2024-0287 SEPTIC VARIANCE Office Use Only
Permit#: 20 2-4 .1)21j9'
Ar PL_( A 1 IO Permit Fee: $ i to J
Town of Qacensbury r�
742 Bay Road,Queensbury,NY 1280
L \J Invoice#:C '�l\
P:518-761-8256 www..ueensbur . = I Approvals:
JUN 12 201.4
Submittal: 1 (one) o gi .y 4` •cnb� 1e ��6mpleted application package
BUILDING&CO
PLEASE PRIN : OR TYPE, PLEASE INCLUDE AN EMAIL
Section 1:
Contact Information:
Property Owner(s): Adam and Tryntze Conway Owner's Agent: HUTCHINS ENGINEERING,PLLC
Address: 73 N. Helderberg Parkway Address: 169 HAVILAND ROAD
Slingerlands, NY 12159 QUEENSBURY,NY 12804
Phone#: 518-810-3960 Phone#: 518-745-0307
Email: tryntzeconway@gmail.com; aconway1999@yahoo.com Email: thutchins@hutchinsengineering.com
Section 2:
Site Information:
Site Address: 74 Reardon Road Tax ID#: 289.11-1-36
Directions to Site: from Bay Rd turn left on Tee Hill Rd for 0.6 miles; left on Reardon Rd for 0.3 miles (on right)
Section 3:
105'(absorption field)21'(pump station)
Distance from well on property to septic system(if applicable) feet
Section 4:
Is it possible to install a conforming septic system on this property? ❑Yes ❑■ No
If YES, please explain and attach a diagram:
Section 5:
Does the proposed system meet setback requirements for distance from wells&septic systems on neighboring
properties? *Yes ❑ No If NO, please explain:
Section 6:
Is the proposed system to be installed under a parking area? ❑Yes No
Section 7:
Section of the Sanitary Sewage Ordinance from which you are seeking the variance (i.e. leaching system will be 89 ft.
from well in lieu of required 100 ft.): see plans for list
Septic Variance Application Revised December 2021
f
Section 3:
List the names, parcel addresses, and tax map numbers of all adjoining property owners. You may obtain this
information from the Town of Queensbury's Assessor's Office:
North Name Seidel Family Irrevocable Trust
Address 70 Reardon Road
Tax Map ID 289.11-1-37
South Name Sharon Stephenson
Address 76 Reardon Road
Tax Map ID 289.11-1-35
East Name Jeffrey Robillard
Address 66 Hall Road
Tax Map ID 289.11-1-59.121
West Name Glen Lake
Address
Tax Map ID
Section 9:
OWNER STATEMENT
I/We do hereby relieve the Town of Queensbury from any liabilities on the plumbing and septic system located at:
74 Reardon Rd . I/We realize that putting the pump station less than the required 50 feet
from the well may increase the risk of pollution.
Owner—Print Name: Tryntze or Adam Conway
Owner—Signature:
Date: 06/12/2024
Section 10:
NEIGHBOR OR TENANT RELEASE STATEMENT(If applicable)
I/We do hereby relieve the Town of Queensbury from any liabilities on the plumbing and septic system located at:
I/We realize that putting the well, septic tank or leaching system less than the required feet
from the may Increase the risk of pollution.
Neighbor/Tenant—Print Name:
Neighbor/Tenant-Signature: Date:
Septic Variance Application Revised December 2021
I i1
i (J-
Section 11:
AUTHORIZATION AND SIGNATURE PAGE
This page includes the Authorization to Act as Agent form, engineering fee disclosure, authorization for site
visits, other permit responsibilities and agreement to provide documentation required.
Complete the following if the OWNER is using an Agent:
Owner's Name: Tryntze and Adam Conway
HUTCHINS ENGINEERING PLLC
Designates: as agent regarding the Septic Variance for -
_
Site Address: 74 Reardon Road _
Tax Map#: 289.11-1-36
Engineerink,Fee-Disclosure: Applications may be referred to the Town consulting engineer for review of septic
design,storm drainage, etc. as determined by the Town Board of Health. Fees for engineering review services
will be charged directly to the applicant.
Authorization.for Site Visits! By signing this page and submitting the application materials attached herein,the
Owner,Applicant and his/her/their agent hereby authorize the Town Board of Health, building and code
Enforcement Officers and Town Engineer to enter the subject properties for the purpose of reviewing the
application submitted.
Please Note: Other permits may be required for construction or alteration activity subsequent to approval by
the Town Board of Health. It is the applicant's responsibility to obtain any additional permits.
Official MeetingiMinutes Disclosure:-!t is the practice of the Town Board of Health to have a designated
stenographer tape record the proceedings of the meetings resulting from the application, and that the
minutes transcribed from those tapes constitute the official record of all proceedings. If there is a discrepancy
between such record and the handwritten minutes taken by the designated stenographer,the handwritten
minutes shall be deemed the official record.
I,the undersigned, have thoroughly read and understand the instructions for submission; agree to the
submission requirements and completed checklist:
OWNER—PRINT NAME:,Tryntze or Adam Conway
OWNER—SIGNATURE: - - - DATE: 6 . I ,
•
AGENT—PRINT NAME: P.E.
.mas ';.0 ins, P.E.
-itAGENT—SIGNATURE: DATE: �j f�`.
Septic Variance Application Revised December 2021
169 Haviland Road
Queensbury, NY 12804
Hutchins Engineering PLLC Phone: (518)745-0307
Fax: (518) 745-0308
June 12, 2024
Town of Queensbury Local Board of Health
742 Bay Road
Queensbury NY 12804
Re: Adam and Tryntze Conway— 74 Reardon Road, Glen Lake
Septic Variance
Tax Map ID: 289.11-1-36
Dear Supervisor Strough and Town Board Members:
This office represents Adam and Tryntze Conway with respect to a wastewater system installation
at their 74 Reardon Road property.
Currently, the residence is served by an antiquated single-vessel system that is within 50' of Glen
Lake.
Variance requests to the Local Board of Health are as follows:
1) 23' from the pump station to the onsite well instead of the required 50';
2) 3' from the pump station to the house instead of the required 10';
3) 3' from the pump station to the south property line instead of the required 10';
4) 21' from the forcemain to the onsite well instead of the required 50';
5) 5' from the forcemain to south property line instead of the required 10'
We respectfully request that this application be placed on the Town Board's meeting agendas for
the next upcoming meetings. Please contact me with any questions that you may have or if you
would like to perform a site visit. Thank you for your assistance with the project.
Best regards,
G. Thomas Hutchins, P.E. 1VECEDVE
Enclosures
JUN 12 2024
Cc. Adam and Tryntze Conway
TOWN OF QUEENSBURY
BUILDING&CODES
Hutchins Engineering PLLC
292293-Conway
Zl_
7'± To Ihore--
/ La
Glen & h:%N/vn/ro
B:635 P
289. 1 1-1-3
n
Lands N/F of
Richard & Tina DeMarsh
B:6850 P:48`
® �=6 043
1�y p. 00 , E� ``/ k25 9 9 R0
f
SITE LOCATION LOCATION MAP
WASTEWATER SYSTEM DESIGN
3-BEDROOM RESIDENCE (DESIGN TO 4)Cc
DESIGN FLOW - 110 GPD/BEDROOM
3
SYSTEM DESIGN FLOW - 440 GPD
r (D A
PUMP STATION-4'0 PRECAST CONCRETE WITH DUPLEX
< a 1
GRINDER PUMPS.
_ W
SEPTIC TANK -1500 PRECAST CONCRETE DUAL
COMPARTMENT
((D a 7
va M
DESIGN APPLICATION RATE: .95 GPD/SF, BASED ON
1-5 MIN/IN PERCOLATION RATE
rt
CL-
9 H
UP NYT9
S
ABSORPTION BED AREA REO D - (440 GPD)/(.95 GPD/SF) � p
\ lti St \ - _ .. 463 SF
-
A�
S a117C� � � � PROPOSED 1.5 \ . =yW `� 0
.� s`�'ak � _.a.,��,:. 5 ,,.., ,/ .� . /i __ _.- � a
USF �00 �y,- _ r_ .� ,. - - �. / FORCEMAIN - �.._. _._ ..�
® a ABSORPTION BED AM PROWDED= 15 x40 = 600 SF
\ \
E \ t _.. \ V
Sq: Feet
ea
7,1 Acres , /.._ CIP_S
��, POTABLE WATER SUPPLY IS TO BE ON -SITE WELL
\ \ >..
0 ::.\ / h q Crushed Stone �. \ \ p'
PROPOSED 1.5
,
FORCEMAIN _
p PROPOSED 1500 GALLON DUAL — - -
COMPARTMENT POLYETHYLENE
SEPTIC TANK = _.... — _ _... _.._.. __. _ _.._ i
•\ \ an N/F of - f /.` qif�. -oo , ' - - - SYSTEM MATERIAL SPECIFICATIONS
August &/Louise %cKasty Estate 4 ' __ - �.'PROPOSED 15X40ABSOPRTION BED tiF ABSORPTION BED AGGREGATE
B.4922 03 0 1 11 / G, /
CIRF
289. I - -34 pSF N J5._ 044 13 ,. / y�0 , .
_ 0 1 WASHED CRUSHED STONE
- /
STONE IS TO BE 3 4" T 1 2"
r ,
/
42
EFFLUENT SEWER PIPE
Z ���` � � _:: - �� � -_.. _ ._ ....._ —,T � _..... '" " '� � � '. '�,NS PIPING TO BE 4" SDR-35 OR SCHEDULE 40 PVC. INSTALL WITH 1/8" PER FOOT MINIMUM SLOPE.
