comcheck AfiCOMcheck Software Version 4.1.1.0
i Envelope Compliance Certificate
Project Information D fG �' .. '17 rp
Energy Code: 2015 IECC I�
Project Title: Additions to the Maintenance Facility r,...._
tl]�N ,. _ e,
Location: Glens Falls, New York AIM
��
Climate Zone: 6a �..:m..--n,,-
Project Type: Addition TOE`•,_;:; a,r-�1:3URY
Vertical Glazing/Wall Area: 3% COMMUNI; i ''L.): 1/ELOPMENT
Construction Site: Owner/Agent: Designer/Contractor:
Jenkinsville Road Town of Queensbury Ethan P. Hall
Queensbury, NY 12804 742 Bay Road Rucinski Hall Architecture
Queensbury, NY 12804 134 Dix Ave
Glens Falls, NY 12801
518-741-0268
ephall@nycap.rr.com
Building Area Floor Area
1-Workshop: Nonresidential 380
Envelope Assemblies
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factorcei
Perimeter
Roof 1:Other Metal Building Roof,[Bldg.Use 1 -Workshop](b) 676 -- -- 0.015 0.031
Floor 1:Slab-On-Grade:Unheated,Vertical 4 ft.,[Bldg.Use 1 - 181 --- 10.0 0.480 0.540
Workshop](d)
EAST
Exterior Wall 3:Steel-Framed,24"o.c.,[Bldg.Use 1 -Workshop] 420 21.0 0.0 0.090 0.064
SOUTH
Exterior Wall 2:Steel-Framed,24"o.c.,[Bldg.Use 1 -Workshop] 420 21.0 0.0 0.090 0.064
Window 2:Metal Frame with Thermal Break:Operable,Perf.Specs.: 20 -- -- 0.290 0.430
Product ID product label,SHGC 0.33,[Bldg.Use 1 -Workshop](c)
Door 1: Insulated Metal,Swinging,[Bldg.Use 1 -Workshop] 21 -- -- 0.300 0.370
WEST
Exterior Wall 1:Steel-Framed,24"o.c.,[Bldg.Use 1 -Workshop] 350 21.0 0.0 0.090 0.064
Window 1:Metal Frame with Thermal Break:Operable,Pert.Specs.: 20 -- -- 0.290 0.430
Product ID product label,SHGC 0.33,[Bldg.Use 1 -Workshop](c)
(a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
(b)'Other'components require supporting documentation for proposed U-factors.
(c)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(d)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
279.-1-21 AST-0593-2019
Town of Queensbury Rec Dept
133 Jenkinsville Rd
Maintenance Bldg Addition 1550 s.f.
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 1 of 18
2018\Jenkinsville Maintenance Building.cck
Envelope PASSES: Design 0.0% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed envelope systems have been
designed to meet the 2015 IECC requirements in COMcheck Versio 4.1.1.0 nd to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Ethan P. Hall-Architect !""'a. fi9/17
Name-Title Signatur uate
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 2 of 18
2018\Jenkinsville Maintenance Building.cck
COMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Additions to the Maintenance Facility
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
Jenkinsville Road Town of Queensbury Ethan P. Hall
Queensbury, NY 12804 742 Bay Road Rucinski Hall Architecture
Queensbury, NY 12804 134 Dix Ave
Glens Falls, NY 12801
518-741-0268
ephall@nycap.rr.com
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Wafts I ft2 (B X C)
1-Common Space Types:Workshop 380 1.59 604
Total Allowed Watts= 604
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Common Space Types:Workshop
LED 1:LED Linear 20W: 2 6 33 198
LED 2:LED PAR 17W: 1 6 34 204
Total Proposed Watts= 402
Interior Lighting PASSES: Design 33% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The - •posed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck V- '•n 4.1.r a • co y with any applicable mandatory
requirements listed in the Inspection Checklist. Q Q,
Ethan P.Hall-Architect / - • Ac/b. 219/9
Name-Title Si. --•re Date
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 3 of 18
2018\Jenkinsville Maintenance Building.cck
AfiCOMcheck Software Version 4.1.1.0
l Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Additions to the Maintenance Facility
Project Type: Addition
Exterior Lighting Zone 2(Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
