Air Balance Test Report_McDonalds Quennsbury NYHVAC SYSTEMS TESTING:
Air and Water Balance Report
for
McDonalds
MICHAEL LUCARELLI
June 25, 2024
2024 EOTF MOD C Existing Building
46 East Main Street Suite 201
Somerville, New Jersey 08876
515A County Route 45 Argyle,NY 12809
Location:
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
Date:
Prepared by:
Engineer
Contractor:
Queensbury NY 12804
Core States Group
Hunt Companies Inc.
192 Corinth Road
Project:
Project:
Address:
DATE:
PROJECT # :
MJL ADTEK Enterprises, LLC.TESTING AND BALANCING FIRM:
BALANCED BY:
SIGNATURE:
June 25, 2025
MICHAEL LUCARELLI
MICHAEL LUCARELLI
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND
WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES
FROM DESIGNED QUANTITIES WHICH EXCEEDS NEBB TOLERANCES ARE NOTED THROUGHOUT
THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS
HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING
AND BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
THE WATER DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL
ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS
FOR TESTING AND BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT
SPECIFICATIONS.
CERTIFICATION
192 Corinth Road
Queensbury NY 12804
McDonalds
2024 EOTF MOD C Existing Building
12205
CD - Ceiling Diffuser
CS - Circuit Setter
DD - Direct Drive
ER - Exhaust Register
LD - Linear Diffuser
NA - Not Accessible
ND - No Volume Damper
NG- No Gauges
NI- Not Installed
NR Not Required
NS -Not Specified
OBD - Opposed Blade Damper
OD - Open Duct
RG - Return Grille
SR - Supply Register
SD - Supply Diffuser
TP- Thermally Protected
EP-Electronically Protected
WMS - Wire Mesh Screen
NN - Diffuser, Register or Grille Noisy: All available
adjustments made to correct condition. Additonal
Dampers, sound lining or duct change required to
correct condition.
MJL ADTEK Enterprises, LLC
P.O. Box 503 Clifton Park NY 12065
Phone: (518) 376-9478
Following are code definitions as used in a balancing report:
M
1 PROJECT NAME:
ADDRESS:
ACTUAL
NA
5218
4101
1117
1.61
1.1
0.51
929
US MOTOR
5
3
208/209/208
11.0/10.8/11.0
1765
1.15
T.P
Remarks:RTU-3 Is 17.5 tons,Based on 400 CFMS Per ton unit would be 7000 CFMS. Filters need to
be changed pretty dirty.Filter size is 24x24x2 needs 6 filters.
MOTOR SHEAVE & NO. GROOVES
FAN SHEAVE & NO. GROOVES
BELTS
1VP65X1 1/8 60 % CLOSED
BK110HX1 7/16
BX-65
13.8/13.0
NS
NS
AMPERAGE
MOTOR RPM
MOTOR SERVICE FACTOR
STARTER HEATER ELEMENTS
NS
MOTOR MANUFACTURER
MOTOR HP/BHP
PHASE
VOLTAGE
FAN RPM
NS
NS
3
208/230
INLET PRESSURE
DISCHARGE PRESSURE
TOTAL STATIC PRESSURE 1.5
NS
NS
SPECIFIED
7000
NS
NS
NS
NS
SERIAL NUMBER
TOTAL CFM-FAN
TOTAL CFM-OUTLET
R/A CFM
O/A CFM
5613F01548
SPECIFIED ACTUAL
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
EQUIPMENT LOCATON
AREA SERVICED
EQUIPMENT MANUFACTURER
MODEL
RTU -3
ROOF
RMS 100,101,102,103&114A
LENNOX
LGH210HBS2Y
TOTAL PAGES:5
MJL ADTEK Enterprises, LLC
Phone: (518) 376-9478
P.O. Box 503, Clifton Park, NY 12065
PAGE NUMBER:1
McDonalds
2024 EOTF MOD C Existing Building
192 Corinth Road
Queensbury NY 12804
PROJECT
NUMBER:12205
6/25/2024DATE:
TYPE SIZE Ak FPM CFM TEST 1 TEST 2 TEST 3 FPM CFM
RTU-3
SUPPLY
1 114A S-4 10''1.0 HOOD NS 216 261 263 HOOD 263
2 101 S-2 12''1.0 HOOD NS 356 366 371 HOOD 371
3 103 S-2 8''1.0 HOOD NS 104 111 112 HOOD 112
4 102 S-2 8''1.0 HOOD NS 107 115 117 HOOD 117
5 101 S-2 8''1.0 HOOD NS 161 199 171 HOOD 171
6 101 S-2 8''1.0 HOOD NS 161 161 167 HOOD 167
