Loading...
Manual J Report Job: 1416 Manual S Compliance p Date: Mar 11,2019 Entire House By: Plan: 1416 FOOTHILL BUILDERS 5b CilruoaQic, Project Information For: FOOTHILLS BUILDERS QUEENSBURY, NY Cooling Equipment Design Conditions Outdoor design DB: 85.0°F Sensible gain: 27673 Btuh Entering coil DB: 75.3°F Outdoor design WB: 71.0°F Latent gain: 5461 Btuh Entering coil WB: 62.6°F Indoor design DB: 75.0°F Total gain: 33134 Btuh Indoor RH: 50% Estimated airflow: 1324 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split AC Manufacturer: York Model: TCGD36S41S3+FC43C3XC1+TM8V080C16MP11 Actual airflow: 1187 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load Total capacity: 0 Btuh 0% of load SHR: 0% Heating Equipment Design Conditions Outdoor design DB: -4.0°F Heat loss: 103228 Btuh Entering coil DB: 65.5°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Gas furnace Manufacturer: York Model: TM9X120D2OMP11 Actual airflow: 1187 cfm Output capacity: 114000 Btuh 110% of load Temp. rise: 50 °F MAR 11 2019 TOWN OF QUEEN`BURY Meets are all requirements of ACCA Manual S. BLlll i i 1p &CO `-S 2019-Mar-11 11:24:46 wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACCP, ....langeworthy\Documents\York\56 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Residential Plans Examiner Review Form Form ACCk for HVAC System Design (Loads, Equipment, Ducts) 15Mar09 ArCaxl6mig Calmar*ciArreta QUEENSBURY NY Header Information Contractor: FOOTHILL BUILDERS REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes ❑ No E Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes ❑ No ❑ OEM performance data(heating,cooling,blower): Yes ❑ No ❑ Building plan#: 1416 Manual D Friction Rate Worksheet: Yes ❑ No ❑ Duct distribution sketch: Yes ❑ No D Home address(Street or Lot#, Block,Subdivision): , Entire House HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: -4 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 103228 Btuh Number of bedrooms: 3 Conditioned floor area: 4959 ft2 Summer Design Conditions Number of occupants: 0 Outdoor temperature: 85 °F Indoor temperature: 75 °F Windows Roof Grains difference: 27 gr/Ib 50% RH Eave overhang depth: 0 ft Sensible heat gain: 30748 Btuh Internal shade: none Eave Latent heat gain: 6068 Btuh Blinds,drapes,etc. Depth Window Total heat gain: 36815 Btuh Number of skylights: 0 HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Cooling Equipment Data Blower Data Equipment tye: Gas furnace Equipment type: Split AC Heating cfm: 1187 umace,Hea pump,Boiler,etc. it onditioner,Heat pump,etc. Cooling cfm: 1187 Model: York Model: York Static pressure: 0 in H2O TM9X120D2OMP11 TCGD36S41 S3 Fan's rated extemal static pressure for design airflow Heating output capacity:. 11400 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winter design outdoorconditions Sensible cooling capacity: 0 Btuh Aux.heating output capacity: 0 Btuh Latent cooling capacity: 0 Btuh HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Design airflow: 1187 cfm Longest supply duct: 0 ft Duct Materials Used Equipment design ESP: 0 in H2O Longest return duct: 0 ft Trunk duct: Total device pressure losses: 0 in H2O Total effective length(TEL): 0 ft Available static pressure(ASP): 0 in H2O Friction rate: 0 in/100ft Branch duct: Sheet metal Friction Rate=ASP=(TEL x 100) I declare the load calculation,equipment,equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature: Date: Reserved for County.Town Municipality orAuthority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist - wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Project Summary Job:Date: Mar Mar 11,2019 Entire House By: FOOTHILL BUILDERS Plan: 1416 Pro'ect Information For: FOOTHILLS