Adirondack Air Balance Co., Inc.
Test and Balance Reports
Project: Glens Falls National Bank
Address: 221 Corinth Rd. Queensbury,New York 12804
• Contractor: Hilltop Construction Co.
Address: 51 Crowley Rd,Hudson Falls, New York 12839
Certification:
The systems herein have been tested and balanced to
within tolerances specified in the plans and specifications or to
within the limitations of the equipment installed.All the Testing
and Balancing has been performed in accordance with The
Associated Air Balance Council and The National Environmental
Balancing Bureau.The results of those tests are recorded herein.
Date:8/24/2019 By: ! Q.i IV\PAiy
John C. Merry
TESTING"AND BALANCING AGENCY: ADIRONDACK AIR BALANCE CO.,INC.
INSTRUMENT LIST For John C.Merry
•
Instrument Manufacturer Model# Calibration Range Serial#
Date
Capture Hood Shortridge ADM 860 2/12/2019 0-2000 CFM M65580
Air Data Shortridge ADM 2/19/2019 50-8000 FPM M08668
Multimeter 860C
Thermal TSI AVM430 2/22/2019 0-6,000 FPM AVM430916003
Anemometer
Incline Dwyer 400 Not Required 0-12,000FPM Not
Manometer 0-10" Required
Magnehelics Dwyer 2002C Not Required 0-2.5" Not
2008 0-8" Required
Sling Taylor 1330 Not Required 32-100F Not
Psychrometer Required
PocketThermo- Taylor TA16903 Not Required -40-180F Not
• meter Required
Water Meter Alnor HM680 3/14/2018 0-300 PSI 70651020
HVAC Clamp Fluke 902 2/19/2019 0-600V 18400123
Meter 0-600A _
Tachometer Shimpo DT-207L 4/1/2019 0-90,000 RPM D56B0073
Vesting and Balancing.Agency: Date: 8/24/2019
Adirondack Air Balance Co.,Inc. Page: 1 of 2
Project# 3337
Project Name: Glens Fall.National Bank Address: 209 Corinth Rd. Queensbury,New York
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM F-1
Equipment Location MER
Area Served Entire Space
Equipment Manufacturer York
Model Number TG9S060B
Serial Number W1D8744930
. • Specified Actual Specified Actual
Total CFM-Fan 1000 NA
Total CFM-Outlet 1303 988
R/A CFM o NS 888
O/A CFM NS 100
Total Static Pressure(Total/Ext.) .50 Ext. .20 Ext.
Inlet Pressure NS 0.12
Discharge Pressure NS 0.08
Fan RPM NS High
Specified Actual Specified Actual.
Motor Manufacturer NS NA
Motor HP 1 BHP NS NA
Phase single single
Voltage 120 120
Amperage NA 5.9
Motor RPM NS • 3 Speed
Motor Service Factor NS 1.0.
Starter Heater Elements NS TP
Motor.Sheave&No. Grooves • Direct Drive
Fan Sheave&No. Grooves •
Belts
Remarks:.
Tenting and Balancing Agency: Date: 8/24/2019
Adirondack Air Balance Co..Inc. Page: 2 of 2
Project#: 3337
Project Name:.Glens Falls National Bank Address: 209 Corinth Rd. Queensbury,New York
AIR DISTRIBUTION TEST SHEET
Terminal Room Terminal Design Test-FPM or CFM Final
Number Number Type Size Factor FPM CFM Test I Test 2 Test 3 FPM CFM
F-1
1 108 CD 6"rd. 1.0 Hood 33 Del. Del.. NR Hood Del..
2 107 CD 7"rd. 1.0 Hood 117 115 70 NR Hood 70
3 104 CD 6"rd. 1.0 Hood 17 82 20 NR Hood 20
4 109 CD 8"rd. 1.0 Hood 137 46 120 NR Hood 120
5 103 CD 8"rd. 1.0 Hood 163 99 100 NR Hood 100
6 110 CD 6"rd. 1.0 Hood 89 72 75 NR Hood 75
7 102 CD 6"rd. 1.0 Hood 207 135 90 NR Hood 90
8 111 CD 6"rd. 1.0 Hood 90 76 75 NR Hood 75
9 101 CD 6"rd. 1.0 Hood 150 52 128 NR Hood 128
10 100 CD 6"rd. 1.0 Hood 150 141 151 NR Flood 151
11 100 CD 6"rd. 1.0 Hood 150 147 159 NR Flood 159
1303 988
HX-1 Supply
1 MER OD 6"rd. .20 NS NS 0 500 NR 500 100
Exhaust
1 MER OD 6"rd. .20 NS NS 0 535 NR 535 107
EF-1
1 104 ER 12x12 1.0 Hood NS 55 NR NR Hood 55