TAB Report - Hyundai QueensbusryNortheastern Air Quality, Inc.
P.O. Box 3271
Albany, New York 12203
(518) 857-3641
HVAC SYSTEMS TESTING:
Project:Garvey Hyundai
Location:Queensbury, New York
Architect:
Engineer:
Piping:
Sheet Metal:Alltek Energy Systems
Waterford, New York
Date:October 6, 2023
Prepared by:T. Waldorf
Air Balance Report
RKelley@NortheasternAirQuality.com
Page 1 of 6
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641 PROJECT:
THE FOLLOWING IS A LIST OF STANDARD ABBREVIATIONS WHICH MAY APPEAR IN THIS REPORT:
MEANING MEANING
A AMPS or AMPERAGE NL NOT LISTED
ACH AIR CHANGES PER HOUR NOM NOMINAL
AD ACCESS DOOR NOM EFFY NOMINAL EFFICIENCY
ADJ ADJUSTABLE NR NOT REQUIRED
Ak KINETIC (EFFECTIVE FREE) AREA NS NOT SPECIFIED
BG BLAST GATE OBD OPPOSED BLADE DAMPER
BHP BRAKE HORSEPOWER OED OPEN END DUCT
CALC CALCULATED PF POWER FACTOR
CALIBR CALIBRATION or CALIBRATED PH PHASE
CD CEILING DIFFUSER Ps STATIC PRESSURE
CF CUBIC FEET Pt TOTAL PRESSURE
CFM CUBIC FEET PER MINUTE Pv VELOCITY PRESSURE
cL CENTERLINE RG RETURN GRILLE
CLG CEILING RPM REVOLUTIONS PER MINUTE
CR CEILING REGISTER RR RETURN REGISTER
CS CIRCUIT SETTER SBD SINGLE BLADE DAMPER
CSD CEILING SUPPLY DIFFUSER SD SMOKE CONTROL DAMPER
DD DIRECT DRIVE SF SERVICE FACTOR
DDC DIRECT DIGITAL CONTROL SMC SHEET METAL CONTRACTOR
DISC DISCONNECT SWITCH SP STATIC PRESSURE
DISCH DISCHARGE SPS STATIC PRESSURE SENSOR
DPR DAMPER SR SUPPLY REGISTER
DR PRESSURE DIFFERENTIAL TC TEMPERATURE CONTROL
EC END CAP TCC TEMPERATURE CONTROL CONTRACTOR
ER EXHAUST REGISTER TCD TEMPERATURE CONTROL DAMPER
FL BHP BRAKE HORSEPOWER @ FULL LOAD AMPS TP THERMALLY PROTECTED
FLA FULL LOAD AMPS TRAV DUCT TRAVERSE
FTR FINNED TUBE RADIATION V VOLTS or VOLTAGE
GPM GALLONS PER MINUTE VAR VARIABLE
HP HORSEPOWER VBD V-BELT DRIVE
LD LINEAR DIFFUSER VD VOLUME DAMPER
LF LINEAR FEET (NOMINAL)VEL VELOCITY
NA NOT ACCESSIBLE W WATTS or WATTAGE
ND NO DAMPER WG WALL GRILLE
NDRG NON-DUCTED RETURN GRILLE WMS WIRE MESH SCREEN
NG NO GAUGE WR WALL REGISTER
NI NOT INSTALLED ZD ZONE DAMPER
NIC NOT IN CONTRACT
ABBREVIATIONS
Garvey Hyundai
ABBREVIATION ABBREVIATION
Page 2 of 6
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641 Project:
Date Last Updated:
Item #System / Note Description Date Closed By Date Closed
1 All RTU Units OA modules not installed 10/6/2023
2 All RTU Units Gas not turned on, preventing fans from
running in high (Heating).10/6/2023
Garvey Hyundai
10/6/2023
Punchlist
Page 3 of 6
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
10/6/2023
MOTOR
NAME-
PLATE VOLTS HERTZ 208 60 208 60
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
RPM
REMARKS:
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
T1 - T3 (3 Ph only)--
F.L.A.ACTUAL 0.54
T2 (3 Ph only)2.4 1.8
T3 (3 Ph only)2.3
TOTAL CFM - FAN NL NL
DISCHARGE NL 0.33 NL 0.28
OUTSIDE AIR CFM #N/A #N/A #N/A NA
TOTAL --0.68
TOTAL CFM - OUTLETS NL 2308 NL 2050
RETURN AIR CFM NL 2300 NL 2000
INLET NL -0.31 NL -0.40
S.F.7.5 -7.5 -
--
--
NOM EFFY --
Direct Drive
Direct Drive Direct Drive
CALCULATED (P.F. x NOM EFFY) *
MOTOR SHEAVE
STARTER HEATER ELEMENTS
0.82 0.82
BELTS
FAN SHEAVE
Direct Drive Direct Drive
Eco-Blue
STYLE FRAME -DD -DD
FAN RPM
Direct Drive
Direct Drive Direct DriveSHEAVE cL DISTANCE
TEST DATA DESIGN ACTUAL DESIGN ACTUAL
P.F.