BUILDERS QUEENSBURY, NY Notes: Desi• n Information Weather: Glens Falls AP, NY, US Winter Design Conditions Summer Design Conditions Outside db -4 °F Outside db 85 °F Inside db 68 °F Inside db 75 °F Design TD 72 °F Design TD 10 °F Daily range M Relative humidity 50 % Moisture difference 27 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 97112 Btuh Structure 26382 Btuh Ducts 6116 Btuh Ducts 1290 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 103228 Btuh Use manufacturer's data n Rate/swing multiplier 0.90 Infiltration Equipment sensible load 24906 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 5461 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling (none) Area (ft2) 4959 4959 Equipment latent load 5461 Btuh Volume(ft3) 44631 44631 Air changes/hour 0.70 0.40 Equipment total load 30367 Btuh Equiv.AVE (cfm) 521 298 Req. total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make York Make York Trade YORK Trade LATITUDE Model TM9X120D2OMP11 Cond TCGD36S41S3 AHRI ref 2008696 Coil FC43C3XC1+TM8V080C16MP11 AHRI ref 3740439 Efficiency 95.5AFUE Efficiency 11.5 EER, 14 SEER Heating input 120000 Btuh Sensible cooling 24920 Btuh Heating output 114000 Btuh Latent cooling 10680 Btuh Temperature rise 87 °F Total cooling 35600 Btuh Actual air flow 1187 cfm Actual air flow 1187 cfm Air flow factor 0.011 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.84 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2019-Mar-11 11:24:46 wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 /CCK ....langeworthy\Documents\York\56 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Right-J®Worksheet Job: 1416 Entire House Date: Mar 11,zols FOOTHILL BUILDERS Plan: 1416 MANUAL J:7th Ed. 1 Name of room Entire House Room1 Room2 Room3 2 Length of exposed wall 712.0 ft 130.0 ft 130.0 ft 21.0 ft 3 Room dimensions 1.0 x 916.0 ft 1.0 x 916.0 ft 11.0 x 10.0 ft 4 Ceilings Condit.Option 9.0 ft d 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 6408 **** **** 1170 **** **** 1170 **** **** 189 **** **** Exposed b 0 0 111111 **** **** will **** **** IIIIII **** **** IIIIII **** **** walls and c 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** partitions d 0 0 111111 **** **** III III **** **** 111111 **** **** ill III **** **** e 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** f 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** 6 Windows and a 3A0 39.7 ** 280 11108 **** 35 1389 **** 0 0 **** 15 595 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 50 **** 950 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 140 **** 9520 35 **** 2380 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 90 **** 3060 0 **** 0 0 **** 0 15 **** 510 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 126 4173 788 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 6002 32411 6122 1135 6129 1158 1170 6318 1193 174 940 177 exposed b 0 0 111111 0 0 null 0 0 null 0 0 111111 0 0 walls and c 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 IIIIII 0 0 partitions d 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 e 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 Ilan 0 0 f 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 10 Ceilings a 16G0 2.4 1.1 2379 5653 2669 0 0 0 84 200 94 0 0 0 b 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 c 0 0 IIIIII 0 0 nun 0 0 WWII 0 0 Inns 0 0 d 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 IIIIn 0 0 e 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 f 0 0 IIIIII 0 0 Ilan 0 0 IIIIII 0 0 IIIIII 0 0 11 Floors a 1910 1.7 0 916 1583 0 916 1583 0 0 0 0 0 0 0 (Note: room b 1910 1.7 0 547 945 0 0 0 0 0 0 0 0 0 0 perimeter c 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 is