Jenkinsville Road Town of Queensbury Ethan P. Hall
Queensbury, NY 12804 742 Bay Road Rucinski Hall Architecture
Queensbury, NY 12804 134 Dix Ave
Glens Falls, NY 12801
518-741-0268
ephall@nycap.rr.com
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Wafts
Wafts/Unit Wattage (B X C)
Entry canopy 1 ft2 0.25 Yes 0
Total Tradable Watts(a)= 0
Total Allowed Watts= 0
Total Allowed Supplemental Watts(b)= 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Entry canopy(1 ft2):Tradable Wattage
LED 1:LED A Lamp 13W: 1 1 34 34
Total Tradable Proposed Watts= 34
Exterior Lighting PASSES: Design 94% better than code
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit applicatio .The • •••s-• exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck ion 4.1. i an. o c • pl, with any applicable mandatory
requirements listed in the Inspection Checklist.
Ethan P. Hall-Architect -V of) l% hiq
Name-Title 5' 1 Date
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 4 of 18
2018\lenkinsville Maintenance Building.cck
• COMcheck Software Version 4.1.1.0
Mechanical Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Additions to the Maintenance Facility
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
Jenkinsville Road Town of Queensbury Ethan P. Hall
Queensbury, NY 12804 742 Bay Road Rucinski Hall Architecture
Queensbury, NY 12804 134 Dix Ave
Glens Falls, NY 12801
518-741-0268
ephall@nycap.rr.com
Mechanical Systems List
Quantity System Type&Description
1 HVAC System 1 (Single Zone):
Heating: 1 each-Unit Heater,Gas,Capacity=45 kBtu/h
Proposed Efficiency=90.00%Ec,Required Efficiency: 80.00%Ec
Fan System: None
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck V- ion 4.1. ' an. • o• • with any applicable mandatory
requirements listed in the Inspection Checklist. 41/
/ /
Ethan P. Hall-Architect I iVp0.��g
Name-Title Si . .re Date
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 5 of 18
2018\Jenkinsville Maintenance Building.cck
COMcheck Software Version 4.1.1.0
IIInspection Checklist
Energy Code: 2015 IECC
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans and/or specifications provide all DComplies Requirement will be met.
[PR1]1 information with which compliance ODoes Not
can be determined for the building ❑Not Observable Location on plans/spec:A-1
envelope and document where
exceptions to the standard are ❑Not Applicable
claimed.
C103.2 Plans, specifications,and/or ❑Complies Requirement will be met.
[PR2]1 calculations provide all information ODoes Not
with which compliance can be DNot Observable Location on plans/spec: M-1
determined for the mechanical
systems and equipment and DNot Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
C103.2 Plans, specifications, and/or ❑Complies Requirement will be met.
(PRO calculations provide all information ODoes Not
with which compliance can be ❑Not Observable Location on plans/spec: E-1
determined for the interior lighting
and electrical systems and equipment DNot Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
C103.2 Plans,specifications,and/or ❑Complies Requirement will be met.
[PR8]1 calculations provide all information ODoes Not
with which compliance can be ❑Not Observable Location on plans/spec: E-1
determined for the exterior lighting
and electrical systems and equipment DNot Applicable
and document where exceptions to
the standard are claimed.Information
provided should include exterior
lighting power calculations,wattage of
bulbs and ballasts,transformers and
control devices.
C402.4.1 The vertical fenestration area <= 30 ❑Complies Requirement will be met.
[PR10]1 percent of the gross above-grade wall ODoes Not
area. Location on plans/spec:A-1
❑Not Observable
DNot Applicable
C402.4.1 The skylight area <= 3 percent of the ❑Complies Requirement will be met.
