TAB Report - Verizon QueensburyNortheastern Air Quality, Inc. P.O. Box 3271 Albany, New York 12203 (518) 857-3641 HVAC SYSTEMS TESTING: Project:Verizon Queensbury Location:Queensbury, New York Architect:Gruskin Architecture + Design, P.C. Spingfield, New Jersey Engineer:Lilker Associates New York, New York Piping: Sheet Metal:Brayton Construction Inc. Date:October 10, 2024 Prepared by:N. Mailly RKelley@NortheasternAirQuality.com Air Balance Report Item Page Certification 3 Standard Abbreviations 4 Air Balance Report Air Moving Equipment 5 Grille, Register & Diffuser Report 6 Minimum Outside Air Report 8 System Diagrams 9 Table of Contents CERTIFICATION PROJECT: ADDRESS: TESTING AND BALANCING FIRM: CERTIFIED BY:DATE:10/10/2024 SIGNATURE: Robert V. Kelley Verizon Queensbury Queensbury, New York THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES FROM DESIGNED QUANTITIES WHICH EXCEEDS NEBB TOLERANCES ARE NOTED THROUGHOUT THIS REPORT. THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB ''PROCEDURAL STANDARDS FOR TESTING AND BALANCING OF ENVIRONMENTAL SYSTEM'' AND THE PROJECT SPECIFICATIONS. Northeastern Air Quality, Inc. #3159 Page 3 Northeastern Air Quality, Inc. P.O. Box 3271, Albany, NY 12203-0271 (518) 857-3641 PROJECT: THE FOLLOWING IS A LIST OF STANDARD ABBREVIATIONS WHICH MAY APPEAR IN THIS REPORT: MEANING MEANING A AMPS or AMPERAGE NL NOT LISTED ACH AIR CHANGES PER HOUR NOM NOMINAL AD ACCESS DOOR NOM EFFY NOMINAL EFFICIENCY ADJ ADJUSTABLE NR NOT REQUIRED Ak KINETIC (EFFECTIVE FREE) AREA NS NOT SPECIFIED BG BLAST GATE OBD OPPOSED BLADE DAMPER BHP BRAKE HORSEPOWER OED OPEN END DUCT CALC CALCULATED PF POWER FACTOR CALIBR CALIBRATION or CALIBRATED PH PHASE CD CEILING DIFFUSER Ps STATIC PRESSURE CF CUBIC FEET Pt TOTAL PRESSURE CFM CUBIC FEET PER MINUTE Pv VELOCITY PRESSURE cL CENTERLINE RG RETURN GRILLE CLG CEILING RPM REVOLUTIONS PER MINUTE CR CEILING REGISTER RR RETURN REGISTER CS CIRCUIT SETTER SBD SINGLE BLADE DAMPER CSD CEILING SUPPLY DIFFUSER SD SMOKE CONTROL DAMPER DD DIRECT DRIVE SF SERVICE FACTOR DDC DIRECT DIGITAL CONTROL SMC SHEET METAL CONTRACTOR DISC DISCONNECT SWITCH SPS STATIC PRESSURE SENSOR DISCH DISCHARGE SR SUPPLY REGISTER DPR DAMPER TC TEMPERATURE CONTROL DR PRESSURE DIFFERENTIAL TCC TEMPERATURE CONTROL CONTRACTOR EC END CAP TCD TEMPERATURE CONTROL DAMPER ER EXHAUST REGISTER TP THERMALLY PROTECTED FL BHP BRAKE HORSEPOWER @ FULL LOAD AMPS TRAV DUCT TRAVERSE FLA FULL LOAD AMPS V VOLTS or VOLTAGE FTR FINNED TUBE RADIATION VAR VARIABLE GPM GALLONS PER MINUTE VBD V-BELT DRIVE HP HORSEPOWER VD VOLUME DAMPER LD LINEAR DIFFUSER VEL VELOCITY LF LINEAR FEET (NOMINAL)W WATTS or WATTAGE NA NOT ACCESSIBLE WG WALL GRILLE ND NO DAMPER WMS WIRE MESH SCREEN NDRG NON-DUCTED RETURN GRILLE WR WALL REGISTER NG NO GAUGE ZD ZONE DAMPER NI NOT INSTALLED NIC NOT IN CONTRACT ABBREVIATIONS Verizon Queensbury ABBREVIATION ABBREVIATION Page 4 Northeastern Air Quality, Inc. P.O. Box 3271, Albany, NY 12203-0271 (518) 857-3641 10/10/2024 MOTOR NAME-RPM PLATE VOLTS HERTZ 208 60 208 60 DATA EXT. STATIC PRESSURE VOLTS AMPS BHP (calc.) REMARKS: * NOTE: If P.F. or NOM EFFY are NL, (P.F. x NOM EFFY) = 746Hp/(VAX), where X = 1 if 1 Ph, and 1.73 if 3 Ph - 0.34 INLET NL -0.36 TOTAL CFM - OUTLETS 2850 3100 825 872 RETURN AIR CFM 2423 2591 TEST DATA DESIGN ACTUAL DESIGN HP 3 1725 3/4 1400 PHASE SHEAVE cL DISTANCE FAN SHEAVE AK74 x 1" -- VM50 x 7/8"Direct Drive Direct Drive A54 Direct Drive 18 3/4" N. Mailly DATE: AIR MOVEMENT EQUIPMENT TEST SHEET ACTUAL 0.72 STYLE FRAME -56HZ -NL DATE TESTED:10/10/2024 10/10/2024 MANUFACTURER Marathon Broad Ocean 3 1 FL AMPS S.F.9.5 1.15 BELTS SYSTEM:RTU-1 (Labeled #2 on roof)RTU-2 (Labeled #1 on roof) LOCATION:Roof Roof MODEL:ZF102N15N2AAA7 PCG4A361003X1A SERIAL NUMBER:N1A6283035 W1M5148419 SERVICE:Retail Sales 101 Stock Room/ Break Room MANUFACTURER:York York PROJECT:Verizon Queensbury TESTED BY: 0.58 NL -0.49 OUTSIDE AIR CFM 428 468 - NL NL NL NL 5.4 1.00 Direct Drive TOTAL NL DISCHARGE NL 0.22 NL T1 - T2 208 208 208 210 FAN RPM NL 987 825 865 NL NL TOTAL CFM - FAN NL -NL - CALCULATED (P.F. x NOM EFFY) * MOTOR SHEAVE STARTER HEATER ELEMENTS 0.72 P.F.NOM EFFY T3 (3 Ph only)6.7 T2 - T3 (3 Ph only)207 NL 0.83 T1 - T3 (3 Ph only)208 F.L.A.ACTUAL 2.28 T1 9.5 6.4 5.4 3.4 T2 (3 Ph only)6.6 0.69 Page 5 Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT P.O. Box 3271, Albany, NY 12203-0271 PROJECT: (518) 857-3641 TESTED BY:DATE: REMARKS: DESIGN INITIAL INTERMEDIATE FINAL % OF NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS RTU-1 1 Retail Sales 101 24" x 24"CD-1 375 Hood 429 Hood 373 Hood 414 110%10/10/24 2 Retail Sales 101 24" x 24"CD-1 375 Hood 360 Hood 382 Hood 410 109%10/10/24 3 Retail Sales 101 24" x 24"CD-1 375 Hood 366 Hood 381 Hood 409 109%10/10/24 4 Retail Sales 101 24" x 24"CD-1 375 Hood 320 Hood 349 Hood 414 110%10/10/24 5 Retail Sales 101 24" x 24"CD-1 375 Hood 452 Hood 392 Hood 413 110%10/10/24 6 Retail Sales 101 24" x 24"CD-1 375 Hood 377 Hood 387 Hood 412 110%10/10/24 7 Storage 104 24" x 24"CD-1 100 Hood 82 Hood 92 Hood 110 110%10/10/24 8 Modified Open Office 103 24" x 24"CD-1 250 Hood 244 Hood 244 Hood 275 110%10/10/24 9 Existing Inventory 105 24" x 24"CD-1 0.55 458.599 250 Hood 174 350 191 445 243 97%10/10/24 Total 2,850 3,100 109%10/10/24 Return 10 Storage 104 24" x 24"RG-1 NL 901 491 Hood 562 Hood 590 -10/10/24 11 Retail Sales 101 24" x 24"RG-1 NL Hood 673 Hood 673 Hood 707 -10/10/24 12 Retail Sales 101 24" x 24"RG-1 NL Hood 870 Hood 870 Hood 914 -10/10/24 15 Modified Open Office 103 24" x 24"RG-1 NL Hood 363 Hood 363 Hood 381 -10/10/24 Total 2,423 2,591 107%10/10/24 RTU-2 16 5-POS 102 24" x 24"CD-1 150 Hood 375 Hood 165 Hood 165 110%10/10/24 17 Existing Restroom 110 24" x 24"CD-1 50 Hood 48 Hood 52 Hood 55 110%10/10/24 18 Existing Restroom 109 24" x 24"CD-1 50 Hood 29 Hood 45 Hood 46 92%10/10/24 19 Break Room 24" x 24"CD-1 250 Hood 289 Hood 267 Hood 275 110%10/10/24 20 Existing Manager 106 24" x 24"CD-1 75 Hood 89 Hood 70 Hood 75 100%10/10/24 21 Break Room 24" x 24"CD-1 250 Hood 244 Hood 255 Hood 256 102%10/10/24 Total 825 872 106%10/10/24 Return N. Mailly 10/10/2024 Verizon Queensbury Page 6 Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT P.O. Box 3271, Albany, NY 12203-0271 PROJECT: (518) 857-3641 TESTED BY:DATE: REMARKS: DESIGN INITIAL INTERMEDIATE FINAL % OF NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS N. Mailly 10/10/2024 Verizon Queensbury 22 5-POS 102 24" x 24"RG-1 NL Hood 250 Hood 242 Hood 202 -10/10/24 23 Break Room 24" x 24"RG-1 NL 411 224 Hood 468 Hood 387 -10/10/24 24 Break Room 24" x 24"RG-1 NL Hood 317 Hood 336 Hood 276 -10/10/24 Total 825 865 105%10/10/24 EF-1 25 Existing restroom 110 10" x 10"NL Hood 29 Hood 131 -10/10/24 EF-2 26 Exiting Restroom 109 10" x 10"NL Hood 29 Hood 117 -10/10/24 EF-3 27 Existing Restroom 108 10" x 10"NL Hood 116 Hood 116 -10/10/24 Page 7 Northeastern Air Quality, Inc.MINIMUM OUTSIDE AIR REPORT P.O. Box 3271, Albany, NY 12203-0271 PROJECT: (518) 857-3641 DATE: System Area % OF Zone or Branch Sq. Ft.VEL CFM VEL CFM SETPOINT VEL CFM SETPOINT DES DATE Min Outside Air AHU-1 (Existing)20''x 28''3.93 109 428 119 468 10%109%10/10/24 Verizon Queensbury 10/10/2024 Duct Size DESIGN REQUIRMENT INITIAL FINAL Page 8 SYSTEM DIAGRAM Verizon Queensbury Page 9