displ. d 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 for slab e 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 floors) f 0 0 111111 0 0 111111 0 0 Illnl 0 0 111111 0 0 12 Infiltration a 102 8.1 406 41239 3273 35 3555 282 0 0 0 15 1524 121 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 97112 **** **** 12655 **** **** 6518 **** **** 3058 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 6116 **** 6% 797 **** 6% 410 **** 6% 193 **** 15 Total loss= 13+14 **** 103228 **** **** 13453 **** **** 6928 **** **** 3251 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. © 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 26382 **** **** 3820 **** **** 1288 **** **** 808 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 1290 5% **** 187 5% **** 63 5% **** 40 19 Total RSH gain=(17+18)*PLF 1.00 **** 27673 1.00 **** 4007 1.00 **** 1351 1.00 **** 848 20 Air required(cfm) 1187 1187 155 172 80 58 37 36 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. ._,. WrlghtSOft® Right-Suite®Universal 2017 17.0.16 RSU25116 2019-Mar-11 11:24:46Page 1 Ae-e-P. ....langeworthy\Documents\York\56 JOHN CLENDON.rup Cale=MJ7 Front Door faces: N Right-J®Worksheet Job: 1416 Entire House Date: Mar 11,2019 By: FOOTHILL BUILDERS Plan: 1416 MANUAL J:7th Ed. 1 Name of room Room4 Room5 Room6 Room7 2 Length of exposed wall 10.0 ft 6.0 ft 2.0 ft 17.0 ft 3 Room dimensions 4.0 x 6.0 ft 6.0 x 6.0 ft 2.0 x 6.0 ft 1.0 x 162.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft*) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 90 **** **** 54 **** **** 18 **** **** 153 **** **** Exposed b 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** walls and c 0 0 111111 **** **** mill **** **** mill **** **** IIIIII **** **** partitions d 0 0 111111 **** **** IIIIII **** **** 111111 **** **** 111111 **** **** e 0 0 111111 **** **** IIIIII **** **** mill **** **** Him **** **** f 0 0 111111 **** **** II111I **** **** IIIIII **** **** 1IIIII **** **** 6 Windows and a 3A0 39.7 ** 0 0 **** 15 595 **** 0 0 **** 0 0 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 0 **** 0 15 **** 510 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 0 0 0 42 1391 263 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 90 486 92 39 211 40 18 97 18 111 599 113 exposed b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 walls and c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 1 1 1 111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 f 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 111111 0 0 c 0 0 111111 0 0 111111 0 0 111111 0 0 IIIIII 0 0 d 0 0 111111 0 0 111111 0 0 null 0 0 III111 0 0 e 0 0 111111 0 0 Mull 0 0 IIIIII 0 0 111111 0 0 f 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note:room b 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 perimeter c 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 111111 0 0 is displ. d 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 floors) f 0 0 Ilnn 0 0 nun 0 0 IIIIII 0 0 n1111 0 0 12 Infiltration a 102 8.1 0 0 0 15 1524 121 0 0 0 42 4266 339 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 486 **** **** 2329 **** **** 97 **** **** 6257 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 31 **** 6% 147 **** 6% 6 **** 6% 394 **** 15 Total loss= 13+14 **** 517 **** **** 2476 **** **** 103 **** **** 6651 **** 16 Int.gains: People @ 300 0 **** 0 0 **** '0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 92 **** **** 671 **** **** 18 **** **** 715 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 4 5% **** 33 5% **** 1 5% **** 35 19 Total RSH gain=(17+18)*PLF 1.00 **** 96 1.00 **** 704 1.00 **** 19 1.00 **** 750 20 Air required(cfm) 6 4 28 30 1 1 76 32 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2019-Mar-11 11:24:46 W rig htSOft' Right-Suite®Universal 2017 17.0.16 RSU25116 Page 2 AC ....langeworthy\Documents\York\56 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Right-J®Worksheet Job: 1416 Entire House Date: Mar 11,2019 By: FOOTHILL BUILDERS Plan: 1416 MANUAL J:7th Ed. 1 Name of room Room8 Room9 Room10 Room11 2 Length of exposed wall 0 ft 74.0 ft 162.0 ft 26.0 ft 3 Room dimensions 11.0 x 4.0 ft 1.0 x 528.0 ft 1.0 x 1106 ft 1.0 x 162.