SERIAL NUMBER:0823P73517 0823P73518
SYSTEM:RTU-Detailing Garage RTU-Sales Floor
LOCATION:Roof Roof
2.90 1800
PHASE 3 3
FL AMPS
HP 2.90 1800
DATE TESTED:10/6/2023 10/6/2023
MANUFACTURER Eco-Blue
AIR MOVEMENT EQUIPMENT TEST SHEET
SERVICE:Detailing Garage Sales Floor
MANUFACTURER:Carrier Carrier
MODEL:48FCEM08A3A5A0A0A0 48FCEM08A3A5A0A0A0
PROJECT:Garvey Hyundai
TESTED BY:N. Mailly DATE:
208 208
1.9
208 208
T1 7.5 2.3 7.5 1.7
0.64
T1 - T2 208 208
T2 - T3 (3 Ph only)
0.40
Page 4
Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:1) No Damper
DESIGN INITIAL INTERMEDIATE FINAL % OF
NO.Location MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS
RTU-Detailing Garage
1 Detailing Garage 26" x 16"NL Hood 769 10/6/23
2 Detailing Garage 26" x 16"NL Hood 769 10/6/23
3 Detailing Garage 26" x 16"NL Hood 770 10/6/23
Total 2,308 10/6/23
Return
4 -14" x 38"3.00 NL 800 2,400 10/6/23
RTU-Sales Floor
5 Sales Floor 27" x 8"NL Hood 293 10/6/23
6 Sales Floor 27" x 8"NL Hood 293 10/6/23
7 Sales Floor 27" x 8"NL Hood 293 10/6/23
8 Sales Floor 27" x 8"NL Hood 293 10/6/23
9 Sales Floor 27" x 8"NL Hood 293 10/6/23
10 Sales Floor 27" x 8"NL Hood 293 10/6/23
11 Sales Floor 27" x 8"NL Hood 292 10/6/23
Total 2,050 10/6/23
Return
12 Sales Floor 32" x 32"2.57 NL 408 1,050 10/6/23
RTU-Mezanine
13 Office Area 14" x 10"0.59 NL 911 534 10/6/23 1
14 Office Area 14" x 10"0.59 NL 554 325 10/6/23 1
15 Office Area 14" x 10"0.59 NL 320 188 10/6/23 1
16 Private Office1 14" x 8"NL Hood 189 10/6/23
17 Private Office 2 14" x 8"NL Hood 246 10/6/23
18 Private Office 3 14" x 10"0.59 NL 344 202 10/6/23
19 Private Office 3 14" x 10"0.59 NL 485 284 10/6/23
20 Electrical Closet 14" x 8"NL Hood 112 10/6/23
Total 2,079 10/6/23
Return
21 Office Area 16" x 16"1.24 NL 420 522 10/6/23
22 Private Office 1 16" x 8"NL Hood 198 10/6/23
23 Private Office 2 16" x 8"NL Hood 277 10/6/23
24 Private Office 3 16" x 16"1.24 NL 284 353 10/6/23
Total 1,350 10/6/23
25 -24" x 24"
N. Mailly 10/6/2023
Garvey Hyundai
Duct Size
Page 5
Northeastern Air Quality, Inc.DUCT TRAVERSE REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:
System Area % OF
NO.Zone or Branch Sq. Ft.VEL CFM VEL CFM SP VEL CFM SP DES DATE REMARKS
T-1 RTU-Detailing G.12''x 27''2.25 #VALUE!NS 1,025 2,306 -#VALUE!10/6/23
T-2 RTU-Sales Floor 22''2.64 #VALUE!NS 777 2,050 -#VALUE!10/6/23
Rnd
Garvey Hyundai
Duct Size
DESIGN REQUIRMENT INITIAL FINAL
N. Mailly 10/6/2023
Page 6