INSPECTION WORKSHEET 02282024
INSPECTION WORKSHEET
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number: CC-0013-2023 Case Module:
Inspection Date: February 28, 2024 Inspection Status: Reinspect
Inspector: Mark Smith Inspection Type: Firestopping
Job Address: 78 MAIN ST
, Parcel Number:
Contact Type Company Name Name
Checklist Item
Status
Penetration sealed
Firestopping
Garage ceiling, living space above, 5/8"
Type X
Fire wall 2, 3, 4 hour
Bath fans connected to exterior vent
Fire separation 1, 2, 3 hour
Garage Fire Separation
16 inch insulation in cavity min.
House side ½ inch or 5/8 inch Type X
Exterior wall outlets sealed
Permit Card Visible From Road
Building Inspector Notes
12/12/23 fire stopping at third floor not approved.
- all penetrations at the the top and bottom plates need to be fire caulked.
-provide documentation showing the fire rating for the toilet flanges and
the penetrations for the pex water supply piping.
- the insulation installed prior to inspection will need to be removed in
order to complete the inspection.
- enclosed plumbing chases will need to be sheet rocked and fire
caulked.
1/2/24 partial approval for fire stopping at second floor exterior walls only.
- install rock wool at tub penetrations.
-install fire caulking at toilet penetrations.
- install fire caulking at domestic water supply plumbing penetrations as
discussed on site.
ok to install insulation at exterior walls only.
1/3/23 partial approval for fire stopping.
- fire stopping at second and third floor partially approved.
- penetrations at truss draft stopping at second and third floor need to be
sealed
- fill the gap at the top plate of the partitions that separate each apartment
with rock wool.
ok to insulate, please call for recheck when insulation at 3rd floor is
completed.
1/10/24 partial approval for fire stopping.
-Rockwool at top plate of double 2x4 partitions separating units at third
floor verified.
2/28/24 partial approval for fire stopping.
- fire stopping at vertical penetrations at first floor exterior walls and
partitions dividing rental spaces only verified
N/O
Fireproofing
Draft stopping 1,000 sq. ft. floor trusses
Mark Smith
Code Enforcement Officer