queensbury, NY 12804
309.10-1-97
Company Name NameContact Type
Applicant HAYES & HAYES LLC
Architect Rucinski-Hall Architecture
Contractor HAYES & HAYES LLC
Granted Permission HAYES & HAYES LLC
Primary Owner HAYES & HAYES LLC
Checklist Item CommentsPassed
Zip exterior sheathing, nailing & taping True Zip sheathing with 1" continuous insulation
Building Inspector Notes False 3/28/23 insulation not approved. Make the corrections discussed
on site, will recheck tomorrow morning.
3/29/23 partial approval for insulation
- thermal insulation approved for unit A only, basement not
completed
4/17/23 partial approval for insulation
- thermal insulation at unit B approved.
9/6/23 partial approval of insulation.
-basement insulation, units A & B approved.
U Factors = .3 cfm for windows, .5 cfm for doors True .29
Insulation under bow & bay window(s)False
Exterior wall outlets sealed True
All Return Air Hard Duct Work False
Duct work sealed properly / No duct tape False Duct work not completed
Duct Testing Outside Conditioned Space False
House Wrap Taped at all Seams True Zip system sheathing with seams taped
Door / Window Sealed (No Insulation)True
Air Seal Outside Penetrations True
All Ductwork Sealed Return and Supply False
Blower Door Test False
Duct Insulation - if required in unheated spaces False
Combustion Air Supply for Furnace False
Fresh air supply 3' from grade False
Window Sealing True
Duct Blaster Test for duct work, R-8, unhtd spaces False
Permit Card Visible From Road False
Insulation ResCheck ComCheck True R 49 in ceilings with R 21 in walls, zip sheathing with 1"
continuous insulation
September 06, 2023 Page 1 of 1