3
4 FILTER FABRIC
,
...�QQ._ FILTER FABRIC TO BE 4.8 OZ/SY NON -WOVEN SEPARATION FABRIC, TENCATE MIRAFI 140N OR EQUIVALENT.
- K
drs i Lands N/ of - _ i-- — C ^, FORCEMAIN
-
��� a 43 - _
._ - - —
Ronald B. &Cynthia F. Mackowiak �'
PIPING TO BE 1 / SDR HD PROVIDE POSITIVE DRAINBA TO PUMP STATION
B:578 P:236 O s
1
Q—
\ 28 289.1 1-) 33 � --- - _ � \`� � � HOUSE SEWER PIPE h . z — — _ _` �. ` y PIPING TO BE 4" SDR-35 OR SCHEDULE 40 PVC. INSTALL WITH 1/4" PER FOOT MINIMUM SLOPE.
-
/ _ SYSTEM FILL
l `�✓o/non -CIPF ^ ®' ! AS DESCRIBED IN FILL MATERIAL NOTES
i TOPSOIL D
r
PLACE 4 MINIMUM TOPSOIL OVER ENTIRE
BACKFILL AREA. SEED, MULCH, AND ESTABLISH TURF.
i
CIRF
� � ts' lam` .. '-...,.. �-. •, .... '—.. .._ " - O }'•�a ._ - ,..
,
_ G
SYSTEM INSTALLATION NOTES
CONSTR7
CTION
LL BE AS
HOWN ON
HIS DRAWING AND IN ACCORDANCE KITH THE N.Y.S. DEPARTMENT OF
_ , _ AND ASTM F481 INSTALLATION OF THERMOPLASTIC PIPE AND CORRUGATED
.._ •,-. .... _.__ .._._ . - _.__ - __ --_ __ _ ___. ,_.'', ... �'� � HEALTH�NDIVIDUALAHOUSEH OLDSSYSTEMS T
_
_._ TUBING IN SEPTIC TANK LEACH FIELDS.
LONG ABSORPTION BED TO THE DEPTH REQUIRED, THE WALLS AND FLOOR
HALL BE CLEANED AND RAKED IN ORDER TO LOOSEN SMEARED AREAS OF SOIL
N- - -- --` "- - - _ __ PLACEMENT OF CRUSHED STONE, PERFORATED PIPE AND FILTER FABRIC SHALL BE AS SHOWN, AND CARE SHALL BE
_ EXERCISED TO AVOID INCLUSION OF FINE GRAINED SOILS AND WASTE MATERIAL IN THE STONE AND PIPE.
- --
_ _
- '_-- ,_ ` _. THE PIPE SHOULD BE LAID AT THE GRADES INDICATED MAINTAINING STRAIGHT CONTINUOUS GRADES WITHOUT SAGS
/
HUMPS , SEPARATED JOINTS, OR OTHER UNSUITABLE CONDITIONS. PIPE SHALL BE LAID WITH HOLES DOWN IN ALL
dy...t a
-~
CASES.
-
' ALL DISPOSAL FIELDS SHALL BE GRADED 0 SHED RAINFALL AND DIVERT SURFACE RUNOFF AWAY F THE
/ X - - - ...... _._ - - (D -
'�
,r. _' _ DISPOSALOFIELLD.F
1PP- ` T FROM
-. DO NOT USE HEAVY EQUIPMENT WITHIN THE ABSORPTION AREA AFTER PIPING HAS BEEN INSTALLED.
WASTEWATER SYSTEM PLAN
SCALE: 1 "=20'
GRAPHIC SCALE
110 Q 1,0 21C 40
( IN FEET )
CONTRACTOR TO FIELD VERIFY LOCA11ONS AND DISTANCES
VARIANCE REQUEST SUMMARY
THE FOLLOWING RELIEF IS REQUESTED FROM THE TOWN OF QUEENSBURY
SANITARY ORDINANCE:
) INSTALL PUMP STATION 23' FROM WELL IN LIEU OF REQUIRED 50'.
INSTALL PUMP STATION 3' FROM BUILDING FOUNDATION IN LIEU OF REQUIRED 10'.
) INSTALL PUMP STATION 3' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'.
) INSTALL FORCE MAIN 21' FROM WELL IN LIEU OF REQUIRED 50'.
c1 MOTAI i rnonr MAIN 5' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'.
V/ 119J1/ " 1 VI\VL
THE WASTEWATER TREATMENT SYSTEM IS DESIGNED AND APPROVED BASED UPON THE INSTALLATION OF WATER
CONSERVING FIXTURES AND A DESIGN FLOW OF 110 GPD PER BEDROOM. THE SYSTEM IS NOT DESIGNED TO
ACCOMMODATE EXTREME WATER USE FIXTURES, SUCH AS JACUZZI-TYPE SPA TUBS OR WATER TREATMENT
EQUIPMENT. THE INSTALLATION OF NON -CONSERVING WATER FIXTURES OR EXTREME WATER USE FIXTURES IS
CONTRARY TO THE APPROVAL OF THIS WASTEWATER TREATMENT SYSTEM.
ROOF, FOOTING, GARAGE, CELLAR AND SURFACE WATER DRAINAGE MUST BE EXCLUDED FROM THE WASTEWATER
SYSTEM.
CONSTRUCT DRAINAGE SWALE UPGRADE OF SYSTEM IN ORDER TO DIVERT SURFACE RUNOFF AROUND ABSORPTION
FIELD.
SEPTIC TANK, PUMP STATION & ABSORPTION BED MUST BE INSPECTED BY LOCAL BUILDING DEPARTMENT AND
DESIGN ENGINEER PRIOR TO BACKFILL AND FINAL GRADING. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
IDENTIFY THE NECESSARY PARTIES AND REQUEST INSPECTIONS.
MAP REFERENCE:
1. BASE MAP INFORMATION FROM "MAP OF A
TOPOGRAPHIC SURVEY MADE FOR TRYNTZE &
ADAM CONWAY" BY VAN DUSEN & STEVES
LAND SURVEYORS, JANUARY 17, 2024.
Dig ® Safely.
NewYork
Call Before You Dig
Wait The Required Time
IS Confirm Utility Response
IM Respect The Marks
® Dig With Care 800.962- 1�y
962
www.digsafelynewyork.com
d-
o N
N_
\ C)
o z
ALTERATION OF THIS DOCUMENT
EXCEPT BY A LICENSED
PROFESSIONAL ENGINEER IS A
Hutchins
Engineering
PLLC
169 HoAand Road
Queensbury, NY 12804
(518) 745-0307 Phone
(518) 745-0308 Fax
TAX MAP # 289.1 1 -1 -36
WASTEWATER
SYSTEM PLAN
& DETAILS
prepared for:
Tryntze and Adam
Conway
74 Reardon Road
Town of Queensbury,
County of Warren,
State of New York
WASTEWATER SYSTEM SETBACK REQUIREMENTS
STREAM, LAKE,
PROPERTY LINE HOUSE 07ERCOURSE, WELL
WETLAND
SEPTIC TANK 10' 10' 50' 50'
ABSORPTION FELD 10' 20' 1 100' 1 100'
Drawn: AVA Checked. GTH
Scale. NOTED Date: 03/06/2024
292293-01 -S1
CAST IRON MANHOLE COVER
W/WATER TIGHT INSERT
PRECAST CONCRETE
RISER
a
4" PVC SDR-35
INLET
LAG/ALARM 3" ABOVE
'PUMP ON'
°
LEAD PUMP ON
PUMP OFF
VOLUME OF DOSE TO
BE 60 f GALLONS
(7-8" BETWEEN ON
AND OFF LEVELS)
EXTERIOR WEATHERPROOF JUNCTION BOX (IF NECESSARY).
POLYETHYLENE EXTENSION TO
POLYETHYLENE EXTENSION TO
SEAL CONDUIT GAS TIGHT. INSTALL CONTROL PANEL IN HOUSE.
GRADE WITH TAMPER RESISTANT
APPROXIMATE
GRADE WITH TAMPER RESISTANT
ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED
ACCESS COVER
FINISH GRADE
ACCESS COVER
ELECTRICAL INSPECTION AGENCY PRIOR TO START-UP OF PUMP
STATION.
12"f
TEE BAFFLE
-
12" MIN. COVER
4" SCH. 40 PVC
7:
DISTRIBUTION BOX
3"
y INLET
4" SDR-35 PVC
LIQUID LEVEL
OUTLET
MIN. SLOPE
1/4" PER FOOT
MIN. SLOPE BAFFLE
2" HDPE SDR-11
15
18"
"
118 PER FOOT
FORCEMAIN
MIN.
WATERTIGHT SLEEVE
USE SPEED LEVELERS TO ASSURE ALL OUTLETS
AND SEAL (TYP.)
118" LONG I
ARE AT EXACTLY THE SAME ELEVATION
BALL VALVE
LIQUID 51 "
4" PVC SDR-35 SOLID HEADER TO ABSORPTION
DEPTH
FIELD, 118" PER FOOT MIN SLOPE
-�
40"
16" MIN.
4' DIAMETER PRECAST
CONCRETE PUMP STATION WITH TRAFFIC
AND ACCESS MANWAY
INSTALL FLOAT SWITCHES TO
OPERATE PUMP AND MAINTAIN
LEVELS AS INDICATED
1-1/2" SCH-40 PVC INSIDE
WET WELL THROUGH WALL
UNION - LOCATE SUCH THAT UNION
CAN BE DISCONNECTED AND PUMP
REMOVED WITHOUT TANK ENTRY
REDUCING TEE POINTED DOWNWARD WITH 1"
BALL VALVE THROTTLED TO ALLOW TRICKLE
DRAIN BACK INTO WETWELL
=oVE BALL CHECK VALVE
DUPLEX GRINDER
PUMPS
PUMP STATION NOTES
GRINDER PUMPS TO BE LIBERTY PROVORE 380 SERIES 1 HP
RESIDENTIAL GRINDER PUMPS IN 4' DIAMETER PRECAST CONCRETE
BASIN WITH TRAFFIC COVER.
