IM Inspection Worksheet_13-10-2023_11-30-14INSPECTION WORKSHEET (BINS-028287-2023)
CC-0699-2019Case Number:Case Module:Permit Management
10/13/2023 Partial PassInspection Status:Inspection Date:
Building InsulationInspection Type:Inspector:Mark Smith
Job Address:Parcel Number:1256-1264 West Mountain Rd
Queensbury, NY 12804
288.-1-64
Company Name NameContact Type
Applicant Schermerhorn Comm. Holdings LP
Architect Rucinski-Hall Architecture
Contractor Schermerhorn Comm. Holdings LP
Granted Permission Schermerhorn Comm. Holdings LP
Primary Owner WESTBROOK SENIOR RESIDENCES
Checklist Item CommentsPassed
Zip exterior sheathing, nailing & taping True
October 13, 2023 Page 1 of 3
INSPECTION WORKSHEET (BINS-028287-2023)
Checklist Item CommentsPassed
Building Inspector Notes False 1/9/23 partial approval for insulation
- R 19 sound insulation verified at the tub enclosure for each unit.
2/21/23 partial approval for insulation
- proper vent in apartment room only verified.
- insulation at box beam first and second floors apartment room
only approved R 25
- R 38 insulation At elevator shaft lid and 4' down the walls verified.
3/9/23 partial approval for insulation
- insulation approved at the areas listed below, ok to cover these
areas with Sheetrock so mechanical work can be installed
- third floor ceilings at north and south walls 48" from top plate, R
38
- third floor walls, north and south wall approximately 12" down
from top plate, R 21
- first and second floors, ceilings 48" from top plate at north and
south walls R 19 sound insulation.
- first and second floor north and south exterior walls only
approximately 12" down from top plate, R 21
4/3/23 partial approval for insulation
- sound insulation at first and second floor corridor ceilings
verified, R 21.
4/5/23 Building Insulation Partial Approval
- Corridor Ceiling Sound Board 1st and 2nd floor approved.
4/19/23 partial approval for insulation
R 30 insulation at cantilevered framing parking lot side of building
verified, ok to install sheathing.
5/26/23 partial approval for insulation
- insulation at electrical room walls first floor verified, ok to sheet
rock this room only.
6/8/23 partial approval for insulation
-sound insulation at electrical room ceiling, entrance foyer ceiling,
and mail room ceiling verified, ok to install sound board and sheet
rock these areas only.
6/20/23 partial approval for insulation
- thermal insulation at mechanical rooms west end of building first
and second floor verified.
-thermal insulation at community room exterior wall verified
10/13/23 partial approval for insulation
- thermal & sound insulation approved at the third floor only.
U Factors = .3 cfm for windows, .5 cfm for doors False .28
Exterior wall outlets sealed True
All Return Air Hard Duct Work False
Duct work sealed properly / No duct tape True
Duct Testing Outside Conditioned Space False
Door / Window Sealed (No Insulation)True
Air Seal Outside Penetrations True
All Ductwork Sealed Return and Supply True
Blower Door Test False
October 13, 2023 Page 2 of 3
INSPECTION WORKSHEET (BINS-028287-2023)
Checklist Item CommentsPassed
Duct Insulation - if required in unheated spaces False
Combustion Air Supply for Furnace False
Fresh air supply 3' from grade True
Window Sealing True
Duct Blaster Test for duct work, R-8, unhtd spaces False
Permit Card Visible From Road True
Proper Vent, Attic Vent True
Insulation ResCheck ComCheck True 4/5/23 Building Insulation Partial Approval
- Corridor Ceiling Sound Board 1st and 2nd floor approved.
4/19/23 partial approval for insulation
R 30 insulation at cantilevered framing parking lot side of building
verified, ok to install sheathing.
October 13, 2023 Page 3 of 3