[PR11]1 gross roof area. DDoes Not
DNot Observable Location on plans/spec:A-1
DNot Applicable
1 1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) 3 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 6 of 18
2018Venkinsville Maintenance Building.cck
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C406 Plans, specifications, and/or ❑Complies Requirement will be met.
[PR9]1 calculations provide all information ❑Does Not
with which compliance can be ❑Not Observable Location on plans/spec:A-1
determined for the additional energy
efficiency package options. ❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) 12 'Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 7 of 18
2018\Jenkinsville Maintenance Building.cck
Section
# Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID
C303.2 Slab edge insulation installed per ElComplies Requirement will be met.
[FO4]Z manufacturer's instructions. ❑Does Not
❑Not Observable Location on plans/spec:A-1
ONot Applicable
C303.2.1 Exterior insulation protected against ❑Complies Requirement will be met.
[FO6J1 damage,sunlight, moisture, wind, ODoes Not
landscaping and equipment
maintenance activities. Not Observable
❑Not Applicable
C402.2.5 Slab edge insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[FO3]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant heating systems panels ❑Complies Exception: Requirement does not apply.
[FO12]3 insulated to>=R-3.5 on face opposite ❑Does Not
space being heated. ❑Not Observable See the Envelope Assemblies table for values.
❑Not Applicable
C403.2.4. Snow/ice melting system sensors for ❑Complies Exception: Requirement does not apply.
5, future connection to controls. Freeze ❑Does Not
C403.2.4. protection systems have automatic
6 controls installed. :Not Observable
[FO9J3 ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 8 of 18
2018\Jenkinsville Maintenance Building.cck
Section
Framing/Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C303.1.3 Fenestration products rated in ❑Complies Requirement will be met.
[FR12]2 accordance with NFRC. ❑Does Not
[Not Observable Location on plans/spec:A-1
❑Not Applicable
C303.1.3 Fenestration products are certified as ❑Complies Requirement will be met.
[FR13]1 to performance labels or certificates ❑Does Not
provided. Location on plans/spec:A-1
❑Not Observable
❑Not Applicable
C402.4.3 Vertical fenestration SHGC value. ❑Complies See the Envelope Assemblies table for values.
[FR10]1 ❑Does Not
['Not Observable
❑Not Applicable
C402.4.3, Vertical fenestration U-Factor. ❑Complies See the Envelope Assemblies table for values.
C402.4.3. ❑Does Not
4
[FR8]1 ONot Observable
❑Not Applicable
C402.4.4 U-factor of opaque doors associated ❑Complies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ❑Does Not
meets requirements.
❑Not Observable
❑Not Applicable
C402.5.1 The building envelope contains a ❑Complies Requirement will be met.
[FR16]1 continuous air barrier that is sealed in ❑Does Not
an approved manner and either ❑Not Observable Location on plans/spec:A-1
constructed or tested in an approved
manner.Air barrier penetrations are ❑Not Applicable
sealed in an approved manner.
C402.5.2, Factory-built fenestration and doors ❑Complies Requirement will be met.
C402.5.4 are labeled as meeting air leakage ❑Does Not
[FR18]3 requirements.
❑Not Observable
❑Not Applicable
C402.5.7 Vestibules are installed on all building ❑Complies Exception: Requirement does not apply.
[FR17]3 entrances. Doors have self-closing Does Not
devices.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 1 2 'Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 9 of 18
2018venkinsville Maintenance Building.cck
Section
Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Req.ID_
C404.5, Heated water supply piping conforms ❑Complies Exception: Requirement does not apply.
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details.
[PL6]3 ❑Not Observable
❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies Exception: Requirement does not apply.
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating ['Not Observable
cycle. ❑Not Applicable
C404.7 Water distribution system that pumps ❑Complies Exception: Requirement does not apply.
