Loading...
INSPECTION WORKSHEET 05072024 INSPECTION WORKSHEET Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number: RC-0108-2022 Case Module: Permit Inspection Date: May 07, 2024 Inspection Status: Passed Inspector: Tyson Converse Inspection Type: Gas Insert Job Address: 211 ASSEMBLY POINT RD , Parcel Number: 226.19-2-18 Contact Type Company Name Name Architect AJA Architecture & Planning null null Contractor Larmon House Movers Inc Owner N/A Erin Steinbach Owner N/A Francis Steinbach Checklist Item Status Fire Marshal notes PASS Manufacturer Hearth & Home PASS Model Pier-DV36in/ST-DV 36in PASS Flex liner PASS Rigid liner PASS Liner size PASS Dual liner PASS Installed per manual PASS Clearances to combustibles on all sides Floor: 0" Side: 1/2" Ceiling: 31" 12” clearance for mantle PASSN/O Connected to flue, flue gases not mixing with room air PASS Liner termination extends above chimney Must extend 18" above Stone work PASS Weather cap installed Verify on Final PASS Gas shut off valve Need to see on final, Below floor or at Unit PASS Witness operation PASS Tank placement (if LP) done and inspected by FM Palmer PASS Carbon monoxide detection or notification device, required verify on Final PASS CSST bonding, if required verify on final PASS Tyson Converse Deputy Fire Marshal