inspectionsINSPECTION WORKSHEET (FIST-000619-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Mon Jan 28, 2019 Inspection Status:Failed Inspector:John O'Brien Inspection Type:Firestopping Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Architect Monarch Design Group LLC Contractor J. Luke Construction Applicant J. Luke Construction Primary Owner Okie Properties, LLC Granted Permission Okie Properties, LLC Checklist Item Passed Comments Building Inspector Notes NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. Jan 28, 2019 Page (1) INSPECTION WORKSHEET (FIST-000619-2019) Checklist Item Passed Comments Fire separation 1, 2, 3 hour NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. Penetration sealed NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. Jan 28, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (FIST-000712-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Fri Feb 1, 2019 Inspection Status:Partial Pass Inspector:John O'Brien Inspection Type:Firestopping Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Applicant J. Luke Construction Primary Owner Okie Properties, LLC Granted Permission Okie Properties, LLC Architect Monarch Design Group LLC Contractor J. Luke Construction Checklist Item Passed Comments Building Inspector Notes NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. 1/31/19 Firestopping Partial Approval - Fire Caulking at Suite 1 side of Demise Wall except over bathroom area. Feb 01, 2019 Page (1) INSPECTION WORKSHEET (FIST-000712-2019) Checklist Item Passed Comments Fire separation 1, 2, 3 hour NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. 1/31/19 Firestopping Partial Approval - Fire Caulking at Suite 1 side of Demise Wall except over bathroom area. Penetration sealed NO 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. Feb 01, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (BINS-001190-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Thu Feb 28, 2019 Inspection Status:Failed Inspector:John O'Brien Inspection Type:Commercial Final Inspection Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Primary Owner Okie Properties, LLC Applicant J. Luke Construction Granted Permission Okie Properties, LLC Architect Monarch Design Group LLC Tenant Motimac USA Contractor J. Luke Construction Checklist Item Passed Comments Firewalls, 2 Hr, 3 Hr / Fire Dampers / Fire Doors NO H/C Bathroom Grab Bars /Sinks/Toilets/Mirrors NO Low flow toilet 1.3 gal/flushing cycle - showerhead/faucet NO Handicapped Service Counters 34 inch NO -Install break room counter with sink as per plan no stove. Bldg Num or Tenant Address on Bld or Drive NO Install Suite Number Engineer or Architect Approval NO Feb 28, 2019 Page (1) INSPECTION WORKSHEET (BINS-001190-2019) Checklist Item Passed Comments Special Inspections NO Submit HVAC Air Balancing Report for Suite #1 & #2 OK to Issue Temporary C/O NO OK to Issue C/O NO 2/28/19 Final Inspection Not Approved Remaining Items: -Submit HVAC Air Balancing Report for Suite #1 & #2 -Install Suite Number -Install right handed flush handle handicapped toilet. -Install break room counter with sink as per plan no stove. -Complete Fire Marshal's Items. Feb 28, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (FM-001189-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Thu Feb 28, 2019 Inspection Status:Partial Pass Inspector:Mike Palmer Inspection Type:OCC-Inspections Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Architect Monarch Design Group LLC Applicant J. Luke Construction Granted Permission Okie Properties, LLC Contractor J. Luke Construction Tenant Motimac USA Primary Owner Okie Properties, LLC Checklist Item Passed Comments Fire Marshal YES Inspection of Suite 2 Exit Access YES Exit Enclosure YES Exit Discharge YES Locks and Latches YES Sign: Normal YES Feb 28, 2019 Page (1) INSPECTION WORKSHEET (FM-001189-2019) Checklist Item Passed Comments Sign: Backup NO Need to verify Main Aisle Width YES Secondary Aisle Width YES Fire Extinguisher Hung NO Need to verify Inspection of Extinguisher YES Emergency Lighting Interior NO Need to verify Clearance to Electrical YES Electrical Wiring Enclosed/Labeled NO Need permanent labelling Storage YES Interior Finishes YES CO Detectors YES Clearance to Sprinkler/Ceiling YES Knox Box: installed/checked YES Occupancy Cycle YES B Feb 28, 2019 Page (2) Patrick Palmer, Mike (Inspector) INSPECTION