SEAL ALL TANK OPENINGS WATERTIGHT.
PROVIDE AND INSTALL UL LISTED PACKAGED PUMP CONTROL PANEL
WITH VISUAL AND AUDIBLE ALARM. INSTALL DUPLEX, DEMAND
DOSE CONTROL PANEL IN BASEMENT UTILITY ROOM IN
COORDINATION WITH OWNER.
INSTALL POWER & CONTROL WIRING TO CONTROLLER WITH ALARM
IN HOUSE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS
AND NATIONAL ELECTRIC CODE (N.E.C.) REQUIREMENTS.
GRINDER PUMPS TO BE LIBERTY PROVOKE PRG-102M,
230V, 1 HP, 25 GPM ® 30 FT TDH.
VERIFY EXISTING ELECTRICAL SERVICE PRIOR TO PURCHASING
PUMPS.
ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED
ELECTRICAL INSPECTION AGENCY PRIOR TO START-UP OF PUMP
STATION.
1,500 GALLON --I
POL YETHYLENE
SEPTIC TANK
4.
6"f PEA GRAVEL
PUMP STATION & SEPTIC TANK DETAIL
SCALE: NTS
4" TOPSOIL COVER ABOVE 4" PVC PERFORATED
TOP OF STONE BED; LATERAL INSTALLED LEVEL,
SEED &ESTABLISH TURF IN BED CONFIGURATION WITH 5.00' PIPE 2 ' TO EL
MANIFOLDED ENDS SPACING OF BED
nn irp ,
NTS
FILTER FABRIC
MIRAFI 140N OR
EQUAL
2" MIN.
2" MIN. DROP
BETWEEN INVERTS
SEPTIC TANK NOTES
ALL UNITS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT
OF HEALTH AND SHALL BE OF PREFABRICATED POLYETHYLENE.
ALL STRUCTURES SHALL BE PLACED ON 6"t LEVEL PEA GRAVEL BASE. WHERE EXISTING
SOIL CONDITIONS ARE UNSUITABLE, CRUSHED STONE SHALL BE PLACED UNDER PEA GRAVEL
AS NECESSARY TO ACHIEVE A STABLE BASE.
RUBBER GASKETS SHALL BE INSTALLED IN ALL INLETS AND OUTLETS.
INSTALL, BACKFILL, & FILL TANK IN STRICT CONFORMANCE WITH TANK MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS.
PROVIDE COPY OF MANUFACTURER'S INSTALLATION INSTRUCTIONS PRIOR TO INSTALLATION.
40'
15'
NTS RPTION BED PLAN
LIMIT OF 15'x4O'
STONE BED
4" PERFORATED PVC LATERALS
INSTALLED NEAR LEVEL IN
BED CONFIGURATION
PROPOSED
DISTRIBUTION BOX
TRANSITION FORCE
MAIN TO 4" PVC
OUTSIDE OF D-BOX
Dig Safely.
Nwork
New
® Call Before You Dig
El Wait The Required Time
El Confirm Utility Response
El Respect The Marks
El Dig With Care
800.962.7962
www.digoafelynewyork.com
O
�
N
�
O
U
z
Q
U
O
W
cn
j
o
�
w
z
ALTERATION OF THIS DOCUMENT
EXCEPT BY A LICENSED
PROFESSIONAL ENGINEER IS A
Hutchins
Engineering
PLLC
169 Haviland Road
Queensbury, NY 12804
(518) 745-0307 Phone
(518) 745-0308 Fax
TAX MAP # 289.11-1-36
prepared for:
Tryntze and Adam
Conway
74 Reardon Road
Town of Queensbury,
County of Warren,
State of New York
drawn: AVA
Checked: GTH
male: NOTED
Date: 0310612024
292293-01-S2
Office Use Only
SEPTIC DISPOSA P��?La.C�T�l Permit#: 20?fit -0�`�
l ' i `� i,_,, ill f r i e rj
Permit Fee:$
Town of Quccns6ury i
742 Bay Road,Queensbury,NY 12804 11)111l J AIN 02 znifi� j Invoice#:
P:518-761-8256 www.queensburv.net
-!°vb�liVO , U Flood Zone? Y TY N
Wetlands?
Reviewed 74 Reardon Road _ BUILDING CODES
Project Location: ,
Reviewed B
Tax Map #: 289.11-1-36
STRUCTURE INFORMATION Garba Grinder Yes No
Year Built Gallons #of X gallons per =total daily flow Installed? Ir l
Per day Bedrooms Bedroom
1980 or 150 Spa or Hot Tub
older Installed? 1
1981-1992 130
1992-Present 110 3 110 330
PARCEL INFORMATION
TOPOGRAPHY Flat Rolling 1 Steep Slope 15+a% Slope
SOIL NATURE Ve Sand Loam Clay Other, explain:
GROUNDWATER At what depth: > 84"
BEDROCK/IMPERVIOUS MATERIAL At what depth: >84"
DOMESTIC WATER SUPPLY Municipal I Well Lake (if well or lake, water
supply from any septic system absorption is >10o feet)
PERCOLATION TEST Rate: 3:30 per minute per inch (test to be completed
by a licensed engineer/architect)
PROPOSED SYSTEM INFORMATION
TANK SIZE 1,500 gallons (min. size 1,000 gallons, add 250 gallons for each garbage
cylinder or spa/hot tub
SYSTEM Absorption field w/#2 stone _ Total length ft. Each trench ft.
Seepage pit w/#3 stone How many: ; Size:
Alternate system Bed or other type: 15'x 40'=600 SF
Holding tank system Total required capacity: ; tank size:
• # of tanks:
Septic Alteration Application Revised May 2024
CONTACT INFORMATI ON: PLEASE PRINT LEGIBLY OR TYPE, PLEASE INCLUDE AN EMAIL
• Applicant:
Name(s): Adam and Tryntze Conway
Mailing Address, C/S/Z: 73 N. Helderberg Parkway Slingerlands, NY 12159
Cell Phone: 518-810-3960 Land Line:
Email: tryntzeconway@gmail.com; aconway1999@yahoo.com
• Primary Owner(s):
Name(s): same as applicants
Mailing Address, C/S/Z:
Cell Phone: Land Line:
Email:
_Check if all work will be performed by property owner only
• Contractor:
Contact Name(s): Stone Installations-Dean Burdick
Contractor Trade: Excavation/Installation
Mailing Address, C/S/Z: 4305 Route 50 Saratoga Springs NY 12866
Cell Phone: Land Line: 518s-564=11348--
Email: dean@stoneindustries.com
**Workers' Comp documentation must be submitted with this application**
• Engineer(s):
Name(s): Hutchins Engineering PLLC
Mailing Address, C/S/Z: 169 Haviland Road Queensbury, NY 12804
Cell Phone: Land Line: 518-745-0307
Email: thutchins@hutchinsengineering.com
Contact Person for any questions regarding this project: Tom Hutchins
Cell Phone: Land Line: 518-745-0307
Email: thutchins@hutchinsengineering.com
Declaration: Any permit or approval granted which is based upon or is granted in reliance
upon any material representation or failure to make a material fact or circumstance known by
or on behalf of an applicant, shall be void. I have read the regulations and agree to abide by
these and all requirements of the Town of Queensbury Sanitary Sewage Disposal Ordinance.
PRINT NAME: G. 4homas Hutchins, P.E. (AGENT)
SIGNATURE: � v� _, _ . C� DATE: 08/02/24
Septic Alteration Application Revised May 2024
10/15/2024 13:18 7981584 RON MUMBLO PAGE 02
?4•,..k:••. : I i : .• cOpyiMONWEACIII ELECTIUCAL INSVACTIpN i 4ia
1 •
66-:, '• . ,, 1. spRVICE,INC.DupucATE CERTiricATV,
%-..,.. . .. . Fur Municipal Confirmation Oniy
lo,l.c.,•• 1 • l l ' ;' ; • i , .1 • • •• 4..441
. iics;•:„' ' •• ,• TYPE OF INSPECTION 5 552
• . . ..,•••••,,,•,,
4i•.•,:• i •;1 " • . •,,,•••.:31.:•.../..1!
gi'4')',•:. !. i! e '
• Cut-in Card No
• WI '
Prmit No i
i . :I • i •-,,q011.,
•• •
("k:.; ' • i . .! Owner ir.".-4i OA .,-- Come-Lz .,71 :.
• •
{ • ....r3.*:.;,.4
4.....!..:. i• • 't.kq.. ft enAit.ro 9.1. a r) . • 't • • 1:•hip
tig: ': • i . : i..ocntion
f,;N•.• ., . 1
' • i : . : Installation Consisting'lit • •
' i L•4.1
'.;il0,1
i,=•' ! • ' • I.!si8t:lw.,:::;1. , , .i I• 'l . ,..y.7.4;,p."7" ..,J,...y0 L,r.„>•• __....
1
I . :.:Irki41
• ,..•..,...1`i,
[x.f., : • , I l
'ile I .7 -r • . •
, ;i•,Alt
• I i Installed 13y ''.. ' ''''.2..CA'. ..I .::,...i),"Iiid*'rAP'2 "..3
EO! • t I • 1 5iP1
gei•,'•. ; • • • TtIC conditions fo1la4ing governed the issuance of this certifictue,and any cdrtifictitc p!•eviously i'sued • .....,)'NO.