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 0 **** **** 666 **** **** 1458 **** **** 234 **** **** Exposed b 0 0 Him **** **** IIIIII **** **** mill **** **** IIIIII **** **** walls and c 0 0 11I I11 **** **** IIIIII **** **** Him **** **** I I I I I I **** **** partitions d 0 0 Hilt' **** **** will **** **** IIIIII **** **** I I I I I I **** **** e 0 0 111111 **** **** IIIIII **** **** 111111 **** **** 111111 **** **** f 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** IIIIII **** **** 6 Windows and a 3A0 39.7 ** 0 0 **** 60 2380 **** 0 0 **** 30 1190 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 0 **** 0 0 **** 0 30 **** 570 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 60 **** 4080 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 84 2782 526 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 0 0 0 522 2819 532 1458 7873 1487 204 1102 208 exposed b 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 walls and c 0 0 111111 0 0 Him 0 0 IIIIII 0 0 Him 0 0 partitions d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 o 0 e 0 0 111111 0 0 IIIIII 0 0 111111 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 0 0 0 84 200 94 1106 2628 1241 162 385 182 b 0 0 111111 0 0 null 0 0 mill 0 0 IIIIII 0 0 c 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 d 0 0 IIIIII 0 0 Him 0 0 Him 0 0 Hun 0 0 e 0 0 IIIIII 0 0 111111 0 0 111111 0 0 mill 0 0 f 0 0 Him 0 0 IIIIII 0 0 111111 0 0 IIIIII 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note: room b 1910 1.7 0 0 0 0 0 0 0 274 473 0 0 0 0 perimeter c 0 0 IIIIII 0 0 I I I I I I 0 0 null 0 0 Him 0 0 is displ. d 0 0 Him 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 111111 0 0 IIIIII 0 0 111111 0 0 111111 0 0 12 Infiltration a 102 8.1 0 0 0 144 14627 1161 0 0 0 30 3047 242 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 0 **** **** 22807 **** **** 10975 **** **** 5724 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 0 **** 6% 1436 **** 6% 691 **** 6% 361 **** 15 Total loss= 13+14 **** 0 **** **** 24244 **** **** 11666 **** **** 6084 **** 16 Int.gains: People© 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. © 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 0 **** **** 6393 **** **** 2728 **** **** 1202 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 0 5% **** 313 5% **** 133 5% **** 59 19 Total RSH gain=(17+18)*PLF 1.00 **** 0 1.00 **** 6706 1.00 **** 2862 1.00 **** 1260 20 Air required(cfm) 0 0 279 288 134 123 70 54 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 4 wrightsoft* 2019-Mar-11 11:24:46 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 3 ACC ....langeworthy\Documents\York\56 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Rig ht-J®Worksheet Job: 1416 Entire House Date: Mar 11,2019 By: FOOTHILL BUILDERS Plan: 1416 MANUAL J:7th Ed. 1 Name of room Room12 Room13 Room14 Room15 2 Length of exposed wall 25.0 ft 11.0 ft 12.0 ft 13.0 ft 3 Room dimensions 12.0 x 14.0 ft 11.0 x 9.0 ft 7.0 x 9.0 ft 1.0 x 139.