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source
through a cold-water supply pipe is a ['Not Observable
demand recirculation water system. Observable,_,
Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Additional Comments/Assumptions:
1 l High Impact(Tier 1) 2 j Medium Impact(Tier 2) 3 'Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 10 of 18
2018\Jenkinsville Maintenance Building.cck
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C402.2.6 Thermally ineffective panel surfaces of❑Complies Exception: Requirement does not apply.
[ME41]3 sensible heating panels have ❑Does Not
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
C402.5.5, Stair and elevator shaft vents have ❑Complies Exception: Requirement does not apply.
C403.2.4. motorized dampers that automatically ODoes Not
3
[ME3]3 close. ONot Observable
❑Not Applicable
C402.5.5, Outdoor air and exhaust systems have ❑Complies Exception: Requirement does not apply.
C403.2.4. motorized dampers that automatically ❑Does Not
3 shut when not in use and meet
[ME58]3 maximum leakage rates.Check ❑Not Observable
gravity dampers where allowed. ❑Not Applicable
C403.2.12 HVAC fan systems at design ❑Complies Requirement will be met.
.1 conditions do not exceed allowable ❑Does Not
[ME65]3 fan system motor nameplate hp or fan ❑Not Observable Location on plans/spec: M-1
system bhp.
❑Not Applicable See the Mechanical Systems list for values.
C403.2.12 Fans have efficiency grade(FEG)>= ❑Complies Exception: Single fans with motor nameplate horsepowerof=
.3 67.The total efficiency of the fan at ❑Does Not 5 hp.
[ME117]2 the design point of operation <= 15%
of maximum total efficiency of the ['Not Observable
fan. ❑Not Applicable
C403.2.13 Unenclosed spaces that are heated ❑Complies Exception: Requirement does not apply.
[ME71]2 use only radiant heat. ❑Does Not
[Not Observable
❑Not Applicable
C403.2.3 HVAC equipment efficiency verified. ❑Complies See the Mechanical Systems list for values.
[ME55]2 ❑Does Not
❑Not Observable
❑Not Applicable
C403.2.6. Demand control ventilation provided ❑Complies Exception: Requirement does not apply.
1 for spaces>500 ft2 and >25 ❑Does Not
[ME59]1 people/1000 ft2 occupant density and
served by systems with air side Not Observable
economizer, auto modulating outside ❑Not Applicable
air damper control, or design airflow
>3,000 cfm.
C403.2.6. Enclosed parking garage ventilation ❑Complies Exception: Requirement does not apply.
2 has automatic contaminant detection ❑Does Not
[ME115]3 and capacity to stage or modulate
fans to 50%or less of design capacity. Not Observable
❑Not Applicable
C403.2.7 Exhaust air energy recovery on ❑Complies Exception: Requirement does not apply.
[ME57)1 systems meeting Table C403.2.7(1) ❑Does Not
and C403.2.7(2). ❑Not Observable
❑Not Applicable
C403.2.8 Kitchen exhaust systems comply with ❑Complies Exception: Requirement does not apply.
[ME116]3 replacement air and conditioned ❑Does Not
supply air limitations, and satisfy hood
rating requirements and maximum Not Observable
exhaust rate criteria. ENot Applicable
C403.2.9 HVAC ducts and plenums insulated. DComplies Exception: Requirement does not apply.
[ME60]2 Where ducts or plenums are installed ❑Does Not
in or under a slab, verification may
need to occur during Foundation ❑Not Observable
Inspection. ❑Not Applicable
1 [High Impact(Tier 1) 12 I Medium Impact(Tier 2) 13 _Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 11 of 18
2018\enkinsville Maintenance Building.cck
Section
Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C403.2.9 Ducts and plenums sealed based on ❑Complies Requirement will be met.
[ME10]2 static pressure and location. ODoes Not
:Not Observable Location on plans/spec: M-1
DNot Applicable
C403.2.9. Ductwork operating >3 in.water DComplies Exception: Requirement does not apply.