. ./ .,•••• .
is cancelled:- lo. ! • ••.l.:1P.11
l'his ceniankite only 41Vers the electrical equipment and installation traditietis tis.of tittte,Upon t a '.'•'-tp
3;;;.4.• .. . •;.P '',..,Z..:.
introduction of add incti itional clwipt or altenttions,application shall he prnmptly ra.ijatbi:inspcctioh.). ! . .. Inspectors'of this Co+pany shall have the privilege of making insp ,:tinrci at luiytlinc,and it its r ilos. . :'
.,,, • arc violated,the Company hallt: have the right to revoke this c° Itieate. l•.,, I • /::lo,,o'illS';7:'' • ;.• ..e.c.1
, er„...1f t ,,I,e,....-- ;., :;•4;g4,,
4V ••
D ic:• - icale i- LH I NS P le.Cl'OR •"1-2Y-- LS s,,esepki,:- .1-'
%.:.?'','.' • • 1 •:::AO
BP/12024 •1••
! . ••••• Moithpr N.F,P.,i.,•1.4..Lt. • . A.,;:tt
E GTE {1 0:4 lt,
TOWN OF QLJEENSBURY
BUILDING &CODES
J
RESOLUTION APPROVING ADAM AND TRYNTZE CONWAY'S
APPLICATION FOR SANITARY SEWAGE DISPOSAL VARIANCES
RESOLUTION NO.: BOH 62,2024
INTRODUCED BY: Mr.Harrison Freer
WHO MOVED ITS ADOPTION FILE COpy
SECONDED BY: Mr.Michael Dixon
WHEREAS,Adam and Tryntze Conway(Applicants)filed an application for variances from
provisions of the Town of Queensbury On-Site Sewage Disposal Ordinance, Chapter 136 to install a
replacement on-site wastewater system with certain of its components to be located as follows:
1. Pump station 23' from the onsite well in lieu of the required 50' setback;
2. Pump station 3' from the house in lieu of the required 10' setback;
3. Pump Station 3' from the south property line in lieu of the required 10' setback;
4. Force main 21' from the onsite well in lieu of the required 50' setback; and
5. Force main 5' from the south property line in lieu of the required 10' setback;
on property located at 74 Reardon Road in the Town of Queensbury,and
WHEREAS,the Town Clerk's Office published the Notice of Public Hearing in the Town's
official newspaper and the Local Board of Health duly conducted a public hearing concerning the
variance requests on Monday,July 1st,2024,and
WHEREAS, the Town Clerk's Office has advised that it duly notified all property owners
within 500 feet of the subject property,
NOW,THEREFORE,BE IT
RESOLVED,that
1. due to the nature of the variances, the Local Board of Health determines that the
variances would not be materially detrimental to the purposes and objectives of this
Ordinance or other adjoining properties nor otherwise conflict with the purpose and
objectives of any Town plan or policy; and
2. the Local Board of Health finds that the granting of the variances is necessary for the
reasonable use of the land and are the minimum variances which would alleviate the
specific unnecessary hardship found by the Local Board of Health to affect the
Applicants; and
BE IT FURTHER,
RESOLVED, that the Local Board of Health hereby approves the application of Adam and
Tryntze Conway for variances from the Sewage Disposal Ordinance to install a replacement on-site
wastewater system with certain of its components to be located as follows:
1. Pump station 23' from the onsite well in lieu of the required 50' setback;
2. Pump station 3' from the house in lieu of the required 10' setback;
3. Pump Station 3' from the south property line in lieu of the required 10' setback;
4. Force main 21' from the onsite well in lieu of the required 50' setback; and
5. Force main 5' from the south property line in lieu of the required 10' setback;
on property located at 74 Reardon Road in the Town of Queensbury and bearing Tax Map No:
289.11-1-36.
Duly adopted this 1st day of July,2024,by the following vote:
AYES : Mr. Freer,Mr. Dixon,Mr. McNulty,Mr. Strough,Mr. Metivier
NOES : None
ABSENT: None
Glen Lake
/La dS N/F Of sue\ Io°Oak I.. w —.�,,, - ♦.......
/ m / 4 oak `. ; ' `�.+ _ ♦ PUMP STATION-4 0 PRECAST CONCRETE WITH DUPLEX
Glen & Sharon PROPOSED 4 �� / ��y`" w
6:635 P BUILDING SEWER I
.-" , � � , � � - � � GRINDI�R PUMPS
2., i i SEPTIC TANK —1500 PRECAST CONCRETE DUAL
I289. - 3G a �► A� �' 8" Oak - COORDINATE ASPHALT ROAD CROSSING IMTH ' -
PRO OSED GRINDER f i4 - COMPARTMENT
�PF
we / QUEENSBURY HIGHWAY DEPARTMENT PRIOR
UMP STATION ;
e 2f. TO WORK. (518)761-8212. SAWCUT EXISTING
ASPHALT AND REPLACE PFR 1-IIGHWAY ,
r"
- DESIGN APPLICATTOII RATE: .95 GPD/SF, BASED ON
WASTEWATER SYSTEM PLAN
SCALE: 1 "=20'
GRAPHIC SCALE
10 Q 'i 10 20 410
( IN FEET )
CONTRACTOR TO FIELD VERIFY LOCATIONS AND DISTANCES
SITE SOILS DATA
TEST PIT
TP-1 — 611812024 BY TOM HUTCHINS, P.E.
WOODS AREA UP HILL — EL. 439'
WOODS DUFF
0-6" — WOODS TOPSOIL
6-32" — RED —BROWN SILTY FINE SAND
32-60" — LIGHT BROWN FINE SAND
60-84" — GRAYISH BROWN FINE SAND
DRY ALL DEPTH
NO GROUNDWATER EVIDENCE
ROOTS TO 80"
NO BOUNDARY CONDITION TO 84"
PROVIDE 240 VERTICAL SEPARATION TO
BOUNDARY CONDITION
PERCOLATION TEST
PT-1 - BY TOM HUTCHINS, P.E.
STABILIZED PERCOLATION RATE = 3.30 MIN/INCH
Dig Safely.
New®YOrk
M Call Before You Dig
M Wait The Required Time
® Confirm Utility Response
M Respect The Marks
E3 Dig With Care
800-962-7962
www.digsafelynewyork.com
. SEPTIC TANK _ - ,_.. 289.11-1-36 2024-0287
VARIANCE REQUEST SUMMARY
THE FOLLOWING RELIEF IS REQUESTED FROM THE TOWN OF QUEENSBURY
SANITARY ORDINANCE:
1) INSTALL PUMP STATION 23' FROM WELL IN LIEU OF REQUIRED 50'.
2) INSTALL PUMP STATION 3' FROM BUILDING FOUNDATION IN LIEU OF REQUIRED 10'.
3) INSTALL PUMP STATION 3' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'.
4) INSTALL FORCE MAIN 21' FROM WELL IN LIEU OF REQUIRED 50'.
5) INSTALL FORCE MAIN 5' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'.
THE WASTEWATER TREATMENT SYSTEM IS DESIGNED AND APPROVED BASED UPON THE INSTALLA77ON OF WATER
CONSERVING FIXTURES AND A DESIGN FLOW OF 110 GPD PER BEDROOM. THE SYSTEM IS NOT DESIGNED TO
ACCOMMODATE EXTREME WATER USE FIXTURES, SUCH AS JACUZZI—TYPE SPA TUBS OR WATER TREATMENT
EQUIPMENT. THE INSTALLA7TON OF NON —CONSERVING WATER FIXTURES OR EXTREME WATER USE FIXTURES IS
CONTRARY TO THE APPROVAL OF THIS WASTEWATER TREATMENT SYSTEM.
ROOF, FOOTING, GARAGE, CELLAR AND SURFACE WATER DRAINAGE MUST BE EXCLUDED FROM THE WASTEWATER
SYSTEM.
CONSTRUCT DRAINAGE SCALE UPGRADE OF SYSTEM IN ORDER TO DIVERT SURFACE RUNOFF AROUND ABSORPTION
FIELD.
SEPTIC TANK, PUMP STATION & ABSORPTION BED MUST BE INSPECTED BY LOCAL BUILDING DEPARTMENT AND
DESIGN ENGINEER PRIOR TO BACKFILL AND FINAL GRADING. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
IDENTIFY THE NECESSARY PARTIES AND REQUEST INSPECTIONS.
MAP REFERENCE:
1. BASE MAP INFORMATION FROM "MAP OF A
TOPOGRAPHIC SURVEY MADE FOR TRYNTZE &
ADAM CONWAY" BY VAN DUSEN & STEVES
LAND SURVEYORS, JANUARY 17, 2024.
WASTEWATER SYSTEM SETBACK REQUIREMENTS
STREAM, LAKE,
PROPERTY LINE HOUSE WATERCOURSE, WELL
WETLAND
SEPTIC TANK 10' 10' 50' 50'
ABSORPTION FIELD 10' 1 20' 1 100' 100'
00
o
ALTERATION OF THIS DOCUMENT
EXCEPT BY A LICENSED
PROFESSIONAL ENGINEER IS A
Hutchins
Engineering
PLLC
169 Haviland Road
Queensbury, NY 12804
(518) 745-0307 Phone
(518) 745-0308 Fax
TAX MAP # 289.11-1-36
WASTEWATER
SYSTEM PLAN
& DETAILS
prepared for.
Tryntze and Adam
Conway
74 Reardon Road
Town of Queensbury,
County of Warren,
State of New York
Drawn: AVA Checked: GTH
Scale: NOTED Date: 0310612024
292293-01 -S1
Dig g Safely.
NewIYork
EXTERIOR WEATHERPROOF JUNCTION BOX (IF NECESSARY).
