TAB Report - Verizon QueensburyNortheastern Air Quality, Inc.
P.O. Box 3271
Albany, New York 12203
(518) 857-3641
HVAC SYSTEMS TESTING:
Project:Verizon Queensbury
Location:Queensbury, New York
Architect:Gruskin Architecture + Design, P.C.
Spingfield, New Jersey
Engineer:Lilker Associates
New York, New York
Piping:
Sheet Metal:Brayton Construction Inc.
Date:October 10, 2024
Prepared by:N. Mailly
RKelley@NortheasternAirQuality.com
Air Balance Report
Item Page
Certification 3
Standard Abbreviations 4
Air Balance Report
Air Moving Equipment 5
Grille, Register & Diffuser Report 6
Minimum Outside Air Report 8
System Diagrams 9
Table of Contents
CERTIFICATION
PROJECT:
ADDRESS:
TESTING AND BALANCING FIRM:
CERTIFIED BY:DATE:10/10/2024
SIGNATURE:
Robert V. Kelley
Verizon Queensbury
Queensbury, New York
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM
PERFORMANCE AND WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD
PROCEDURES. ANY VARIANCES FROM DESIGNED QUANTITIES WHICH EXCEEDS NEBB
TOLERANCES ARE NOTED THROUGHOUT THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL
ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB ''PROCEDURAL
STANDARDS FOR TESTING AND BALANCING OF ENVIRONMENTAL SYSTEM'' AND THE
PROJECT SPECIFICATIONS.
Northeastern Air Quality, Inc. #3159
Page 3
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641 PROJECT:
THE FOLLOWING IS A LIST OF STANDARD ABBREVIATIONS WHICH MAY APPEAR IN THIS REPORT:
MEANING MEANING
A AMPS or AMPERAGE NL NOT LISTED
ACH AIR CHANGES PER HOUR NOM NOMINAL
AD ACCESS DOOR NOM EFFY NOMINAL EFFICIENCY
ADJ ADJUSTABLE NR NOT REQUIRED
Ak KINETIC (EFFECTIVE FREE) AREA NS NOT SPECIFIED
BG BLAST GATE OBD OPPOSED BLADE DAMPER
BHP BRAKE HORSEPOWER OED OPEN END DUCT
CALC CALCULATED PF POWER FACTOR
CALIBR CALIBRATION or CALIBRATED PH PHASE
CD CEILING DIFFUSER Ps STATIC PRESSURE
CF CUBIC FEET Pt TOTAL PRESSURE
CFM CUBIC FEET PER MINUTE Pv VELOCITY PRESSURE
cL CENTERLINE RG RETURN GRILLE
CLG CEILING RPM REVOLUTIONS PER MINUTE
CR CEILING REGISTER RR RETURN REGISTER
CS CIRCUIT SETTER SBD SINGLE BLADE DAMPER
CSD CEILING SUPPLY DIFFUSER SD SMOKE CONTROL DAMPER
DD DIRECT DRIVE SF SERVICE FACTOR
DDC DIRECT DIGITAL CONTROL SMC SHEET METAL CONTRACTOR
DISC DISCONNECT SWITCH SPS STATIC PRESSURE SENSOR
DISCH DISCHARGE SR SUPPLY REGISTER
DPR DAMPER TC TEMPERATURE CONTROL
DR PRESSURE DIFFERENTIAL TCC TEMPERATURE CONTROL CONTRACTOR
EC END CAP TCD TEMPERATURE CONTROL DAMPER
ER EXHAUST REGISTER TP THERMALLY PROTECTED
FL BHP BRAKE HORSEPOWER @ FULL LOAD AMPS TRAV DUCT TRAVERSE
FLA FULL LOAD AMPS V VOLTS or VOLTAGE
FTR FINNED TUBE RADIATION VAR VARIABLE
GPM GALLONS PER MINUTE VBD V-BELT DRIVE
HP HORSEPOWER VD VOLUME DAMPER
LD LINEAR DIFFUSER VEL VELOCITY
LF LINEAR FEET (NOMINAL)W WATTS or WATTAGE
NA NOT ACCESSIBLE WG WALL GRILLE
ND NO DAMPER WMS WIRE MESH SCREEN
NDRG NON-DUCTED RETURN GRILLE WR WALL REGISTER
NG NO GAUGE ZD ZONE DAMPER
NI NOT INSTALLED
NIC NOT IN CONTRACT
ABBREVIATIONS
Verizon Queensbury
ABBREVIATION ABBREVIATION
Page 4
Northeastern Air Quality, Inc.
P.O. Box 3271, Albany, NY 12203-0271
(518) 857-3641
10/10/2024
MOTOR
NAME-RPM
PLATE VOLTS HERTZ 208 60 208 60
DATA
EXT.
STATIC
PRESSURE
VOLTS
AMPS
BHP (calc.)