1.3 column requires air leakage testing. ❑Does Not
[ME11]3 ❑Not Observable
❑Not Applicable
C403.4.4. Multiple zone VAV systems with DDC ❑Complies Exception: Requirement does not apply.
6 of individual zone boxes have static DDoes Not
[ME110]3 pressure setpoint reset controls. ❑Not Observable See the Mechanical Systems list for values.
❑Not Applicable
C408.2.2. Air outlets and zone terminal devices DComplies Exception: Requirement does not apply.
1 have means for air balancing. DDoes Not
[ME53]3 ❑Not Observable
❑Not Applicable
C403.5, Refrigerated display cases,walk-in DComplies Exception: Requirement does not apply.
C403.5.1, coolers or walk-in freezers served by DDoes Not
C403.5.2 remote compressors and remote
[ME123]3 condensers not located in a ['Not Observable
condensing unit, have fan-powered ❑Not Applicable
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 12 of 18
2018\enkinsville Maintenance Building.cck
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.1 Lighting controls installed to uniformly ❑Complies Requirement will be met.
[EL15]1 reduce the lighting load by at least ❑Does Not
50%. Location on plans/spec: E-1
['Not Observable
❑Not Applicable
C405.2.1 Occupancy sensors installed in DComplies Requirement will be met.
[EL18]1 required spaces. ❑Does Not
['Not Observable Location on plans/spec: E-1
❑Not Applicable
C405.2.1, Independent lighting controls installed DComplies Requirement will be met.
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and Location on plans/spec: E-1
[EL23]2 visible to occupants. ['Not Observable
❑Not Applicable
C405.2.2. Automatic controls to shut off all DComplies Requirement will be met.
1 building lighting installed in all ElDoes Not
[EL22]2 buildings. Location on plans/spec: E-1
ENot Observable
❑Not Applicable
C405.2.3 Daylight zones provided with ❑Complies Exception: Requirement does not apply.
[EL16]2 individual controls that control the ❑Does Not
lights independent of general area
lighting. ENot Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are DComplies Exception: Requirement does not apply.
C405.2.3. equipped with required lighting ❑Does Not
1, controls.
C405.2.3. ENot Observable
2 ❑Not Applicable
[EL20J1
C405.2.3, Enclosed spaces with daylight area DComplies Exception: Requirement does not apply.
C405.2.3. under skylights and rooftop monitors ODoes Not
1, are equipped with required lighting
C405.2.3. controls. ONot Observable
3 ENot Applicable
[EL21]1
C405.2.4 Separate lighting control devices for DComplies Requirement will be met.
[EL4J1 specific uses installed per approved ❑Does Not
lighting plans. Location on plans/spec: E-1
❑Not Observable
ENot Applicable
C405.2.4 Additional interior lighting power DComplies Requirement will be met.
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is ❑Not Observable Location on plans/spec: E-1
automatically controlled and
separated from general lighting. ENot Applicable
C405.2.5 Automatic lighting controls for exterior DComplies Exception: Requirement does not apply.
[EL25]na0 lighting installed.Controls will be ❑Does Not
daylight controlled,set based on
business operation time-of-day,or ❑Not Observable
reduce connected lighting >30%. ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per DComplies Requirement will be met.
[EL6J1 face. ❑Does Not
[Not Observable Location on plans/spec: E-1
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 12 1 Medium Impact(Tier 2) 1 3 'Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 13 of 18
2018lenkinsville Maintenance Building.cck
1 High Impact(Tier 1) 2 [Medium Impact(Tier 2) I 3 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 14 of 18
2018Venkinsville Maintenance Building.cck
Section
# Insulation Inspection Complies? Comments/Assumptions
& Req.ID
C303.1 Roof insulation installed per EComplies Requirement will be met.
