IM Inspection Worksheet_11-09-2023_14-27-31INSPECTION WORKSHEET (COMFIN-027630-2023)
CC-0265-2023Case Number:Case Module:Permit Management
ScheduledInspection Status:Inspection Date:
Commercial Final InspectionInspection Type:Inspector:Mark Smith
Job Address:Parcel Number:1424 State Rte 9
Lake George, NY 12845
288.16-1-1
Company Name NameContact Type
Architect Kenneth Park Architect
Contractor Herman Stewart Construction & Development Inc
Granted Permission Columbia Sportswear Co
Primary Owner Lake George Northway LLC
Checklist Item CommentsPassed
Low flow toilet 1.3 gal/flushing cycle True
Handicapped Ramps False
Building Inspector Notes False 9/11/23 commercial final inspection not approved, please
address the items listed below and call for recheck when ready.
-please submit a letter of substantial completion from design
architect.
- provide air balancing report.
- final electrical inspection
- complete interior work at cash wrap and racking for store
merchandise.
- install grab bars at rest room as disused on site.
- provide electronic as built drawings
Bldg Access All Sides 20ft Drivable Surface True
H/C rear grab bar 36" with 24" to open side False
Public Toilet Room Handicapped Accessible False
Exterior timer for exterior lighting True
Handicap parking striping True
Bldg Num or Tenant Address on Bld or Drive True
Public Sewer Sign-Off False
Handicapped Service Counters 34 inch False
Gas Furnace Shut Off True
H/C side & rear grab bars 36" above floor False
HVAC air balancing report False
H/C sinks 34" above floor True
H/C 18" minimum vertical grab bar False
Hot water drain pan to indirect waste True
H/C grab bar: 42" side, 12" from center False
OK to Issue C/O False
HVAC Vent Terminal 10' from Lot Line & Openings True
Universal Symbol of Access displayed False
Final Electrical / Flex Gas Piping Bonded False
Plumbing Vent Through Roof/Roof complete True
Relief Valve ,Heat Trap/Water Temp 110 deg or less True
September 11, 2023 Page 1 of 2
INSPECTION WORKSHEET (COMFIN-027630-2023)
Checklist Item CommentsPassed
Electronic as-builts False
Handicapped Bath/Parking Lot Signage True
Exits At Grade Or Platform 36 (w) x 44 (l)True
H/C mirrors 40" above floor False
H/C toilet flush handle on open side True
OK to Issue Temporary C/O False
H/C vertical grab bar 39" from floor and corner False
Elevator Hoistways Pressurized False
Ext Finish /Grade Complete/6 in 10ft or Equivalent True
Occupancy sensor lighting control True
Doors 36 inch wLever Hand Panic Hardware, if req True
Floor Bathroom Watertight Other Floors Okay True
September 11, 2023 Page 2 of 2