REMARKS:
* NOTE: If P.F. or NOM EFFY are NL,
(P.F. x NOM EFFY) = 746Hp/(VAX),
where X = 1 if 1 Ph, and 1.73 if 3 Ph
-
0.34
INLET NL -0.36
TOTAL CFM - OUTLETS 2850 3100 825 872
RETURN AIR CFM 2423 2591
TEST DATA DESIGN ACTUAL DESIGN
HP 3 1725 3/4 1400
PHASE
SHEAVE cL DISTANCE
FAN SHEAVE AK74 x 1"
--
VM50 x 7/8"Direct Drive
Direct Drive
A54 Direct Drive
18 3/4"
N. Mailly DATE:
AIR MOVEMENT EQUIPMENT TEST SHEET
ACTUAL
0.72
STYLE FRAME -56HZ -NL
DATE TESTED:10/10/2024 10/10/2024
MANUFACTURER Marathon Broad Ocean
3 1
FL AMPS S.F.9.5 1.15
BELTS
SYSTEM:RTU-1 (Labeled #2 on roof)RTU-2 (Labeled #1 on roof)
LOCATION:Roof Roof
MODEL:ZF102N15N2AAA7 PCG4A361003X1A
SERIAL NUMBER:N1A6283035 W1M5148419
SERVICE:Retail Sales 101 Stock Room/ Break Room
MANUFACTURER:York York
PROJECT:Verizon Queensbury
TESTED BY:
0.58
NL -0.49
OUTSIDE AIR CFM 428 468 -
NL NL NL NL
5.4 1.00
Direct Drive
TOTAL NL
DISCHARGE NL 0.22 NL
T1 - T2 208 208 208 210
FAN RPM NL 987
825 865
NL NL
TOTAL CFM - FAN NL -NL -
CALCULATED (P.F. x NOM EFFY) *
MOTOR SHEAVE
STARTER HEATER ELEMENTS
0.72
P.F.NOM EFFY
T3 (3 Ph only)6.7
T2 - T3 (3 Ph only)207
NL 0.83
T1 - T3 (3 Ph only)208
F.L.A.ACTUAL 2.28
T1 9.5 6.4 5.4 3.4
T2 (3 Ph only)6.6
0.69
Page 5
Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:
DESIGN INITIAL INTERMEDIATE FINAL % OF
NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS
RTU-1
1 Retail Sales 101 24" x 24"CD-1 375 Hood 429 Hood 373 Hood 414 110%10/10/24
2 Retail Sales 101 24" x 24"CD-1 375 Hood 360 Hood 382 Hood 410 109%10/10/24
3 Retail Sales 101 24" x 24"CD-1 375 Hood 366 Hood 381 Hood 409 109%10/10/24
4 Retail Sales 101 24" x 24"CD-1 375 Hood 320 Hood 349 Hood 414 110%10/10/24
5 Retail Sales 101 24" x 24"CD-1 375 Hood 452 Hood 392 Hood 413 110%10/10/24
6 Retail Sales 101 24" x 24"CD-1 375 Hood 377 Hood 387 Hood 412 110%10/10/24
7 Storage 104 24" x 24"CD-1 100 Hood 82 Hood 92 Hood 110 110%10/10/24
8 Modified Open Office 103 24" x 24"CD-1 250 Hood 244 Hood 244 Hood 275 110%10/10/24
9 Existing Inventory 105 24" x 24"CD-1 0.55 458.599 250 Hood 174 350 191 445 243 97%10/10/24
Total 2,850 3,100 109%10/10/24
Return
10 Storage 104 24" x 24"RG-1 NL 901 491 Hood 562 Hood 590 -10/10/24
11 Retail Sales 101 24" x 24"RG-1 NL Hood 673 Hood 673 Hood 707 -10/10/24
12 Retail Sales 101 24" x 24"RG-1 NL Hood 870 Hood 870 Hood 914 -10/10/24
15 Modified Open Office 103 24" x 24"RG-1 NL Hood 363 Hood 363 Hood 381 -10/10/24
Total 2,423 2,591 107%10/10/24
RTU-2
16 5-POS 102 24" x 24"CD-1 150 Hood 375 Hood 165 Hood 165 110%10/10/24
17 Existing Restroom 110 24" x 24"CD-1 50 Hood 48 Hood 52 Hood 55 110%10/10/24
18 Existing Restroom 109 24" x 24"CD-1 50 Hood 29 Hood 45 Hood 46 92%10/10/24
19 Break Room 24" x 24"CD-1 250 Hood 289 Hood 267 Hood 275 110%10/10/24
20 Existing Manager 106 24" x 24"CD-1 75 Hood 89 Hood 70 Hood 75 100%10/10/24
21 Break Room 24" x 24"CD-1 250 Hood 244 Hood 255 Hood 256 102%10/10/24
Total 825 872 106%10/10/24
Return
N. Mailly 10/10/2024
Verizon Queensbury
Page 6
Northeastern Air Quality, Inc.GRILLE, REGISTER & DIFFUSER REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 TESTED BY:DATE:
REMARKS:
DESIGN INITIAL INTERMEDIATE FINAL % OF
NO.LOCATION SIZE MODEL Ak VEL CFM VEL CFM VEL CFM VEL CFM DES DATE REMARKS
N. Mailly 10/10/2024
Verizon Queensbury
22 5-POS 102 24" x 24"RG-1 NL Hood 250 Hood 242 Hood 202 -10/10/24
23 Break Room 24" x 24"RG-1 NL 411 224 Hood 468 Hood 387 -10/10/24
24 Break Room 24" x 24"RG-1 NL Hood 317 Hood 336 Hood 276 -10/10/24
Total 825 865 105%10/10/24
EF-1
25 Existing restroom 110 10" x 10"NL Hood 29 Hood 131 -10/10/24
EF-2
26 Exiting Restroom 109 10" x 10"NL Hood 29 Hood 117 -10/10/24
EF-3
27 Existing Restroom 108 10" x 10"NL Hood 116 Hood 116 -10/10/24
Page 7
Northeastern Air Quality, Inc.MINIMUM OUTSIDE AIR REPORT
P.O. Box 3271, Albany, NY 12203-0271 PROJECT:
(518) 857-3641 DATE:
System Area % OF
Zone or Branch Sq. Ft.VEL CFM VEL CFM SETPOINT VEL CFM SETPOINT DES DATE
Min Outside Air
AHU-1 (Existing)20''x 28''3.93 109 428 119 468 10%109%10/10/24
Verizon Queensbury
10/10/2024
Duct Size
DESIGN REQUIRMENT INITIAL FINAL
Page 8
SYSTEM DIAGRAM
Verizon Queensbury
Page 9