Queensbury water/wastewater dept. comments TOWN OF QUEENSBURY WATER/WASTEWATER DEPARTMENT
823 CORINTH ROAD * QUEENSBURY,NEW YORK 12804 *PHONE(518)793-8866 *FAX(518)798-3320
Christopher Harrington Alex Benway
Water Superintendent Water Treatment Plant Operations Engineer
Acting Wastewater Director
June 12, 2017
Mr. Craig Brown, Administrator
Town of Queensbury Planning Board
742 Bay Road
Queensbury, New York 12804
Re: June 2017 Planning Board Applications
Dear Craig:
My comments regarding the agenda for the June 2017 Planning Board applications.
Site Plan 442017- O'Reilly Auto Parts:
• A large service tap application needs to be applied for at the Water Department. Updated
plans will be required to show cut and cap. Application and associated installation
requirements are on the Water Department's webpage.
• The water line to the existing building must be cut and capped.
• NYSDOH Backflow requirements shall be followed, i.e. ,parts cleaning apparatus
• Wastewater permit needs to be applied for at the Wastewater Department. Updated Plans
required.
• Sewer line needs to be 6". Backwater Valve needs to be installed. Manhole covers need
to be pickless. An air vent needs to be installed. Details are found on Wastewater's
webpage.
Discussion 7-2017 - `Bo2uslaw and Anna Bielecki"
• A large service tap application needs to be applied for at the Water Department.
Application and associated installation requirements are on the Water Department's
webpage.
• Fire Sprinkler systems shall comply with Queensbury Design and Construction
Standards. If only water supply from Queensbury is being utilized, a check valve
isolating the fire system needs to be installed.
Site Plan 45-2017—"Aviation Hospitality, LLC"
• A large tap application needs to be applied for at the Water Department. Application and
associated installation requirements are on the Water Departments's webpage.
• NYSDOH Backflow requirements shall be followed.
• Fire Sprinkler systems shall comply with Queensbury Design and Construction
Standards. If only water supply from Queensbury is being utilized, a check valve
isolating the fire system needs to be installed.
• Wastewater permit needs to be applied for at the Wastewater Department. Updated Plans
required.
• Backwater Valve needs to be installed. Manhole covers need to be pickless. An air vent
needs to be installed. Details are found on Wastewater's webpage.