Queensbury water/wastewater dept. comments TOWN OF QUEENSBURY WATER/WASTEWATER DEPARTMENT 823 CORINTH ROAD * QUEENSBURY,NEW YORK 12804 *PHONE(518)793-8866 *FAX(518)798-3320 Christopher Harrington Alex Benway Water Superintendent Water Treatment Plant Operations Engineer Acting Wastewater Director June 12, 2017 Mr. Craig Brown, Administrator Town of Queensbury Planning Board 742 Bay Road Queensbury, New York 12804 Re: June 2017 Planning Board Applications Dear Craig: My comments regarding the agenda for the June 2017 Planning Board applications. Site Plan 442017- O'Reilly Auto Parts: • A large service tap application needs to be applied for at the Water Department. Updated plans will be required to show cut and cap. Application and associated installation requirements are on the Water Department's webpage. • The water line to the existing building must be cut and capped. • NYSDOH Backflow requirements shall be followed, i.e. ,parts cleaning apparatus • Wastewater permit needs to be applied for at the Wastewater Department. Updated Plans required. • Sewer line needs to be 6". Backwater Valve needs to be installed. Manhole covers need to be pickless. An air vent needs to be installed. Details are found on Wastewater's webpage. Discussion 7-2017 - `Bo2uslaw and Anna Bielecki" • A large service tap application needs to be applied for at the Water Department. Application and associated installation requirements are on the Water Department's webpage. • Fire Sprinkler systems shall comply with Queensbury Design and Construction Standards. If only water supply from Queensbury is being utilized, a check valve isolating the fire system needs to be installed. Site Plan 45-2017—"Aviation Hospitality, LLC" • A large tap application needs to be applied for at the Water Department. Application and associated installation requirements are on the Water Departments's webpage. • NYSDOH Backflow requirements shall be followed. • Fire Sprinkler systems shall comply with Queensbury Design and Construction Standards. If only water supply from Queensbury is being utilized, a check valve isolating the fire system needs to be installed. • Wastewater permit needs to be applied for at the Wastewater Department. Updated Plans required. • Backwater Valve needs to be installed. Manhole covers need to be pickless. An air vent needs to be installed. Details are found on Wastewater's webpage. Christopher T. Harrington Superintendent CTH Cc: Scott Burnard, QWD Engineering Department File