INSPECTION WORKSHEET 04162024
INSPECTION WORKSHEET
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number: RC-0275-2023 Case Module: Permit
Inspection Date: April 16, 2024 Inspection Status: Reinspect
Inspector: Charles Dyer Inspection Type: Residential Final
Job Address: 81 ASSEMBLY POINT RD
, Parcel Number:
Contact Type Company Name Name
Owner N/A G. THOMAS MOYNIHAN JR
Contractor J. Clarke Constructiion
Architect Flynn Design Studios LLC
Owner N/A Joan Moynihan
Checklist Item
Status
Building Inspector notes
PASS
4 inch min building number address
visible from road
FAIL
Chimney height, B vent, direct vent
location
PASS
Chimney rain cap installed
PASS
Fresh air intake
PASS
Fresh air supply 3 feet from grade
PASS
3 inch plumbing vent through roof,
minimum 18 inches
PASS
Outside spigots have air gap
PASS
Roof complete
PASS
Exterior finish complete
PASS
Platform at all exterior doors
provide temp stairs at patio
FAIL
Handrail required with 4 or more risers
PASS
Guard at stairwell at 34 inches or more
PASS
Window guards req at less than 2' above
floor and 6' above grade
PASS
Handrail termination at newell post or wall
PASS
Interior and exterior handrails 34" to 38"
high
PASS
Grade away from foundation sloping 6
inches in the first 10 feet
PASS
6 inch clearance to sill plate from grade
PASS
HVAC vent terminal 10 feet from lot line
and openings
PASS
Interior privacy doors and trim required
PASS
Exterior main entrance door min 36" wide
PASS
Bathroom and Kitchen floors must be
watertight
PASS
Low flow toilet 1.3 gallon per flushing
cycle
PASS
Safety glazing required within 5 feet of
tub and shower
PASS
Smoke detectors are min of 3 feet
horizontally from opening of bathroom
PASS
Smoke Detectors are required on every
level and in every bedroom
PASS
Smoke Detectors are required outside
every bedroom area
PASS
Smoke Detectors have battery back up
provide letter of certification from Mahoney notifier
PASS
Smoke detectors are interconnected
PASS
Carbon monoxide detectors are within 10
ft of all sleeping areas
PASS
Carbon monoxide detectors are required
on all levels with gas appliances (i.e.
furnace)
PASS
Heat detector required in attached garage
PASS
Attic access 22 inches x 30 inches
minimum with 30 inch high clearance
PASS
Attic access insulation R-value must
equal ceiling R- value
foam at ceiling
N/O
Attic access gasketed
PASS
Foam in basement and attics covered
with thermal barrier
PASS
Knee wall and crawl space areas require
18 inches x 24 inches access
PASS
Crawl space and knee wall access
insulated and gasketed
PASS
Bathroom fans required, if no window
PASS
All plumbing fixtures complete
PASS
Backflow preventors where required
PASS
Foundation insulation to basement floor
PASS
Energy sticker on elec. panel, R values
and heating systems
FAIL
All Hot Water Systems R 3 on 3/4 inches
or larger piping
PASS
Duct work sealed properly
PASS
Intake openings for HVAC
PASS
Range Hood 400 or more cfm make up
air required
PASS
Blower door test certification
FAIL
HRV or ERV installed per bedroom
requirements
PASS
Furnace shut off within 30 ft. or within line
of site
PASS
Propane tank proper setback from
property line or structure
PASS
Furnace and hot water heater operating
PASS
Low water shut off required for boiler
PASS
Pressure relief valve, heat trap, water
temp 110 degrees or less
PASS
Pressure relief valve down spout within 6
inches of floor
PASS
1/2 inch Gypsum or House Wall and
Gable
PASS
5/8 inch Type X with living space above
PASS
20 minute fire door and self-closing
hardware
PASS
Seals on garage doors, esp. wood
PASS
Basement stairs closed rise greater than
4 inches
PASS
Basement wall insulation R- value verified
5 ft crawl area
N/O
Jack posts in basement lagged at top and
bottom
tap con bases
FAIL
Fireblocking at fl joist 80 s.f. or less
Garage floor pitched
PASS
1/2" Gypsum board req. in basement for
framing if 2" x 8" or TJI/Floor Trusses
PASSN/O
Gas log in sealed or glass enclosure
PASS
Fin elect; energy saving light bulbs 90
percent
FAIL
Final survey plot plan
FAIL
Arc fault breaker habitable spaces
Flex gas pipe bonding
As built septic system
FAIL
Site plan or variance approval inspection
FAIL
Truss ID signage installed at electrical
meter
provide sticker for TJI’s
FAIL
Electronic as builts
Ok to issue temporary certificate of
occupancy
CONDITIONS: provide final electric 2. Engineer septic asbuilt 3. Fuji
maintenance contract agreement 4. Site plan certification 5. Final survey
6. Blower door results— OK to issue temp CO when final electric and
blower door received 4/16/24
PASSN/O
Ok to issue certificate of occupancy
FAIL
Charles Dyer
Code Enforcement Officer