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 225 **** **** 99 **** **** 108 **** **** 117 **** **** Exposed b 0 0 111111 **** **** IIIIII **** **** win **** **** min **** **** walls and c 0 0 IIIIII **** **** min **** **** IIIIII **** **** IIIIII **** **** partitions d 0 0 111111 **** **** win **** **** min **** **** IIIIII **** **** e 0 0 111111 **** **** win **** **** nun **** **** IIIIII **** **** f 0 0 IIIIII **** **** !lilt' **** **** nun **** **** IIIIII **** **** 6 Windows and a 3A0 39.7 ** 30 1190 **** 10 397 **** 10 397 **** 30 1190 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 10 **** 190 10 **** 190 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 15 **** 1020 0 **** 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 15 **** 510 0 **** 0 0 **** 0 30 **** 1020 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 195 1053 199 89 481 91 98 529 100 87 470 89 exposed b 0 0 nnn 0 0 111111 0 0 111111 0 0 111111 0 0 walls and c 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 111111 0 0 min 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 111111 0 0 IIIIII 0 0 10 Ceilings a 16G0 2.4 1.1 168 399 188 99 235 111 63 150 71 139 330 156 b 0 0 111111 0 0 min 0 0 nun 0 0 IIIIII 0 0 c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 111111 0 0 IIIIII 0 0 f 0 0 111111 0 0 win 0 0 Him 0 0 min 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note: room b 1910 1.7 0 0 0 0 0 0 0 0 0 0 9 16 0 perimeter c 0 0 111111 0 0 IIIIII 0 0 null 0 0 111111 0 0 is displ. d 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 for slab e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 nun 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 102 8.1 30 3047 242 10 1016 81 10 1016 81 30 3047 242 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 5690 **** **** 2128 **** **** 2091 **** **** 5053 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 358 **** 6% 134 **** 6% 132 **** 6% 318 **** 15 Total loss= 13+14 **** 6048 **** **** 2262 **** **** 7773 **** **** 5371 **** 16 Int.gains: People© 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 2159 **** **** 472 **** **** 441 **** **** 1507 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 106 5% **** 23 5% **** 22 5% **** 74 19 Total RSH gain=(17+18)*PLF 1.00 **** 2265 1.00 **** 496 1.00 **** 463 1.00 **** 1580 20 Air required(cfm) 70 97 26 21 26 20 62 68 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. wr- htsoft- 2019-Mar-1111:24:46 9 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 4 AC ....langeworthy\Documents\York\56 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Right-J®Worksheet Job: 1416 Entire House Date: Mar 11,2019 By: FOOTHILL BUILDERS Plan: 1416 MANUAL J:7th Ed. 1 Name of room Room16 Room17 Room18 Room19 2 Length of exposed wall 17.0 ft 0 ft 0 ft 56.0 ft 3 Room dimensions 1.0 x 70.0 ft 1.0 x 100.0 ft 10.0 x 4.0 ft 22.0 x 12.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 153 **** **** 0 **** **** 0 **** **** 504 **** **** Exposed b 0 0 IIIIII **** **** mill **** **** iiiiii **** **** min **** **** walls and c 0 0 IIIIII **** **** min **** **** iiiiii **** **** IIIIII **** **** partitions d 0 0 IIIIII **** **** iiiiii **** **** iiiiii **** **** Will **** **** e 0 0 111111 **** **** iiiiii **** **** iiiiii **** **** IIIIII **** **** f 0 0 111111 **** **** iiiiii **** **** Him **** **** iiiiii **** **** 6 Windows and a 3A0 39.7 ** 15 595 **** 0 0 **** 0 0 **** 30 1190 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 0 **** 0 0 **** 0 30 **** 2040 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 15 **** 510 0 **** 0 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 1 ODO 33.1 6.3 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 138 745 141 0 0 0 0 0 0 474 2560 483 exposed b 0 0 111111 0 0 IIIIII 0 0 win 0 0 HIM 0 0 walls and c 0 0 111111 0 0 mill 0 0 IIIIII 0 0 HMI 0 0 partitions d 0 0 111111 0 0 IIIIII 0 0 iiiiii 0 0 HMI 0 0 e 0 0 111111 0 0 will 0 