SEAL CONDUIT GAS TIGHT. INSTALL CONTROL PANEL IN HOUSE.
CAST IRON MANHOLE COVER ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED
W/WATERTIGHT INSERT ELECTRICAL INSPEC71ON AGENCY PRIOR TO START—UP OF PUMP
STATION.
PRECAST CONCRETE
E
:a
4" SCH. 40 PVC
INLET
4" PVC SDR-35 MIN. SLOPE
INLET 2" HDPE SDR-1 i 1/4" PER FOOT
FORCEMAIN
WATERTIGHT SLEEVE
BALL VALVE AND SEAL (TYP.)
LAG/ALARM 3" ABOVE
°
'PUMP ON'
'a
LEAD PUMP ON
a
1-1/2" SCH-40 PVC INSIDE
° WET WELL THROUGH WALL
PUMP OFF
UNION — LOCATE SUCH THAT UNION
16" MIN. ° CAN BE DISCONNECTED AND PUMP
VOLUME OF DOSE TO
REMOVED WITHOUT TANK ENTRY
BE 60 t GALLONS
REDUCING TEE POINTED DOWNWARD WITH 1"
(7-8" BETWEEN ON
° • ' ° °• a •.
BALL
1WEETWET0 ALLOW TRICKLE
AND OFF LEVELS)
°' DRAINVALVE BACK INRO LL
4' DIAMETER PRECAST
CONCRETE PUMP STATION WITH TRAFFIC COVE BALL CHECK VALVE
AND ACCESS MANWAY
INSTALL FLOAT SWITCHES TO DUPLEX GRINDER
OPERATE PUMP AND MAINTAIN PUMPS
LEVELS AS INDICATED
PUMP STATION NOTES
GRINDER PUMPS TO BE LIBERTY PROVORE 380 SERIES 1 HP
RESIDENTIAL GRINDER PUMPS IN 4' DIAMETER PRECAST CONCRETE
BASIN WITH TRAFFIC COVER.
SEAL ALL TANK OPENINGS WATERTIGHT.
PROVIDE AND INSTALL UL LISTED PACKAGED PUMP CONTROL PANEL
WITH VISUAL AND AUDIBLE ALARM. INSTALL DUPLEX, DEMAND
DOSE CONTROL PANEL IN BASEMENT UTILITY ROOM IN
COORDINATION WITH OWNER.
INSTALL POWER & CONTROL WIRING TO CONTROLLER WITH ALARM
IN HOUSE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS
AND NATIONAL ELECTRIC CODE (N.E.C.) REQUIREMENTS.
GRINDER PUMPS TO BE LIBERTY PROVOKE PRG-102M,
230V, 1 HP, 25 GPM @ 30 FT TDH.
VERIFY EXISTING ELECTRICAL SERVICE PRIOR TO PURCHASING
PUMPS.
ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED
ELECTRICAL INSPEC77ON AGENCY PRIOR TO START—UP OF PUMP
STATION.
RESOLUTION APPROVING ADAM AND TRYNTZE CONWAY'S
APPLICATION FOR SANITARY SEWAGE DISPOSAL VARIANCES
N
RESOLUTION NO.: BOH 62, 2024
INTRODUCED BY: Mr. Harrison Freer
WHO MOVED ITS ADOPTION
SECONDED BY: Mr. Michael Dixon
WHEREAS, Adam and Tryntze Conway (Applicants) filed an application for variances from
provisions of the Town of Queensbury On -Site Sewage Disposal Ordinance, Chapter 136 to install a
replacement on -site wastewater system with certain of its components to be located as follows:
1. Pump station 23' from the onsite well in lieu of the requited 50' setback;
2. Pump station 3' from the house in lieu of the required 10' setback;
3. Pump Station 3' from the south property tine in lieu of the required 10' setback;
4. Force main 21' from the onsite well in lieu of the required 50' setback; and
5. Force main 5' from the south property line in lieu of the required 10' setback;
on property located at 74 Reardon Road in the Town of Queensbury, and
WHEREAS, the Town Clerk's Office published the Notice of Public Hearing in the Town's official
newspaper and the Local Board of Health duly conducted a public hearing concerning the variance requests
on Monday, July 1', 2024, and
WHEREAS, the Town Clerk's Office has advised that it duly notified all property owners within
500 feet of the subject property,
NOW, THEREFORE, BE IT
RESOLVED, that
1. due to the nature of the variances, the Local Board of Health determines that the variances
would not be materially detrimental to the purposes and objectives of this Ordinance or other
adjoining properties nor otherwise conflict with the purpose and objectives of any Town
POLYETHYLENE EXTENSION TO POLYETHYLENE EXTENSION TO
GRADE WITH TAMPER RESISTANT APPROXIMATE TACCESS
GRADE WITH TAMPER RESISTANT
ACCESS COVER FINISH GRADE COVER
12"±
TEE BAFFLE
30 4" SDR-35 PVC
LIQUID LFVFI OUTLET
15" 18"
MIN.
118" LONG
LIQUID 51 "
DEPTH
40"
1,500 GALLON ---
POLYETHYLENE ~ `'
SEPTIC TANK ' 't
i
6"f PEA GRAVEL
PUMP STATION & SEPTIC TANK DETAIL
SCALE: NTS
5.00' PIPE
SPACII:'G
6" MIN STONE BED WIDTH & GEOMETRY PER PLAN
BELOW PIPE
3/4"-1-1/2" WASHED
CRUSHED STONE
plan or policy; and
2. the Local Board of Health finds that the granting of the variances is necessary for the
reasonable use of the land and are the minimum variances which would alleviate the specific
unnecessary hardship found by the Local Board of Health to affect the Applicants; and
BE IT FURTHER,
RESOLVED, that the Local Board of Health hereby approves the application of Adam and Tryntze
Conway for variances from the Sewage Disposal Ordinance to install a replacement on -site wastewater
system with certain of its components to be located as follows:
1. Pump station 23' from the onsite well in lieu of the required 50' setback;
2. Pump station 3' from the house in lieu of the required 10' setback;
3. Pump Station 3' from the south property line in lieu of the required 10' setback;
4. ' Force main 21' from the onsite well in lieu of the required 50' setback; and
5. Force main 5' from the south property line in lieu of the required 10' setback;
on property located at 74 Reardon Road in the Town of Queensbury and bearing Tax Map No: 289.11-1-
36.
Duly adopted this 1" day of July, 2024, by the following vote:
AYES Mr. Freer, Mr. Dixon, Mr. McNulty, Mr. Strough, Mr. Metivier
NOES None
ABSENT: None
I, Colleen Rathbun, Deputy Town Clerk of the Town of Queensbury, Warren County, New York, do hereby
certify that I have compared the foregoing with the original resolution as listed above adopted at a regular
meeting of the Town Board of the Town of Queensbury held on the t" day of July, 2024 at which a quorum
was present and that the same is a correct transcript therefrom and of the whole original thereof to date.
IN WITNESS THEREOF, I have hereto set my hand and the SEAL of said Town of Queensbury, this 2nd
day of July, 2024.
SEAL SIGNED:
Colleen Rat
Deputy Tov*n
Town of Q6
aura Cl��k
jeensbiq
ABSORPTION BED SECTION
NTS
12" MIN. COVER
DISTRIBU71ON BOX
MIN. SLOPE BAFFLE
1/8" PER FOOT 2" MIN.
USE SPEED LEVELERS TO ASSURE ALL OUTLETS 2" MIN. DROP
ARE AT EXACTLY THE SAME ELEVATION BETWEEN INVERTS
4" PVC SDR-35 SOLID HEADER TO ABSORPTION
FIELD, 1/8" PER FOOT MIN SLOPE
SEPTIC TANK NOTES
ALL UNITS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT
OF HEALTH AND SHALL BE OF PREFABRICATED POLYETHYLENE.
ALL STRUCTURES SHALL BE PLACED ON 6"f LEVEL PEA GRAVEL BASE. WHERE EXISTING
SOIL CONDITIONS ARE UNSUITABLE, CRUSHED STONE SHALL BE PLACED UNDER PEA GRAVEL
AS NECESSARY TO ACHIEVE A STABLE BASE.
RUBBER GASKETS SHALL BE INSTALLED IN ALL INLETS AND OUTLETS
INSTALL, BACKFILL, & PRE —FILL TANK IN STRICT CONFORMANCE WITH TANK
MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
PROVIDE COPY OF MANUFACTURER'S INSTALLATION INSTRUCTIONS PRIOR TO INSTALLATION.
FILTER FABRIC
2 ' TO ED MIRAFI 140N OR
OF BED EQUAL
40'
15' -- f
NIS TON BED PLAN
NTS
LIMI T OF 15'x40'
STONE BED
ERFORATED PVC LATERALS
4LLED NEAR LEVEL IN
CONFIGURATION
'OSED
?IBUTION BOX
SI TION FORCE
TO 4" PVC
IDE OF D—BOX
® Call Before You Dig
EM Wait The Required Time
® Confirm Utility Response
® Respect The Marks
® Dig With Care
800.962-7962
www.digsafelynewyork.com
-1016
ALTERATION OF THIS DOCUMENT
EXCEPT BY A LICENSED
PROFESSIONAL ENGINEER IS A
Hutchins
Engineering
PLLC
169 HaAand Road
Queensbury, NY 12804
(518) 745-0307 Phone
(518) 745-0308 Fax
TAX MAP # 289.11-1 -36
prepared for:
Tryntze and Adam
Conway
74 Reardon Road
Town of Queensbury,
County of Warren,
State of New York
Drawn: AVA Checked: GTN
Scale: 00TED Date: 0310612024.