7 101 S-2 8''1.0 HOOD NS 146 157 161 HOOD 161
8 101 S-2 8''1.0 HOOD NS 156 173 167 HOOD 167
9 101 S-2 12''1.0 HOOD NS 307 386 384 HOOD 384
10 101 S-2 12''1.0 HOOD NS 368 412 401 HOOD 401
11 101 S-2 10''1.0 HOOD NS 185 204 210 HOOD 210
12 101 S-2 12''1.0 HOOD NS 366 451 376 HOOD 376
13 100 S-2 12''1.0 HOOD NS 264 344 347 HOOD 347
14 100 S-2 12''1.0 HOOD NS 367 376 371 HOOD 371
15 100 S-2 12''1.0 HOOD NS 318 346 353 HOOD 353
16 100 S-2 12''1.0 HOOD NS 222 257 296 HOOD 296
17 100 S-2 12''1.0 HOOD NS 366 404 373 HOOD 373
18 100 S-2 12''1.0 HOOD NS 286 299 323 HOOD 323
19 114B S-4 10''1.0 HOOD NS 208 250 255 HOOD 255
4664 5272 5218 5218
RETURNS
1 101 R-1 16''1.0 HOOD NS 621 739 NR HOOD 739*
2 101 R-1 16''1.0 HOOD NS 734 854 NR HOOD 854*
3 101 R-1 16''1.0 HOOD NS 682 787 NR HOOD 787*
4 101 R-1 16''1.0 HOOD NS 696 802 NR HOOD 802*
5 101 R-1 16''1.0 HOOD NS 816 919 NR HOOD 919*
3549 4101 4101
Remarks:
Queensbury NY 12804
192 Corinth Road
PROJECT NUMBER:12205
6/25/2024DATE:
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
PROJECT NAME: McDonalds
2024 EOTF MOD C Existing Building
* No Volume Damper
PAGE NUMBER:
TOTAL PAGES:
2
5
FINAL
AIR DISTRIBUTION TEST SHEET
TERMINAL
NUMBER ROOM NUMBER TERMINAL DESIGN TEST-FPM or CFM
ADDRESS:
TYPE SIZE Ak FPM CFM TEST 1 TEST 2 TEST 3 FPM CFM
RTU
Existing
1 106 S-2 10''1.0 HOOD NS 333 333 NR HOOD 333*
2 106 S-2 10''1.0 HOOD NS 309 309 NR HOOD 309*
3 106 S-2 10''1.0 HOOD NS 382 382 NR HOOD 382*
1024 1024
Remarks:
FINAL
* No volume damper
Queensbury NY 12804 TOTAL PAGES:5
AIR DISTRIBUTION TEST SHEET
TERMINAL
NUMBER ROOM NUMBER TERMINAL DESIGN TEST-FPM or CFM
2024 EOTF MOD C Existing Building DATE:6/25/2024
ADDRESS: 192 Corinth Road PAGE NUMBER:3
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
PROJECT NAME: McDonalds PROJECT NUMBER:12205
PROJECT NAME:
ADDRESS:
ACTUAL
NA
586
0.15
0.15
0.00
1666
VARI GREEN
1/4
1
119
3.2
300-1725
1.0
T.P
Remarks:
PROJECT
NUMBER:12205
6/25/2024DATE:
Queensbury NY 12804
McDonalds
2024 EOTF MOD C Existing Building
192 Corinth Road PAGE NUMBER:
TOTAL PAGES:5
4
NS
PHASE 1
DISCHARGE PRESSURE NS NS 0.11
FAN RPM NS NS HIGH
NS
PANSONIC
NA
1
118
0.3
3 SPEED
1.0
NS
NS
1
120
0.31
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9476
BELTS
MOTOR SERVICE FACTOR NS
STARTER HEATER ELEMENTS NS
DDMOTOR SHEAVE & NO. GROOVES
FAN SHEAVE & NO. GROOVES
NS T.P
VOLTAGE 120
AMPERAGE 3.9
MOTOR RPM NS
MOTOR MANUFACTURER NS
MOTOR HP/BHP NS
GREENHECK PANASONIC
MODEL MC6-098-VG FV-0511VQL1
NS NS 0.03
TOTAL CFM-FAN NS 50/80/110 NA
TOTAL CFM-OUTLET NS NS 105
INLET PRESSURE
NS 0.14TOTAL STATIC PRESSURE NS
SYSTEM EF-1 EF-5
EXHAUST FAN DATA SHEET
EQUIPMENT LOCATON ROOF CEILING
AREA SERVICED RMS 102&103 RM 115
DD
DD
DD
DD
DD
SERIAL NUMBER 13314359 NA
SPECIFIED SPECIFIED ACTUAL
EQUIPMENT MANUFACTURER
TYPE SIZE Ak FPM CFM TEST 1 TEST 2 TEST 3 FPM CFM
EF-1
1 102 EG 12X12 1.0 HOOD NS 136 NR NR HOOD 136*
2 102 EG 12X12 1.0 HOOD NS 146 NR NR HOOD 146*
3 102 EG 12X12 1.0 HOOD NS 157 NR NR HOOD 157*
4 102 EG 12X12 1.0 HOOD NS 147 NR NR HOOD 147*
586 586
EF-5
1 115 EG 10X10 1.0 HOOD NS 105 NR NR HOOD 105
Remarks:
FINAL
* Bath room grills are plugged.
Queensbury NY 12804 TOTAL PAGES:5
AIR DISTRIBUTION TEST SHEET
TERMINAL
NUMBER ROOM NUMBER TERMINAL DESIGN TEST-FPM or CFM
2024 EOTF MOD C Existing Building DATE:6/25/2024
ADDRESS: 192 Corinth Road PAGE NUMBER:5
MJL ADTEK Enterprises, LLC
P.O. Box 503, Clifton Park, NY 12065
Phone: (518) 376-9478
PROJECT NAME: McDonalds PROJECT NUMBER:12205