20240617142316312 QWBR,,1D � PROJECT; I<AMCO ENGINEERING INC, ® LOCATION:QUEENSBURY, NY Reference: 4725 SF CAL-Q-HEATO Heat Load Calculation DATE:06/06/24 DESIGN TEMPERATURES 60 OF Indoor Design Temperature 0°F Outdoor Design Temperature BASE HEAT LOAD 60 OF Design Temperature Difference (DTD) CONDUCTION LOAD (Net Area[,qq ftlx U-Value tBtuAeFsq.ft.]x DTD[OF]_I000[Btu1 MBH]=MBH) Roof R=40 150'L x 32'W 4,725 sq.ft. x 0,025 x 60 + 1000 = 7 MBH Walls R=25 M H x 230'L 5,520 sq.ft. x 0.040 x 60 ; 1000 = 13 MBH Windows/Skylights NONE CONSIDERED Subtotals: Roof Load: 7 MBH Wall Load: + 13 M8H Total Conduction Load: 20 MBH INFILTRATION LOAD Airflow[CFM]x Heat Transmission Factor[Btulhr°F'sq ft.]x DTD j°F]_1000(Btuh/MBH]=MBH) (Cold Air Gain) 113,400 tuft. + 60 Min/Hr x 0.20 AC/Hr = 378 CFM x 1.21 x 60 � 1000= 27 MSH Total Conduction Load: f 20 MBH Total Base Heat Load-, 47MBH f OPERATING HEAT LOAD Open Door Load (Quantity of Doors x MBH/Door x%Open=MBH) l DRIVE DOOR 16'W x 16'H w/o seals 1 x 2300 x 4% 92 MBH � Process Losses/<Gains> NO EXHAUST CONSIDERED WARNING:This information is based on using genuine Cambridge S-Series Blow-ThruTM+ Total Operating Heat Load; 92 MBH heater technology. DO NOT ATTEMPT TD SUBSTITUTE any direct gas-hied heater Incapable of achieving 160°F temperature Has with a discharge temperature of 18011= at 0°outdoor.The technologies are different.Ability to heat the building will be jeopardized Total Heat Load: 139 MBH and energy costs will increase. 3 NOTE: We provide this projection to aid In decision making. We believe our computations to be accurate.However,this projection is based upon and Is directly dependent upon the accuracy of Input data provided to us as described in the attached CAL-Q-HEATO t System Conditions. Any changes in these System Conditions may result in a change in the Heat Load Calculation.