29293-01-S2
i
f v o Wooa stogy y\-, j� _ --s Dig Safely.
11 �o� Frame � -✓ \\ New ®York
�Q�� ` \ OUse � / _� ;. Cali Before You Dig
°� `tea \ (1 5) /...._.// ,., s q
Wait The Required Time
/ ` , / ®Confirm Utility Response
o ��0� / Marks
ncre�
,; , - st - - ` � ,� WithCare Respect
\ eps \
�11z 800- 62.7
/ U�
/' � y www.digsafelynewyork.com
Glen Lake 7'± TO Shor 0r rator� ASPHALT DRIVE
/ Angle r2n C�
� RIGHT-OF-WAY WAS NOT
6 Beec 8"Hem�cck �+i\ �aO'r7/ 'N�
Lands N/F of \ SAWCUT FOR FORCEMAIN IRF N N
-- / c 6'>�� w 9h��s ��` Seidel Family Irrevocable Trust\ INSTALLATION N o o N
_` __` O° 24"White Pme 6"B,rch i a,C$ak Rs ` " `� b @ / VO 8:4905 P:.139
V. ' , \ \ \
\ - Sty`S F� COORDINATE ASPHALT ROAD CROSSING W11N "' "� p
•S81 o LAKE WATER SUPPLY x
EXIS77NG SEP77C AREA - QUEENSBURY HIGHWAY DEPARTMENT PRIOR `" ` '"''
t ,
. 'ice"Wh,fe Pme \ /� "-"� �.�_ \ 289.i I-I-37
BENEATH DECK aepc�'Mark >` 0/ TO WORK. (518)761-8212. SAWCUT EXISTING ::a. '
4 �✓11 403.54 , - 0 `�� / ASPHALT AND REPLACE PER HIGHWAY <� �
/ \ 4. /34 W.Fine '
NIII Snp 0, / c/)'s,;" '�� R 0 / � / DEPARTMENT REQUIREMENTS o /
/ ,
\,N - l-' \ / /. / \� ,' \\ `r,s s �r o��\ �... .. Ad�oininy Garage ..
,
p
yy.. To;Shore \� ,/ ,4pft._ /� 1
\ ��
/ \ / `F / N. �.. 8� <c ♦.3 CIRF T _ i-
26".Wfnte P ne °
.. < / I F� Fti '' V / 1 ��,
sc v v SITE LOCH N
ow o IPF •►
y/' .- 4 3�L�(Jhite Pne /...
.�4"Cher 4/
/ o
/ / � 4 `\ � 'I'll t ".� - ..,,� � R,� Q� - Lands N/F of �
LOCATION MAP
\ � � _ -
o
P l� 11
P.NM �11
�� /$R°°f, �\\ \" c����/ � " \ Richard & Tina DeMarsh �,� WASTEWATER SYSTEM DESIGN o
sr 4 R \ '76'�� / 8:6850 P:48
�o 0 x I / I \ � -; ; �.,� 43 3j„ 289.I I-I-38 �.,, 3-BEDROOM RESIDENCE DESIGN TO 4 o v
FUTURE SEWAGE l a / / 'L ( ) W z
Lands N/ l a Crushed Stone '
EJECTOR TO SERVE I ; se\ cF / ' / Oak \ �,, r30.p�•- / g 9 DESIGN FLOW - 110 GPD/BEDROOM ER
-;'��. \ went\ .. /. ,% / V - ``; k25
ipf Glen & Sharo Sfhp enson BASEMENT ORA/NS I I _� f \ ' / �1� SYSTEM DESIGN FLOW - 440 GPD z 0
I /
8:63 P:737 � i - f . %,, _. z la'oak =/ �',.. ,, - �,� �� PUMP STATION-4'0 PRECAST CONCRETE WITH DUPLEX Q I U
/ -- -
-35 INSTALLED 4" \\ .', i / 14`oak C1 �-
S 9.i I-i I / / ! \ GRINDER PUMPS o o nco
I ,
a BUILDING SEWER ,
\
he / / / /
2 -
r
{
PF \ SEPTIC TANK -1500 PRECAST CONCRETE DUAL o *>
�� ��, / `\ . . �'/ 18"Oak _... \ \ \ O
, _11
I �,;
I INSTALLED GRINDER ' , � �� / COMPARTMENT p
\ PUMP STA77ON N. '7j,'�� 3 /, f21 ,:(\ �Wht� ,ne j' \ \\ \ \
\ / / / \ (j 2� / \ \
.. _ _ . ..
`\ \\\ �/ ,� '- / �\ ; / \ \ \ DESIGN APPLICATION RATE: .95 GPD/SF, BASED ON v j
\ \
q �\ � � \ -
/" � ! ` 1 5 MI /N PERCOLATON RATE
d v ;
✓o mow' \ -
v \
<., \
\ ' Z
h N. /.. n . `\ - DSO. _ \\ \ a
j
i
..\K - .. , , _.:<��y11 ABSORPTION BED AREA RE 'D = 440 GPD 95 GPD SF
S - , )/( /
i \ 0 ( ) a
w St = w
>' o o \ _ .., �o , '_ .; , , , ....-.. _. ....- ...._- / 463 SF
O ;
_� r
C
aryl / \, O
ulr 1
I.
1
\ a e p Q
/ pd \ ,, 5 INS 1. c>
\ _
->r
,� ® INSTALLED 5 > _
" I °e rd . ,' - 1,1 - Area st oad �� ABSORPTION BED AREA PROVIDED = 15 x40 600 SF
-1�1)1 ,, e
... ...._. . .... ..... _..
a� ....,_ .... .....
\ . t '' Sq Feet
' FORCEMA/N
--,., / \ ,
\ >.
�, _ _ \ , , � CIR
f - 7:1 Acres. -
f ,'
POTABLE WATER SUPPLY IS TO BE ON SITE WELL
f %
9 / ,
JS� I. c -� ��
s
y o :.- r.:" he Crushed Stone." O %/ / /
\_
a \ _
r
289 36-
a \:
's 0 \ -11
O �/ N O
e e ,:, \ _`
\:. _.._
"I I / I 00 1 , // ,_.
,
y
I
,
z
w. = i
�i11,
r
i . "111-
� IRF ' ' '
t.
c,
r ��
;.. e
sF �L T
�\ \% � an N/F of / -1i' '
\ „ ,%° ,- . . i Fro SYSTEM MATERIAL SPECIFICATIONS
`� � ` � �%` � S ` Au ust &)Louise cKast Estate \ 4 F
�"' 9 y ? - ___- __-, / / - �l tiF e ABSORPTION BED AGGREGATE
,v. t �> l
CIRF s ... -- N' 55.. 04.'_13..._.• W
;x T 289.I I-!-34 - :. - ' :-� i 'PT-1` ���p`, STONE IS TO BE 3/4" TO 1-1/2" WASHED CRUSHED STONE.
421.A
a
' i
..1,.._�.�_z .. 't ... .. _._. fL
\ '
EFFLUENT SEW PIPE
4,. ;, , J -43 - _. .....-. ., __ _. PIPING TO BE 4" SDR-35 OR SCHEDULE 40 PVC. INSTALL WITH 1/8" PER FOOT MINIMUM SLOPE.
✓ ✓ 'S' >..: -__ ....._. r
a, \ C i R5 __ FILTER FABRIC
as j . _
-1 OUP_ __- - `,_ \ i� '� FILTER FABRIC TO BE 4.8 OZ/SY NON WOVEN SEPARATION FABRIC, TENCATE MIRAFI 14ON OR EQUIVALENT,
Lands N/ of - ="�
TBA
y � �
' Ronald 8. & C nth�a F. Mackowiak �� ,� _ .._ �-<� - . FORCEMA N
Y _ __
'\� O� / LYRI GRA STAL NSE TIC�ANK '� PIPING TO BE1-1/2" SDR-11 HDPE, PROVIDE POSITIVE DRAINBACK TO PUMP STATION.
L
8:578 P:236 - .. 6 TW SE D P /'
O
289.I I-I-33 . 4 1 �.` , ,
.
0 PO ��,TO IN 0
\4 .. .-.zo INSTALLED 15 X40 R PIPE
HOUSE SEINE
payers \� \ -.` - 4 SDR-35 OR SCHEDULE 40 PVC. INSTALL WITH / PER FOOT MINIMUM SLOPE.
ABSORP77ON BED - - y 10 x PIPING To BE 1 4"
/ '�d✓o, CIRF INSTALLED 1500 GALLON '� SYSTEM FILL
/ \ \ , \ n9 Cara I / / ' AS DESCRIBED IN "FILL MATERIAL NOTES �g �{ TC
/ / \ 9� a�/ . Ill ., ., -- POLYETHYLENE SSEP77C TANK �s / ' TOPSOIL , ®�
/ i \ ' ' -� PLACE 4" MINIMUM TOPSOIL OVER ENTIRE BACKFILL AREA. SEED MULCH AND ESTABLISH TURF. . GOh� �' Cr
� \ ,"�
-. _.__.. , ,
I ,
/ / (0
....1.
- �
I - � ,
i� � " -
-- 1.
CIPIf I ) - "I .1- .... "", "". - _�� _.... -.........'_""_ 1, - -,____ �� - - ! 11 11" ,_ I-, _'___ "� -1- "I" I'll ,_ -.1..... ........ -.1-1... ...-,.......... ...", INSTALLED 4 PVC1. �' '� , �,"- _-�"� .
�,� / \ , \ ; wa "" . - PIPE MARKER o � - / s
�c /
a- SYSTEM INSTALLATION NOTES
IRF
4"PVC.,MARKER PIPE INSTALLED AT D BU7ZON SOX.. ��/ ;
_._.
