inspectionsINSPECTION WORKSHEET (FIST-001459-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0395-2018 Case Module:Permit
Inspection Date:Mon Mar 18, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Firestopping
Job Address:Parcel Number:147 Chestnut Ridge RD
Queensbury, NY 12804
290.-1-22.8
Contact Type Company Name Name
Granted Permission Rhein, George
Engineer Scharff, Michael
Contractor Rhein, George
Applicant Rhein, George
Primary Owner Rhein, George
Checklist Item Passed Comments
Building Inspector Notes NO 1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
3/11/19 fire stopping for vertical penetrations approved for
first floor and bonus room only. Basement not completed.
3/18/19 fire stopping in basement approved for vertical
penetrations
Fire separation 1, 2, 3 hour NO
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Mar 18, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001459-2019)
Checklist Item Passed Comments
Firestopping NO 1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
Penetration sealed YES 3/11/19 fire stopping for vertical penetrations approved for
first floor and bonus room only. Basement not
completed3/18/19 fire stopping in basement approved for
vertical penetrations
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Mar 18, 2019 Page (2)
Smith, Mark (Inspector)
INSPECTION WORKSHEET (BINS-001460-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0395-2018 Case Module:Permit
Inspection Date:Mon Mar 18, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Building Insulation
Job Address:Parcel Number:147 Chestnut Ridge RD
Queensbury, NY 12804
290.-1-22.8
Contact Type Company Name Name
Applicant Rhein, George
Contractor Rhein, George
Primary Owner Rhein, George
Granted Permission Rhein, George
Engineer Scharff, Michael
Checklist Item Passed Comments
Building Inspector Notes NO 1/7/19 Insulation Partial Approval
- R19 Exterior wall of fireplace chase.
3/18/19 insulation on first floor walls and bonus room ceiling
approved. Ceilings on main level not insulated at this time.
Knee walls in bonus room not insulated. Closed cell spray
foam in walls and bonus room ceiling Basement insulation
approved. R 21 in cavities with foam insulation over
foundation.
Provide documents from installer stating R value and
thickness of insulation.
U Factors = .3 cfm for windows, .5 cfm for doors NO
Tyvek or Similar Exterior Sealant YES Zip system used
Mar 18, 2019 Page (1)
INSPECTION WORKSHEET (BINS-001460-2019)
Checklist Item Passed Comments
Proper Vent, Attic Vent NO
Insulation Residential Check Commercial Check NO 1/7/19 Insulation Partial Approval
- R19 Exterior wall of fireplace chase.
Blower Door Test NO
Combustion Air Supply for Furnace NO
Fresh air supply 3' from grade NO
Duct Insulation - if required in unheated spaces NO
Tub Shower R-20 with Vapor Barrier NO
Air Barrier behind Knee Walls NO
All Ductwork Sealed Return and Supply NO
Duct Blaster Test for duct work, R-8 NO
All Return Air Hard Duct Work NO
House Wrap Taped at all Seams NO
Mar 18, 2019 Page (2)
Smith, Mark (Inspector)
INSPECTION WORKSHEET (RPLUM-001341-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0395-2018 Case Module:Permit
Inspection Date:Fri Mar 8, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Rough Plumbing
Job Address:Parcel Number:147 Chestnut Ridge RD
Queensbury, NY 12804
290.-1-22.8
Contact Type Company Name Name
Granted Permission Rhein, George
Contractor Rhein, George
Primary Owner Rhein, George
Engineer Scharff, Michael
Applicant Rhein, George
Checklist Item Passed Comments
Building Inspector Notes NO 3/8/19 rough plumbing approved inspection for supply and
sanitary drain lines only.
Items remaining
Air pressure test for gas lines
Air pressure test for radiant heat in floor.
Plumbing Under Slab NO
Rough Plumbing / Nail Plates YES
Plumbing Vent Vents in Place YES
3" Vent Through Roof YES Verified glue joint above ball stop at roof penetration
Mar 08, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001341-2019)
Checklist Item Passed Comments
1 ½ inch minimum Drain Size YES
Shower liner test (2" of water)NO
Washing Machine Drain 2 inch minimum YES
Washing Machine Trap: 18"-24" discharge YES
Cleanout every 100 feet change of direction YES
Pressure Test NO
Drain Vent NO
Air Head YES
5 psi or 10 ft. above highest conn. for 15 minutes YES Holding 5 psi for fifteen minutes
Pressure Test YES Holding 5 psi for fifteen minutes
Water Supply Piping YES
Air Head YES
50 P.S.I for 15 minutes YES Holding 60 psi for 15 minutes
Air Test Gas Piping 10 psi for 10 Minutes NO Gas piping not ready
All Return Air Hard Duct Work NO
Duct Insulation - if required in unheated spaces NO
Mar 08, 2019 Page (2)
INSPECTION WORKSHEET (RPLUM-001341-2019)
Checklist Item Passed Comments
Duct Testing Outside Conditioned Space NO
Duct work sealed properly NO
Mar 08, 2019 Page (3)
Smith, Mark (Inspector)
INSPECTION WORKSHEET (RPLUM-001359-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0395-2018 Case Module:Permit
Inspection Date:Mon Mar 11, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Rough Plumbing
Job Address:Parcel Number:147 Chestnut Ridge RD
Queensbury, NY 12804
290.-1-22.8
Contact Type Company Name Name
Contractor Rhein, George
Granted Permission Rhein, George
Engineer Scharff, Michael
Primary Owner Rhein, George
Applicant Rhein, George
Checklist Item Passed Comments
Building Inspector Notes NO 3/8/19 rough plumbing approved inspection for supply and
sanitary drain lines only.
