IM Inspection Worksheet_07-12-2023_12-01-28INSPECTION WORKSHEET (RPLUM-029227-2023) RC-0433-2023Case Number:Case Module:Permit Management 12/07/2023 Partial PassInspection Status:Inspection Date: Rough PlumbingInspection Type:Inspector:Charles Dyer Job Address:Parcel Number:10 Michaels Dr Queensbury, NY 12804 308.6-1-37 Company Name NameContact Type Applicant CHAD WARNER Architect Dreamscapes Unlimited Contractor Amken Construction Granted Permission CHAD WARNER Primary Owner CHAD WARNER Checklist Item CommentsPassed Building Inspector Notes False 10/18/23 Rough Plumbing Not Approved - Plumbing under slab not approved the vents for shower and tub not installed. Will reinspect tomorrow at 9:00 am. 10/19/23 Rough Plumbing Partial Approval - Plumbing Under Slab Approved - Pressure Test Approved 5 psi Pressure Test True Pressure Test False 3" Vent Through Roof - 18" min True Washing Machine Drain 2 inch minimum False All Return Air Hard Duct Work False 5 psi or 10 ft. above highest conn. for 15 minutes True Rough Plumbing / Nail Plates False 10/19/23 Rough Plumbing Partial Approval - Plumbing Under Slab Approved - Pressure Test Approved 5 psi Duct Testing Outside Conditioned Space False Shower liner test (2" of water)False Water Supply Piping True existing Duct Insulation - if required in unheated spaces False Duct work sealed properly False Cleanout every 100 feet change of direction False Plumbing Vent Vents in Place True Air Test Gas Piping 10 psi for 10 Minutes False Washing Machine Trap: 18"-42" discharge False Air Head False Air Head True 50 P.S.I for 15 minutes False 1 ½ inch minimum Drain Size True Drain Vent False Permit Card Visible From Road True December 07, 2023 Page 1 of 1