CONSTRUCTION SHALL BE AS SHOWN ON THIS DRA G AND IN ACCORDANCE WITH THE N.Y.S. DEPARTMENT OF
- ;
/. __
_. _ .
�.. - ..:. - - HEALTH INDIVIDUAL HOUSEHOLD SYSTEMS AND ASTM F481 INSTALLATION OF THERMOPLASTIC PIPE AND CORRUGATED
\ /
V / �� ' I I-
- 1
TUBING IN SEPTIC TANK LEA FIELDS
\ I- / ., ✓ I - 11.1
\ h 1 I" OF THIS DOCUMENT
_.._
REQUIRED, THE WALLS AND FLOOR
EXCEPT BY A LICENSED
/ �.% \ _ _. __. AFTER EXCAVATION OF 15 WIDE X 40 LONG ABSORPTION BED TO THE DEPTH ED,
\ _ � ' - _ ..... _ .._. I..... - _ -.._ '11- . J PROFESSIONAL ENGINEER /S A
\ / �' ....- .. _ > -.-- _.. 11 _.-.. .. `A h.. . __.-. SHALL BE CLEANED AND RAKED IN ORDER TO LOOSEN SMEARED AREAS OF SOIL. VIOLATION OF NYS EDUCATION LAW.
\ \ c� _ - _
/ �� oti_
\ / / 11" STONE,PLACEMENT OF CRUSHED SHALL E
\`
le - -
ti
, _
_._.
_.
-
_...
\ %j
--- - EXERCISED TO AVOID INCLUSION OF FINE GRAINED SOILS AND WASTE MATERIAL IN THE STONE AND PIPE.
Oa .
/ \ 7777
- _
----- , _ _.. .... .._.. _
RC
i
,, .. O._.
_ _....... . - -
° 6 _._ _ _ _- _ -_ THE PIPE SHOULD BE LAID AT THE GRADES INDICATED, MAINTAINING STRAIGHT CONTINUOUS GRADES WITHOUT SAGS
�+/.�
\ / �RF .'' � / ,r _... .. _ .. .- _.. _ ..... Hutchins
�' y _.... ...... ��� __. HUMPS, SEPARATED JOINTS, OR OTHER UNSUITABLE CONDI7IONS PIPE SHALL BE LAID IMTH HOLES DOWN IN ALL
_ .... ._
,; __ . _ . 11 Engineering
�; . c
_ _.._
. ... _
/ _ .
�� I ,0 FIELDS SHALL BE GRADED TO SHED RAINFALL AND DIVERT SURFACE RUNOFF AWAY FROM THE
i1. -
'�e� P L L
oO� 46 ` A- .._-. __ .. -.- -- -... - _ - _.-._ DISPOSAL POFIELD.F 169 Hoviland Road
' _ - .. _.... ..
' ' '✓` ' ; .... _..._ -._ _..... .. _... een 04
x to,� 7. -._ _..._ - __. Qu sbury, N
/ - 1p . ._.. - _ -
_:_.. _.__ ... _ _..- DO NOT USE HEAVY EQUIPMENT WITHIN 7HE ABSORPTION AREA AFTER PIPING HAS BEEN INSTALLED. ((51 745 0030 Phone
/I ^ s �♦ - _... _.�/. (518) 745-0308 Fax
THE WASTEWATER TREATMENT SYSTEM IS DESIGNED AND APPROVED BASED UPON THE INSTALLATION OF WATER TAX MAP # 289,l I-1-36
WASTEWATER SYSTEM PLAN CONSERVING FIXTURES AND A DESIGN FLOW OF 110 GPD PER BEDROOM. THE SYSTEM IS NOT DESIGNED TO
ACCOMMODATE EXTREME WATER USE FIXTURES, SUCH AS JACUZZI-TYPE SPA TUBS OR WATER TREATMENT
SCALE: 1"=20' EQUIPMENT. THE INSTALLATION OF NON-CONSERVING WATER FIXTURES OR EXTREME WA7ER USE FIXTURES Is WASTEWATER
GRAPHII. SC4LE CONTRARY TO THE APPROVAL OF THIS WASTEWATER TREATMENT SYSTEM.
10 10 20 40 SITE SOILS DATA VARIANCE RE UEST SUMMARY ROOF, FOOTING GARAGE, CELLAR AND SURFACE WATER DRAINAGE MUST BE EXCLUDED FROM THE WASTEWATER SYSTEM PLAN
TEST PIT SYSTEM. O� DETAILS
( IN FEET ) TP-1 - 611812024 BY TOM HUTCHINS, P.E. THE FOLLOWING RELIEF IS REQUESTED FROM THE TOWN OF QUEENSBURY
RECORD DRAWING CONTRACTOR TO FIELD VERIFY LOCATIONS AND DISTANCES WOODS AREA UP HILL - EL. 439' SANITARY ORDINANCE: CONSTRUCT DRAINAGE SWALE UPGRADE OF SYSTEM IN ORDER TO DIVERT SURFACE RUNOFF AROUND ABSORPTION
WOODS DUFF � ' FIELD. prepared for:
INSTALLATION DATE: 101712024 0-6" - WOODS TOPSOIL 1) INSTALL PUMP STATION 23 FROM WELL IN LIEU OF REQUIRED 50. T ntze and Adam
6-32" - RED-BROWN SILTY FINE SAND SEPTIC TANK, PUMP STATION & ABSORPTION BED MUST BE INSPECTED BY LOCAL BUILDING DEPARTMENT AND
INSTALLED BY - STONE INSTALLATIONS 6-32" - LIGHT BROWN FINE SAND 2) INSTALL PUMP STATION 3' FROM BUILDING FOUNDATION IN LIEU OF REQUIRED 10'. DESIGN ENGINEER PRIOR TO BACKFILL AND FINAL GRADING. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO Conway
60-60" - GRAYISH BROWN FINE SAND IDEN77FY THE NECESSARY PARTIES AND REQUEST INSPECTIONS. 74 Reardon Road
3) INSTALL PUMP STATION 3' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'.
Town of Queensbury,
RECORD DRAWING NOTE: DRY ALL DEPTH 4) INSTALL FORCE MAIN 21' FROM WELL IN LIEU OF REQUIRED 50: County of Warren,
A REPRESENTATIVE OF OUR OFFICE WS17ED THE SITE NO GROUNDWATER EVIDENCE MAP REFERENCE: State of New York
DURING CONS7RUCRON AND IT IS MY OPINION THAT ROOTS TO 80" 5) INSTALL FORCE MAIN 5' FROM SOUTH PROPERTY LINE IN LIEU OF REQUIRED 10'. 1. BASE MAP INFORMATION FROM 'MAP OF A
7HE SYS7EM IS INSTALLED IN GENERAL CONFORMANCE NO BOUNDARY COND177ON TO 84" TOPOGRAPHIC SURVEY MADE FOR 7RYNTZE &
WTH 7HE APPROVED PLAN AND 7HIS RECORD PROVIDE 24" VERTICAL SEPARATION TO ADAM CONWAY" BY VAN DUSEN & SIEVES
DRA{MNG. FINAL SURFACE FINISHING AND TURF LAND SURVEYORS, JANUARY 17, 2024.
ESTABLISHMENT IS ONGOING BOUNDARY CON0177ON
G. 7HOMAS HUTCHINS, P.E. PERCOLATION TEST WASTEWATER SYSTEM SETBACK REQUIREMENTS Drawn: AVA Checked: GTH
1011512024
PT-1 - BY TOM HUTCHINS, P.E. S7REAM, LAKE, Scale: NOTED Date: 0310612024
, STABILIZED PERCOLATION RATE' = 3:30 MIN/INCH PROPERTY LINE HOUSE WATERCOURSE, WELL
WETLAND
SEP71C TANK 10' 10' 50' 50' 292293-01 -S1
ABSORP7ON FIELD 10' 20' 100' 100'
Dig Safely.
New ®York
®Call Before You Dig
®Wait The Required Time
Confirm Utility Response
Respect The Marks
EM Dig With Care
TWO POLY RISERS TO GRADE INSTALLED ON SEPTIC TANK 800-962-7962
www.digsafelynewyork.com
01
CN
�t d-
:n N
EXTERIOR WEATHERPROOF JUNCTION BOX (IF NECESSARY). POLYETHYLENE EXTENSION TO POLYETHYLENE EXTENSION TO o
SEAL CONDUIT GAS TIGHT. INSTALL CONTROL PANEL IN HOUSE. GRADE WITH TAMPER RESISTANT APPROXIMATE GRADE WITH TAMPER RESISTANT
CAST IRON MANHOLE COVER ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED ACCESS COVER FINISH GRADE ACCESS COVER
W/WA TER TIGHT INSERT ELECTRICAL INSPECTION AGENCY PRIOR TO START—UP OF PUMP
STATION.
PRECAST CONCRETE
RISER
12"f
TEE BAFFLE
12" N. COVER
4" SCH. 40 PVC DISTRIBUTION BOX
3»
INLET
4" SDR-35 PVC U
a a.
4" PVC SDR-35 MIN. SLOPE LIQUID LEVEL OUTLET
01
z
INLET 2" HDPE SDR-11 1/4 PER FOOT ��� » MIN. SLOPE BAFFLE Z
FORCEMAIN 15 18 1/8 PER FOOT 2 MIN.