WORKSHEET (FM-001225-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Fri Mar 1, 2019 Inspection Status:Partial Pass Inspector:Mike Palmer Inspection Type:OCC-Inspections Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Primary Owner Okie Properties, LLC Contractor J. Luke Construction Architect Monarch Design Group LLC Applicant J. Luke Construction Granted Permission Okie Properties, LLC Tenant Motimac USA Checklist Item Passed Comments Fire Marshal YES Inspection of Suite 2 Exit Access YES Exit Enclosure YES Exit Discharge YES Locks and Latches YES Sign: Normal YES Mar 01, 2019 Page (1) INSPECTION WORKSHEET (FM-001225-2019) Checklist Item Passed Comments Sign: Backup NO Need to verify Main Aisle Width YES Secondary Aisle Width YES Fire Extinguisher Hung YES Need to verify Inspection of Extinguisher YES Emergency Lighting Interior YES Need to verify Clearance to Electrical YES Electrical Wiring Enclosed/Labeled NO Need permanent labelling 3/1. - breaker to test door fixtures is in space 1. Wire devices to activate in Space 2 service panel Storage YES Interior Finishes YES CO Detectors YES Clearance to Sprinkler/Ceiling YES Knox Box: installed/checked YES Occupancy Cycle YES B Mar 01, 2019 Page (2) Patrick Palmer, Mike (Inspector) INSPECTION WORKSHEET (BINS-001217-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Fri Mar 1, 2019 Inspection Status:Partial Pass Inspector:John O'Brien Inspection Type:Commercial Final Inspection Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Applicant J. Luke Construction Primary Owner Okie Properties, LLC Granted Permission Okie Properties, LLC Architect Monarch Design Group LLC Contractor J. Luke Construction Tenant Motimac USA Checklist Item Passed Comments Firewalls, 2 Hr, 3 Hr / Fire Dampers / Fire Doors NO Handicapped Service Counters 34 inch NO -Install break room counter with sink as per plan, range not allowed. Remove outlet box from break room partition, wiring and breakers from panel for range. Bldg Num or Tenant Address on Bld or Drive YES Install Suite Number Special Inspections NO -Submit HVAC Air Balancing Report for Suite #2 Mar 01, 2019 Page (1) INSPECTION WORKSHEET (BINS-001217-2019) Checklist Item Passed Comments OK to Issue Temporary C/O NO 3/1/19 Final Inspection Partial Approval-Ok to Issue a Temporary CO! Conditions -Submit HVAC Air Balancing Report for Suite #2 -Install break room counter with sink as per plan, range not allowed. Remove outlet box from break room partition, wiring and breakers from panel for range. -Complete outstanding Fire Marshal's item regarding wiring of emergency lights and exit signs for each individual tenant space. OK to Issue C/O NO 2/28/19 Final Inspection Not Approved Remaining Items: -Submit HVAC Air Balancing Report for Suite #1 & #2 -Install Suite Number -Install right handed flush handle handicapped toilet. -Install break room counter with sink as per plan no stove. -Complete Fire Marshal's Items. Mar 01, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (FIST-001138-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Mon Feb 25, 2019 Inspection Status:Passed Inspector:John O'Brien Inspection Type:Firestopping Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Tenant Motimac USA Contractor J. Luke Construction Architect Monarch Design Group LLC Applicant J. Luke Construction Primary Owner Okie Properties, LLC Granted Permission Okie Properties, LLC Checklist Item Passed Comments Building Inspector Notes YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. 1/31/19 Firestopping Partial Approval - Fire Caulking at Suite 1 side of Demise Wall except over bathroom area. 2/25/19 Fire Separation Approved - Suite #2 wall between Suite #1 & Suite #2. Feb 25, 2019 Page (1) INSPECTION WORKSHEET (FIST-001138-2019) Checklist Item Passed Comments Fire separation 1, 2, 3 hour YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 1/28/19 Sample Fire Caulking at top of tenant separation wall approved. 1/31/19 Firestopping Partial Approval - Fire Caulking at Suite 1 side of Demise Wall except over bathroom area. 2/25/19 Fire Separation Approved - Suite #2 wall between Suite #1 & Suite #2. Penetration sealed YES 1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. 