[IN3]1 manufacturer's instructions. Blown or EDoes Not
poured loose-fill insulation is installed ❑Not Observable Location on plans/spec:A-1
only where the roof slope is<=3 in
12. ❑Not Applicable
C303.1 Building envelope insulation is labeled ❑Complies Requirement will be met.
[IN10]z with R-value or insulation certificate ❑Does Not
providing R-value and other relevant
data. ['Not Observable
❑Not Applicable
C303.2 Above-grade wall insulation installed ❑Complies Requirement will be met.
[IN7]1 per manufacturer's instructions. ❑Does Not
❑Not Observable Location on plans/spec:A-1
❑Not Applicable
C303.2.1 Exterior insulation is protected from ❑Complies Exception: Requirement does not apply.
[IN14]Z damage with a protective material. ❑Does Not
Verification for exposed foundation
insulation may need to occur during ❑Not Observable
Foundation Inspection. ❑Not Applicable
C402.2.1 Insulation intended to meet the roof ❑Complies Requirement will be met.
[IN17]3 insulation requirements cannot be ❑Does Not
installed on top of a suspended ['Not Observable Location on plans/spec:A-1
ceiling. Mark this requirement
compliant if insulation is installed ❑Not Applicable
accordingly.
C402.2.3 Above-grade wall insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN6]1 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.5 Floor insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN812 ❑Does Not
['Not Observable
❑Not Applicable
C402.2.6 Radiant panels and associated ❑Complies Exception: Requirement does not apply.
[IN18]3 components, designed for heat ❑Does Not
transfer from the panel surfaces to the
occupants or indoor space are ❑Not Observable
insulated with a minimum of R-3.5. ❑Not Applicable
C402.2.2 Roof R-value.For some ceiling ❑Complies See the Envelope Assemblies table for values.
[IN2]1 systems,verification may need to ❑Does Not
occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C402.5.1. All sources of air leakage in the ❑Complies Requirement will be met.
1 building thermal envelope are sealed, ❑Does Not
[IN1]1 caulked,gasketed, weather stripped ❑Not Observable Location on plans/spec:A-1
or wrapped with moisture vapor-
permeable wrapping material to ❑Not Applicable
minimize air leakage.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) I]Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 15 of 18
2018\Jenkinsville Maintenance Building.cck
• Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M instructions for OComplies Requirement will be met.
C408.2.5. systems and equipment to the ODoes Not
2 building owner or designated
[FI17]3 representative. DNot Observable
ONot Applicable
C303.3, Furnished O&M manuals for HVAC ❑Complies Requirement will be met.
C408.2.5. systems within 90 days of system ❑Does Not
3 acceptance.
[F18]3 ONot Observable
ONot Applicable
C402.5.3 Where open combustion air ducts ❑Complies Exception: Requirement is not applicable.
[FI51]3 provide combustion air to open ❑Does Not
combustion fuel burning appliances,
the appliances and combustion air ONot Observable
opening are located outside the ONot Applicable
building thermal envelope or enclosed
in a room, isolated from inside the
thermal envelope.Such rooms are
sealed and insulated.
C402.5.6 Weatherseals installed on all loading ❑Complies Exception: Requirement does not apply.
[FI37]' dock cargo doors. ❑Does Not
ONot Observable
ONot Applicable
C402.5.8 Recessed luminaires in thermal ❑Complies Exception: Requirement does not apply.
[FI26]3 envelope to limit infiltration and be IC ❑Does Not
rated and labeled.Seal between
interior finish and luminaire housing. ONot Observable
ONot Applicable
C403.2.2 HVAC systems and equipment ❑Complies Requirement will be met.
[FI27]3 capacity does not exceed calculated ❑Does Not
loads. Location on plans/spec: M-1
['Not Observable
ONot Applicable
C403.2.4. Heating and cooling to each zone is ❑Complies Requirement will be met.
