IM Inspection Worksheet_02-01-2024_11-13-25INSPECTION WORKSHEET (FIST-029647-2023)
CC-0013-2023Case Number:Case Module:Permit Management
01/02/2024 Partial PassInspection Status:Inspection Date:
FirestoppingInspection Type:Inspector:Mark Smith
Job Address:Parcel Number:80 Main St
Queensbury, NY 12804
309.10-1-25
Company Name NameContact Type
Applicant FOOTHILLS BUILDERS, LLC
Architect Rucinski Hall Architecture
Contractor FOOTHILLS BUILDERS, LLC
Granted Permission FOOTHILLS BUILDERS, LLC
Primary Owner 78-80 Main Street LLC
Checklist Item CommentsPassed
Building Inspector Notes False 12/12/23 fire stopping at third floor not approved.
- all penetrations at the the top and bottom plates need to be fire
caulked.
-provide documentation showing the fire rating for the toilet
flanges and the penetrations for the pex water supply piping.
- the insulation installed prior to inspection will need to be
removed in order to complete the inspection.
- enclosed plumbing chases will need to be sheet rocked and fire
caulked.
1/2/24 partial approval for fire stopping at second floor exterior
walls only.
- install rock wool at tub penetrations.
-install fire caulking at toilet penetrations.
- install fire caulking at domestic water supply plumbing
penetrations as discussed on site.
ok to install insulation at exterior walls only.
Exterior wall outlets sealed False
Garage Fire Separation False
Draft stopping 1,000 sq. ft. floor trusses False
Fire separation 1, 2, 3 hour False
Bath fans connected to exterior vent False
Firestopping False
House side ½ inch or 5/8 inch Type X False
Garage ceiling, living space above, 5/8" Type X False
Penetration sealed False
16 inch insulation in cavity min.False
Fire wall 2, 3, 4 hour False
Fireproofing False
Permit Card Visible From Road False