0 Him 0 0 HMI 0 0 f 0 0 IIIIII 0 0 iiiiii 0 0 Illlll 0 0 HIM 0 0 10 Ceilings a 16G0 2.4 1.1 70 166 79 100 238 112 40 95 45 264 627 296 b 0 0 IIIIII 0 0 will 0 0 IIIIII 0 0 iiiiii 0 0 c 0 0 IIIIII 0 0 IIIIII 0 0 will 0 0 HMI 0 0 d 0 0 null 0 0 nnu 0 0 Inns 0 0 MI 0 0 e 0 0 111111 0 0 Mill 0 0 iiiiii 0 0 HMI 0 0 f 0 0 111111 0 0 Him 0 0 Him 0 0 IIIIII 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note: room b 1910 1.7 0 0 0 0 0 0 0 0 0 0 264 456 0 perimeter c 0 0 111111 0 0 I I I I I I 0 0 IIIIII 0 0 Mill 0 0 is displ. d 0 0 nun 0 0 Ilan 0 0 IIIIII 0 0 IIIIII 0 0 for slab e 0 0 Illlll 0 0 HIM 0 0 HIM 0 0 HIM 0 0 floors) f 0 0 Illlll 0 0 will 0 0 Inlll 0 0 anti 0 0 12 Infiltration a 102 8.1 15 1524 121 0 0 0 0 0 0 30 3047 242 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 3030 **** **** 238 **** **** 95 **** **** 7880 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 191 **** 6% 15 **** 6% 6 **** 6% 496 **** 15 Total loss= 13+14 **** 3221 **** **** 253 **** **** 101 **** **** 8377 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 850 **** **** 112 **** **** 45 **** **** 3062 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 42 5% **** 5 5% **** 2 5% **** 150 19 Total RSH gain=(17+18)*PLF 1.00 **** 892 1.00 **** 118 1.00 **** 47 1.00 **** 3211 20 Air required(cfm) 37 38 3 5 1 2 96 138 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2019-Mar-11 11:24:46 t wrightSOft' Right-Suite®Universal 2017 17.0.16 RSU25116 Page 5 AC ....langeworthy\Documents\York156 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N :; EXHAUST SYSTEMS TABLE M1507.3.3(1) t,{ CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS V' NUMBER OF BEDROOMS _ DWELLING UNIT k FLOOR AREA 0-1 2_3 4-5 6-7 >7 (square feet) Airflow in GFM " <1,500 30 45 60 75 90 (. 1,501-3,000 45 60 75 90 105 3,001-4,500 j 60 f 75 — 90 105 120 t 4,501-6,000 75 90 - 105 120 135 6,001-7,500 90 105 120 135 150 >7,500 105 120 135 150 165 , For SI: 1 square foot=0.0929 m2,1 cubic foot per minute=0.0004719 m3/s. (i t 4.4-i, ,; TABLE M1507.3.3(2) INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa,b RUN-TIME PERCENTAGE IN EACH 4-HOUR 25% 33% 50% 66°I 75/ s;-;f,± SEGMENT 1 Factor' 4 3 2 1.5 1.3 _!:' a. For ventilation system run time values between those given,the factors are permitted to be determined by interpolation. -,.-1,-,..: b.Extrapolation beyond the table is prohibited. 4 r:; A, TABLE M1507,4 ' M1507.4 Local exhaust rates. Local exhaust systems shall MINIMUM REQUIRED LOCAL EXHAUST RATES'F 4' _ be designed to have the capacity to exhaust the minimum air ONE-AND TWO-FAMILY DWELLINGS fl : flow rate determined in accordance with Table M 1507.4. AREA TO BE;41 , EXHAUST RATES !"° EXHAUSTED q , Kitchens 100 cfm intermittent or 25 cfm co 1 Ac,• '= Bathrooms-Toilet Mechanical exhaust capacity of'$ Rooms intermittent or 20 cfm continuous ;; For SI: I cubic foot per minute=0.0004719 m3/s. yi �,' 1 l ( fi Q`1 ?..i `N 42/3 Q4fo0r 3 = ©cI:P1 )CO, CO S'o% - FRO COY) - 'S 4 a 5.• �:! cS t I , 1 G C 8<i.' k" - . .; �J - '4 Ys E `:e'.:•' '.•.tip_ fl —_ • 2015INTERNATIONQ� ' ' 0 100 ECM !�`($ 4 i` HEAT RECOVERY VENTILATOR .. ENGINEERING DATA LIFEBRERTH THERMALLY CONDUCTIVE,PATENTED DEFROST ALUMINUM CORE Recirculating damper defrost system. The counter-flow heat recovery core transfers heat between the two airstreams.It is easily removed for cleaning or service. CASE Twenty gauge prepainted galvanized steel for superior corrosion resistance.Insulated to MOTORS AND BLOWERS prevent exterior condensation.Drain connections 2-1/2 in.