2/25/19 Fire Separation Approved - Suite #2 wall between Suite #1 & Suite #2. Feb 25, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (RPLUM-000833-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Fri Feb 8, 2019 Inspection Status:Partial Pass Inspector:John O'Brien Inspection Type:Rough Plumbing Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Contractor J. Luke Construction Applicant J. Luke Construction Architect Monarch Design Group LLC Granted Permission Okie Properties, LLC Primary Owner Okie Properties, LLC Checklist Item Passed Comments Building Inspector Notes NO 2/8/19 Plumbing Partial Approval - Sanitary & Water Remaining Items: - Need to Install and pressurize vent stack to exterior side wall termination location. Rough Plumbing / Nail Plates YES 2/8/19 Plumbing Partial Approval - Sanitary & Water Remaining Items: - Need to Install and pressurize vent stack to exterior side wall termination location. Plumbing Vent Vents in Place NO 2/8/19 Plumbing Partial Approval - Sanitary & Water Remaining Items: - Need to Install and pressurize vent stack to exterior side wall termination location. 3" Vent Through Roof NO Feb 08, 2019 Page (1) INSPECTION WORKSHEET (RPLUM-000833-2019) Checklist Item Passed Comments Pressure Test YES Sanitary Air Head YES Head 5 psi or 10 ft. above highest conn. for 15 minutes YES 10 ft head Pressure Test YES Water Air Head YES Air 50 P.S.I for 15 minutes YES 100 psi Air Test Gas Piping 10 psi for 10 Minutes NO All Return Air Hard Duct Work NO Duct Insulation - if required in unheated spaces NO Duct Testing Outside Conditioned Space NO Duct work sealed properly NO Feb 08, 2019 Page (2) O'Brien, John (Inspector) INSPECTION WORKSHEET (BINS-000933-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number:CC-0005-2019 Case Module:Permit Inspection Date:Wed Feb 13, 2019 Inspection Status:Passed Inspector:John O'Brien Inspection Type:Building Insulation Job Address:Parcel Number:75 CAREY RD Queensbury, NY 12804 308.20-1-3.3 Contact Type Company Name Name Contractor J. Luke Construction Granted Permission Okie Properties, LLC Architect Monarch Design Group LLC Applicant J. Luke Construction Primary Owner Okie Properties, LLC Checklist Item Passed Comments Building Inspector Notes YES 2/13/19 Insulation Approved-Interior partitions Insulation Residential Check Commercial Check YES 2/13/19 Insulation Approved-Interior partitions Feb 13, 2019 Page (1) O'Brien, John (Inspector) INSPECTION WORKSHEET (FIST-000519-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal CC-0005-2019Permit Case Number:Case Module: Wed Jan 23, 2019Failed Inspection Date:Inspection Status: John O'BrienFirestopping Inspector:Inspection Type: 75 CAREY RD308.20-1-3.3 Job Address:Parcel Number: Queensbury, NY 12804 Contact TypeCompany NameName ArchitectMonarch Design Group LLC ContractorJ. Luke Construction Primary OwnerOkie Properties, LLC Granted PermissionOkie Properties, LLC ApplicantJ. Luke Construction Checklist ItemPassedComments Building Inspector NotesNO1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. Fire separation 1, 2, 3 hourNO1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. Jan 23, 2019Page (1) INSPECTION WORKSHEET (FIST-000519-2019) Checklist ItemPassedComments Penetration sealedNO1/23/19 Firestopping Not Approved- Tenant Separation Wall Remaining Items: - Need to fire caulk joint between top of wall and roof panels both sides of wall. - Need to fire caulk joints at ends of walls and exterior wall panels on both sides of wall. - Seal all wall penetrations with fire caulk on both sides of wall. O'Brien, John (Inspector) Jan 23, 2019Page (2) INSPECTION WORKSHEET (BINS-000518-2019) Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal CC-0005-2019Permit Case Number:Case Module: Wed Jan 23, 2019Partial Pass Inspection Date:Inspection Status: John O'BrienBuilding Framing Inspector:Inspection Type: 75 CAREY RD308.20-1-3.3 Job Address:Parcel Number: Queensbury, NY 12804 Contact TypeCompany NameName ArchitectMonarch Design Group LLC ContractorJ. Luke Construction Primary OwnerOkie Properties, LLC Granted PermissionOkie Properties, LLC ApplicantJ. Luke Construction Checklist ItemPassedComments Building Inspector NotesNO1/23/19 Framing Partial Approval- Non-bearing Interior partitions for Bathroom, Mechanical Room, and coffee area. FramingYES1/23/19 Framing Partial Approval- Non-bearing Interior partitions for Bathroom, Mechanical Room, and coffee area. Design Professional Sign-off, if requiredNO O'Brien, John (Inspector) Jan 23, 2019Page (1)