Items remaining
Air pressure test for gas lines
Air pressure test for radiant heat in floor.
3/11/19 air test for gas piping approved. Holding 10 PSI for
ten minutes
Call when radiant heat is ready for inspection.
Plumbing Under Slab NO
3" Vent Through Roof YES Verified glue joint above ball stop at roof penetration
Shower liner test (2" of water)NO
Mar 11, 2019 Page (1)
INSPECTION WORKSHEET (RPLUM-001359-2019)
Checklist Item Passed Comments
Drain Vent NO
5 psi or 10 ft. above highest conn. for 15 minutes YES Holding 5 psi for fifteen minutes
Pressure Test YES Holding 5 psi for fifteen minutes
50 P.S.I for 15 minutes YES Holding 60 psi for 15 minutes
Air Test Gas Piping 10 psi for 10 Minutes YES Gas piping not ready
3/11/19 air test for gas piping approved. Holding 10 PSI for
ten minutes
Duct Insulation - if required in unheated spaces NO
Duct Testing Outside Conditioned Space NO
Mar 11, 2019 Page (2)
Smith, Mark (Inspector)
INSPECTION WORKSHEET (FIST-001379-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:RC-0395-2018 Case Module:Permit
Inspection Date:Mon Mar 11, 2019 Inspection Status:Partial Pass
Inspector:Mark Smith Inspection Type:Firestopping
Job Address:Parcel Number:147 Chestnut Ridge RD
Queensbury, NY 12804
290.-1-22.8
Contact Type Company Name Name
Contractor Rhein, George
Granted Permission Rhein, George
Engineer Scharff, Michael
Primary Owner Rhein, George
Applicant Rhein, George
Checklist Item Passed Comments
Building Inspector Notes NO 1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
3/11/19 fire stopping for vertical penetrations approved for
first floor and bonus room only. Basement not completed.
Fire separation 1, 2, 3 hour NO
Fire wall 2, 3, 4 hour NO
Fireproofing NO
Mar 11, 2019 Page (1)
INSPECTION WORKSHEET (FIST-001379-2019)
Checklist Item Passed Comments
Firestopping NO 1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
Penetration sealed YES 3/11/19 fire stopping for vertical penetrations approved for
first floor and bonus room only. Basement not completed
16 inch insulation in cavity min.NO
Garage Fire Separation NO
House side ½ inch or 58 inch Type X NO
Garage side 5/8 inch Type X NO
Ceilingwall NO
Mar 11, 2019 Page (2)
Smith, Mark (Inspector)
INSPECTION WORKSHEET (FIST-000101-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
RC-0395-2018Permit
Case Number:Case Module:
Mon Jan 7, 2019Partial Pass
Inspection Date:Inspection Status:
John O'BrienFirestopping
Inspector:Inspection Type:
147 Chestnut Ridge RD290.-1-22.8
Job Address:Parcel Number:
Queensbury, NY 12804
Contact TypeCompany NameName
Granted PermissionRhein, George
Primary OwnerRhein, George
EngineerScharff, Michael
ContractorRhein, George
ApplicantRhein, George
Checklist ItemPassedComments
Building Inspector NotesNO1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
Fire separation 1, 2, 3 hourNO
Fire wall 2, 3, 4 hourNO
FireproofingNO
FirestoppingNO1/7/19 Firestopping Partial Approval
- Firestopped two truss area dead spaces to create areas
smaller than 32 sf at bonus room. No access required in
these two areas.
Jan 07, 2019Page (1)
INSPECTION WORKSHEET (FIST-000101-2019)
Checklist ItemPassedComments
Penetration sealedNO
16 inch insulation in cavity min.NO
Garage Fire SeparationNO
House side ½ inch or 58 inch Type XNO
Garage side 5/8 inch Type XNO
CeilingwallNO
O'Brien, John (Inspector)
Jan 07, 2019Page (2)
INSPECTION WORKSHEET (BINS-000102-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
RC-0395-2018Permit
Case Number:Case Module:
Mon Jan 7, 2019Partial Pass
Inspection Date:Inspection Status:
John O'BrienBuilding Insulation
Inspector:Inspection Type:
147 Chestnut Ridge RD290.-1-22.8
Job Address:Parcel Number:
Queensbury, NY 12804
Contact TypeCompany NameName
ContractorRhein, George
Granted PermissionRhein, George
EngineerScharff, Michael
ApplicantRhein, George
Primary OwnerRhein, George
Checklist ItemPassedComments
Building Inspector NotesNO1/7/19 Insulation Partial Approval
- R19 Exterior wall of fireplace chase.
Window SealingNO
U Factors = .3 cfm for windows, .5 cfm for doorsNO
Tyvek or Similar Exterior SealantNO
Proper Vent, Attic VentNO
Insulation Residential Check Commercial CheckNO1/7/19 Insulation Partial Approval
- R19 Exterior wall of fireplace chase.
Jan 07, 2019Page (1)
INSPECTION WORKSHEET (BINS-000102-2019)
Checklist ItemPassedComments
Blower Door TestNO
Combustion Air Supply for FurnaceNO
Fresh air supply 3' from gradeNO
Duct Insulation - if required in unheated spacesNO
Door / Window Sealed (No Insulation)NO
Air Barrier behind Knee WallsNO
Tub Shower R-20 with Vapor BarrierNO
All Ductwork Sealed Return and SupplyNO
Duct Blaster Test for duct work, R-8NO
All Return Air Hard Duct WorkNO
House Wrap Taped at all SeamsNO
O'Brien, John (Inspector)
Jan 07, 2019Page (2)