(12 mm)OD.Balancing ports High efficiency electronic commutate ECM motor,for maximum energy savings.Each are located on door. airstream has one centrifugal blower,with multiple fanspeed operations driven by one double shaft motor. ELECTRONICS The DXPL02 control included with the unit can be wall mounted in a central location of FILTERS the home.3 wire 20 gauge(min.)100 ft length(max.). Washable antimicrobial MERV 6 air filters in exhaust and supply airstreams. MOUNTING WARRANTY Four threaded inserts at corners of the cabinet designed to accept the 's' hooks and Units carry a lifetime warranty on the HRV cots and a5year hanging straps supplied with the unit replacement parts warranty. OPTIONAL ACCESSORIES: Tech6rWeather Hood 99-EAG4 Terminator Wireless 20/40/60 99-185 99-EAG4 Fitting Min Timer 99-186 99 FAGS 99-TM4 99-DET02 99-EAG6 lei ,, 99-187 99 EAGB 99-TM5 `_ ' ( 99-TM6 ' 4-- LIFEBREATH CONTROL OPTIONS TIMER OPTIONS FEATURES 99-DXPLO2 99-BCO2 99-BC03 99-BC04 99 OETO3 Lifebreath 20/40/60 Minute Timer Initiates high speed Ventilation for 20,40 or 60 ✓ minutes.3 wire connection. 5 speed fan operation on each mode 99-DET02 2 speed fan operation(Low/High) ✓ ✓ Wireless Lifebreath 20/40/60 Minute Timer Continuous low speed fan operation V Initiates high speed Ventilation for 20,40 or 60 minutes.Wirelessly connects to main control for Humidity control through adjustable Dehumidistat V V V ease of installation.40'approximate range. Excusive to Lifebreath. Large digital LCD screen ✓ 99-RX02-Wireless Lifebreath Repeater LED status indicator lights V V V Extends range of 99-DET02 Wireless Timers.Plugs into 120V power outlet.Wirelessly connects to Continuous Ventilation ✓ ✓ main control and 99-DET02.Install at halfway ✓ ✓ point between timer and main wall control if timer Continuous Recirculation is out of range. 20 ON/40 OFF ✓ s 10 ON/50 OFF 20 ON/40 Recirculation V V ✓ ' 20/40/60 min.High speed override button ✓ 99-DXPLO2 99-DET02 Compatible with 99-DET02 Wireless Timer V ✓ V V a 3 wire connection V V V V LIFEBRERTH Iti Indoor Air Systems 100ECM(9-11-18) www.lifebreath.com 100 ECM • r HEAT RECOVERY VENTILATOR PERFORMANCE (HVI CERTIFIED) a. as LIFEBRERTH Ill I, Oa(25) 0.2(50) 0.3(75) 0.4(100) 0.5(125) 0.6(150) ELECTRICAL SPECIFICATIONS I. IN.W.G.(PA) CFM(L/s) CFM(L/s) CFM(Us) CFM(Lis) CFM(L/s) CFM(Lis) VAC @ 60Hz 120 Net Supply Airflow 161(76) 143(68) 129(61) 114(54) 97(46) 78(37) Watts/Low Speed 40 Gross Supply Airflow 165(78) 147(69) 131(62) 117(55) 102(48) 81(38) Watts/High Speed 115 Gross Exhaust Airflow 229(108) 215(101) 210(99) 203(96) 184(87) 142(67) Amp Rating 1.75 18D WEIGHT: Sensible Effectiveness(ASE) 32°F(0°C) 18% 71 LBS(32 KG) @ 64 CFM(30 Us) 16D Sensible Efficiency(SRE) 32°F(0°C) 71% 140 SHIPPING WEIGHT: @ 64 CFM(30 Us) -. 12D 73 LBS(33 KG) Sensible Efficiency(SRE) 32°F(0°C) 69% 3 100 • @ 95 CFM(45 Us) so NOTE: Sensible Efficiency(SRE) a -13°F(-25°C) 64% 60 Front clearance of 25 in.(635 mm)is @ 68 CFM(32 Us) 4o recommended for servicing unit.All ducts zo use 6 in.(152 mm)round collars.Balancing r1 r r r dampers are located in all air streams. ® e62'1,` 9UO ®k...r ,�T o.1 o.z o.3 0.4 os o.8 o�31OULSu35 CERTIFIED HEMMED Him- Static Pressure(in w.g.) DIMENSIONS FRONT VIEW SIDE VIEW I Filter ir14 3/4 in.(375 Recirculating Illi Defrost !!" __ I I I I Romper — 1 A . Removable iis,APIIII"Nlinii Blower IIIJ Heat 0 Stale air to outside Recovery _ Motor E Core �- 0 Fresh air from outside TV -- — �e Stale air from inside v / y Fresh air to inside I 6 in.(152 mm) I' 33 5/8 in.(854 mm) ' V o v Round Collars I Date: WARRANTY Contractor: Units carry a lifetime warranty Tag: on the HRV core and a 5 year replacement parts warranty. Project. Qty: Supplier: Engineer: Quote#: All units conform to CSA and UL standards I Control: Submitted By: LIFEQRERTH4 •8 Indoor Air Systems Timer: Timer Qty: 100ECM(9-11-18) www.lifebreath.com