1 controlled by a thermostat control. ❑Does Not
(FI47]3 Minimum one humidity control device ❑Not Observable Location on plans/spec: M-1
per installed
humidification/dehumidification ONot Applicable
system.
C403.2.4. Thermostatic controls have a 5 °F ❑Complies Requirement will be met.
1.2 deadband. ❑Does Not
[FI38]3 Location on plans/spec: M-1
[Not Observable
ONot Applicable
C403.2.4. Temperature controls have setpoint ❑Complies Exception: Requirement does not apply.
1.3 overlap restrictions. ['Does Not
[FI20]3 ['Not Observable
ONot Applicable
C403.2.4. Each zone equipped with setback ❑Complies Exception: Requirement does not apply.
2 controls using automatic time clock or ❑Does Not
[F139]3 programmable control system.
['Not Observable
ONot Applicable
C403.2.4. Automatic Controls: Setback to 55°F ❑Complies Exception: Requirement does not apply.
2.1, (heat)and 85°F (cool); 7-day clock, 2- ❑Does Not
C403.2.4. hour occupant override, 10-hour
2.2 backup ❑Not Observable
(F140]3 ONot Applicable
r i High Impact(Tier 1) 12 'Medium Impact(Tier 2) 3 I Low Impact(Tier 3)
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 16 of 18
2018\Jenkinsville Maintenance Building.cck
. Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[F118]1 lighting power is consistent with what DDoes Not
is shown on the approved lighting
plans, demonstrating proposed watts ['Not Observable
are less than or equal to allowed Observable,__,
Applicable
watts.
C405.5.1 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[FI19]1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal Not Observable
to allowed watts. Observable,....,
Applicable
C408.2.1 Commissioning plan developed by ❑Complies Requirement will be met.
[FI28]1 registered design professional or DDoes Not
approved agency. Location on plans/spec: M-1
[Not Observable
❑Not Applicable
C408.2.3. HVAC equipment has been tested to ❑Complies Exception: Unitary or packaged HVAC eqiupment without
1 ensure proper operation. DDoes Not supply air economizers.
[FI31]1 ❑Not Observable
❑Not Applicable
C408.2.3. HVAC control systems have been ❑Complies Requirement will be met.
2 tested to ensure proper operation, DDoes Not
[FI10]1 calibration and adjustment of controls. ❑Not Observable Location on plans/spec: M-1
❑Not Applicable
C408.2.4 Preliminary commissioning report ❑Complies Requirement will be met.
[FI29]1 completed and certified by registered DDoes Not
design professional or approved ❑Not Observable Location on plans/spec: M-1
agency. ❑Not Applicable
C408.2.5. Furnished HVAC as-built drawings ❑Complies Requirement will be met.
1 submitted within 90 days of system ❑Does Not
[FI7]3 acceptance.
['Not Observable
❑Not Applicable
C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met.
1 electric power systems within 90 days DDoes Not
(FI16]3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.2.5. An air and/or hydronic system ❑Complies Requirement will be met.
3 balancing report is provided for HVAC DDoes Not
[FI43]1 systems. Location on plans/spec: M-1
[Not Observable
❑Not Applicable
C408.2.5. Final commissioning report due to ❑Complies Requirement will be met.
4 building owner within 90 days of DDoes Not
[F130]1 receipt of certificate of occupancy. DNot Observable Location on plans/spec: M-1
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[FI33]1 ensure proper calibration, adjustment, DDoes Not
programming, and operation. ❑Not Observable Location on plans/spec: E-1
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 12 'Medium Impact(Tier 2) 13 Low Impact(Tier 3) I
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec. Dept\New Maintenance Facility\Building Expansion Page 17 of 18
2018\enkinsville Maintenance Building.cck
Project Title: Additions to the Maintenance Facility Report date: 08/30/19
Data filename: Y:\Town of Queensbury\Queensbury Rec, Dept\New Maintenance Facility\Building Expansion Page 18 of 18
2018\Jenkinsville Maintenance Building.cck