WATERTIGHT SLEEVE MIN. USE SPEED LEVELERS TO ASSURE ALL OUTL TS 2" MIN. DROP o a
BALL VALVE AND SEAL (TYP.) 118" LONG ARE AT EXACTLY THE SAME ELEVA ON BETWEEN INVERTS �p cWn j
LIQUID 51„ 4" PVC SDR-35 SOLID HEADER TO ABSORP ON N
LAG/ALARM 3" ABOVE DEPTH FIELD, 1/8" PER FOOT MIN SLOPE
'PUMP ON' 1,500 GALLON-1SEPTIC TANK NOTES
POLYETHYLENE ALL UNITS SHALL COMPLY WITH THE REQUIREMENTS F THE NEW YORK STATE DEPARTMENT
LEAD PUMP ON SEP77C TANK
1-1/2" SCH-40 PVC INSIDE OF HEALTH AND SHALL BE OF PREFABRICATED POLYETHYLENE.
WET WELL THROUGH WALL »
'.������������ ���� ��������� ������������ ���������� ���� ���� � � ��% ALL STRUCTURES SHALL BE PLACED ON 6 f LEVEL EA GRAVEL BASE. WHERE EXISTING
PUMP OFF % % %/�/�/�%/%%/%/%%%%%%%%%%/�/ % % % % % i % % ��% % i�/��/��/��/i�/i�/�� SOIL CONDITIONS ARE UNSUITABLE, CRUSHED STONE HALL BE PLACED UNDER PEA GRAVEL
UNION - LOCATE SUCH THAT UNION AS NECESSARY TO ACHIEVE A STABLE BASE.
16" MIN. CAN BE DISCONNECTED AND PUMP 6"f PEA GRAVEL
VOLUME OF DOSE TO REMOVED WITHOUT TANK ENTRY RUBBER GASKETS SHALL BE INSTALLED IN ALL INLET AND OUTLETS.
BE 60 E GALLONS REDUCING TEE POINTED DOWNWARD WITH 1"
(7-8" BETWEEN ON � BALL VALVE THROTTLED TO ALLOW TRICKLE INSTALL, BACKFILL, & PRE—FILL TANK IN STRICT CON ORMANCE WITH TANK
AND OFF LEVELS) DRAIN BACK INTO WETWELL MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
4' DIAMETER PRECAST
CONCRETE PUMP STA71ON WITH TRAFFIC COVE BALL CHECK VALVE N
AND ACCESS MANWAY PUMP STATION NOTE: PROVIDE COPY OF MANUFACTURER'S INSTALLATION IN TRUCTIONS PRIOR TO INSTALLATION. z
INSTALL FLOAT SWITCHES TO DUPLEX GRINDER
OPERATE PUMP AND MAINTAIN PUMPS THE PUMPS THAT WERE INSTALLED IN THE 4''0 PUMP
LEVELS AS INDICATED STATION WERE CHAMPION PUMPS:MODEL CPG1022-2 PUMP STATION & SEPTIC TANK DETAIL
SCALE: NTS
PUMP STATION NOTES
GRINDER PUMPS TO BE LIBERTY PROVORE 380 SERIES 1 HP
RESIDENTIAL GRINDER PUMPS IN 4' DIAMETER PRECAST CONCRETE
BASIN WITH TRAFFIC COVER.
SEAL ALL TANK OPENINGS WATERTIGHT.
PROVIDE AND INSTALL UL LISTED PACKAGED PUMP CONTROL PANEL 4" PVC PERFORATED
4" TOPSOIL COVER ABOVE FILTER FABRIC
WITH VISUAL AND AUDIBLE ALARM. INSTALL DUPLEX, DEMAND TOP OF STONE BED; LATERAL INSTALLED LEVEL, MIRAFI 140N OR
DOSE CONTROL PANEL IN BASEMENT U77LITY ROOM IN 1N BED CONFIGURATION WITH 5.00' PIPE 2 ' TO ED QF SEED & ESTABLISH TURF EQUAL E'
COORDINATION WITH OWNER. MANIFOLDED ENDS SPACING OF BED �F �c�
INSTALL POWER & CONTROL WIRING TO CONTROLLER WITH ALARM C ER
\ 12 TOTAL ua
IN HOUSE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS 2" STONE � '
•
AND NATIONAL ELECTRIC CODE (N.EC.) REQUIREMENTS. LIJ
COVER OVER PIPE r L' sue' �$ f ,;�' �r�� f �� STONE w,e
-j
6" MIN STONE BED, WIDTH & GEQMETRY PER PLAN 2' MINIMUM
n '
GRINDER PUMPS TO BE LIBERTY PROVORE PRG-102M, = BELOW PIPE A71ON
�:
.;-
SEPAR
230V, 1 HP, 25 GPM @ 30 FT TDH.
TO BOUNDARY.' o67g't�'
- _ CONDITIONOF
PUMPS.
5
VERIFY EXISTING ELECTRICAL SERVICE PRIOR TO PURCHASING 3/4"-1-112" WASHED
PUMPS. CRUSHED STONE ABSORPTION BED SECTION
NTS — 15, ALTERATION OF THIS DOCUMENT
ALL ELECTRICAL WORK TO BE INSPECTED BY A CERTIFIED EXCEPT BY A LICENSED
ELECTRICAL INSPECTION AGENCY PRIOR TO START-UP OF PUMP T ` R `T` PROFESSIONAL ENGINEER /S A
° VIOLATION OF NYS EDUCATION LAW.
v t
STATION. 3
,;✓t c fi c K c M = c F c �C
v vv v , � Hutchins
RESOLUTION APPROVING ADAM AND TRYNTZE CONWAY'S plan or policy;and s u 1 <
APPLICATION FOR SANITARY SEWAGE DISPOSAL VARIANCES 2. the Local Board of Health finds that the granting of the variances is necessary for the \ \ \ \ \ \ \
M Engineering
reasonable use of the land and are the minimum variances which would alleviate the specific \ \ \ \ \ \
RESOLUTION NO.:BOH 62,2024 unnecessary hardship found by the Local Board of Health to affect the Applicants;and ����
p .,-x,
INTRODUCED BY: Mr.Harrison Freer
v v vv v N v v� v' v
WHO MOVED ITS ADOPTION BE IT FURTHF,R, LIMt T OF 15'x40' 169 Haviland Road
STONE BED Queensbury, NY 12804
SECONDED BY: Mr.Michael Dixon e °M e \ \ G f (518) 745-0307 Phone
RESOLVED,that the Local Board of Health hereby approves the application of Adam and Tryntze
v y% (518) 745-0308 Fax
Conway for variances from the Sewage Disposal Ordinance to install a replacement on-site wastewater ( r f
WHEREAS, Adam and Tryntze Conway (Applicants) filed an application for variances from system with certain of its components to be located as follows:
provisions of the Town of Queensbury On-Site Sewage Disposal Ordinance, Chapter 136 to install a TAX MAP # 289.11-1-36
replacement on-site wastewater system with certain of its components to be located as follows: 1. Pump station 23'from the onsite well in lieu of the required 50'setback;
2. Pump station 3'from the house in lieu of the required 10'setback;
1. Pumpstation 23'from the onsite well in lieu of the required 50'setback; Y WASTEWATER
q 3. Pump Station 3'from the south property line in lieu of the required t0'setback;
2. Pump station 3'from the house in lieu of the required 10'setback; 4. Force main 21'from the onsite well in lieu of the required 50'setback;and ° `
v v v SYSTEM PLAN
3. Pump Station 3'from the south property line in lieu of the required IO'setback; 5. Force main 5'from the south properly tine in lieu of the required 10'setback; , ,, `, c
40 y
4. Force main 21'from the onsite well in lieu of the required 50'setback;and
5. Force main 5'from the south property line in lieu of the required 10'setback; on property located at 74 Reardon Road in the Town of Queensbury and bearing Tax Map No: 289.11-1- (�C DETAILS
36.
c �cei
on property located at 74 Reardon Road in the Town of Queensbury,and '< < \ t ` \ »
4 PERFORATED PVC LATERALS
( prepared for:
INSTALLED NEAR LEVEL IN
Duly adopted this I"day of July,2024,by the following vote: Tryntze and Adam
WHEREAS,the Town Clerk's Office published the Notice of Public Hearing in the Town's official BED CONFIGURA77ON
< < \ N y \ \
newspaper and the Local Board of Health duly conducted a public hearing concerning the variance requests AYES Mr.Freer,Mr.Dixon,Mr.McNulty,Mr.Strough,Mr.Metivier
NOES None ( N t ' Conway
on Monday,July 11,2024,and ABSENT: None C` `
74 Reardon Road
I,Colleen Rathbun,Deputy Town Clerk of the Town of Queensbury,Warren County,New York,do hereby N^ PROPOSED Town f WHEREAS,the Town Clerk's Office has advised that it duly notified all property owners within certify that I have compared the foregoing with the original resolution as listed above adopted at a regular = , DISTRIBUT70N BOX 0 o Queensbury,
500 feet of the subject property, meeting of the Town Board of the Town of Queensbury held on the Is`day of July,2024 at which a quorum
County of Warren,
was present and that the same is e correct transcript yha therefrom and L the whole original thereof to date. � N TRANSITION FORCE State Of New York
IN WITNESS THEREOF,I have hereto set my hand and the SEAL of said Town of Queensbury,this 2"a K"
NOW,THEREFORE,BE IT day of July,2024. Ns \ N „
\^ MAIN TO 4 PVC
OUTSIDE OF D-BOX
RESOLVED.that SEAL SIGNED:
Colleen Rathbun
Deputy Town Clerk ABSORPTION BED PLAN
1. due to the native of the variances,the Local Board of Health determines that the variances Town of Queensbury
would not be materially detrimental to the purposes and objectives of this Ordinance or other NTS Drawn: AVA Checked: GTH
adjoining properties nor otherwise conflict with the purpose and objectives of any Town
Scale: NOTED Date: 0310612024
QUEENSBURY VARIANCE RESOLUTION
NTS 292293-01 -S2