Manual S Manual S Compliance Report Job: LOT 1 LENDON p p Date: Mar 13,2019019 Entire House By: FOOTHILL BIULDERS Plan: 1418 C c \ Project Information For: FOOTHILL BIULDERS Cooling Equipment Design Conditions Outdoor design DB: 85.0°F Sensible gain: 18716 Btuh Entering coil DB: 75.3°F Outdoor design WB: 71.0°F Latent gain: 4665 Btuh Entering coil WB: 62.6°F Indoor design DB: 75.0°F Total gain: 23380 Btuh Indoor RH: 50% Estimated airflow: 895 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split AC Manufacturer: York Model: TCHD30S41S3+HD36A3XH1+TM8X060Al2MP11+S1-1TVM4G1 Actual airflow: 933 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load Total capacity: 0 Btuh 0% of load SHR: 0% Heating Equipment Design Conditions Outdoor design DB: -4.0°F Heat loss: 82260 Btuh Entering coil DB: 65.4°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Gas furnace Manufacturer: York Model: TM9X100C16MP11 Actual airflow: 933 cfm Output capacity: 95000 Btuh 115% of load Temp. rise: 50 °F p E © EodEE 0 MAR 13 2019 TOWN OF QUEENSBURY Meets are all requirements of ACCA Manual C BUILDING&CODES 2019-Mar-13 08:48:25 wrightsoft® Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACCN ....langeworthy\Documents\York\14 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Form i Residential Plans Examiner Review Form RPER1 ACCk for HVAC System Design (Loads, Equipment, Ducts) 15Mar09 4 Cmcilionig CcrfralomlArreta QUEENSBURY NY Header Information Contractor: FOOTHILL BIULDERS REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes ❑ No ❑ Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes 0 No ❑ OEM performance data(heating,cooling,blower): Yes ❑ No Building plan#: 1418 Manual D Friction Rate Worksheet: Yes ❑ No ❑ Duct distribution sketch: Yes E No Home address(Street or Lot#,Block,Subdivision): , Entire House HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: -4 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 82260 Btuh Number of bedrooms: 3 Conditioned floor area: 4236 ft2 Summer Design Conditions Number of occupants: 0 Outdoor temperature: 85 °F Indoor temperature: 75 °F Windows Roof Grains difference: 27 gr/Ib q�5O% RH Eave overhang depth: 0 ft Sensible heat gain: 20795 Btuh Internal shade: none Eave Latent heat gain: 5183 Btuh Blinds,drapes,etc. Depth Window Total heat gain: 25978 Btuh Number of skylights: 0 HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Cooling Equipment Data Blower Data Euipment tye: Gas furnace Ec uioment type: Split AC Heating cfm: 933 Furnace,Heatpump,Boiler,etc. it onditioner,Heat pump,etc. Cooling cfm: 933 Model: York Model: York Static pressure: 0 in H2O TM9X100C16MP11 TCHD30S41S3 Fan's rated extemal static pressure for design airflow Heating output capacity:. 95000 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winter design outdoor conditions Sensible cooling capacity: 0 Btuh Aux.heating output capacity: 0 Btuh Latent cooling capacity: 0 Btuh HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601 .1) Design airflow: 933 cfm Longest supply duct: 0 ft Duct Materials Used Equipment design ESP: 0 in H2O Longest return duct: 0 ft Trunk duct: Total device pressure losses: 0 in H2O Total effective length(TEL): 0 ft Available static pressure(ASP): 0 in H2O Friction rate: 0 in/100ft Branch duct: Sheet metal Friction Rate=ASP=(TEL x 10 ) I declare the load calculation,equipment,equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature: Date: Reserved for County,Town Municipality orAuthority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist f-F wrightsoft* Right-Suite®Universal 2017 17.0.16 RSU25116 Project SummaryJob: LOT 14 JOHN CLENDON Entire House Date: Mar 13,2019 By: FOOTHILL BIULDERS Plan: 1418 Pro'ect Information For: FOOTHILL BIULDERS Notes: Desi• n Information Weather: Glens Falls AP, NY, US Winter Design Conditions Summer Design Conditions Outside db -4 °F Outside db 85 °F Inside db 68 °F Inside db 75 °F Design TD 72 °F Design TD 10 °F Daily range M Relative humidity 50 % Moisture difference 27 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 77386 Btuh Structure 17843 Btuh Ducts 4874 Btuh Ducts 873 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 82260 Btuh Use manufacturer's data n Rate/swing multiplier 0.90 Infiltration Equipment sensible load 16844 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4665 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 4236 4236 Equipment latent load 4665 Btuh Volume(ft') 38124 38124 Air changes/hour 0.70 0.40 Equipment total load 21509 Btuh Equiv.AVF (cfm) 445 254 Req. total capacity at 0.70 SHR 2.0 ton Heating Equipment Summary Cooling Equipment Summary Make York Make York Trade YORK Trade HORIZONTAL DISCHARGE Model TM9X100C16MP11 Cond TCHD30S41S3 AHRI ref 2008692 Coil HD36A3XH1+TM8X060Al2MP11+S1-1TVM4G1 AHRI ref 3743063 Efficiency 95.5AFUE Efficiency 12.5 EER, 14 SEER Heating input 100000 Btuh Sensible cooling 19600 Btuh Heating output 95000 Btuh Latent cooling 8400 Btuh Temperature rise 93 °F Total cooling 28000 Btuh Actual air flow 933 cfm Actual air flow 933 cfm Air flow factor 0.011 cfm/Btuh Air flow factor 0.050 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2019-Mar-13 08:48.25 wrightsoft® Right-Suitee Universal 2017 17.0.16 RSU25116 Page 1 ACCN ....langeworthy\Documents\York\14 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Right-J®Worksheet Job: LOT 14 JOHN CLENDON Entire House Date: Mar 13,2019 FOOTHILL BIULDERS Plan: 1418 MANUAL J:7th Ed. 1 Name of room Entire House Room2 Room3 Room4 2 Length of exposed wall 522.0 ft 174.0 ft 174.0 ft 24.0 ft 3 Room dimensions 1.0 x 1412 ft 1.0 x 1412 ft 1.0 x 138.0 ft 4 Ceilings Condit.Option 9.0 ft d 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 4698 **** **** 1566 **** **** 1566 **** **** 216 **** **** Exposed b. 0 0 mu! **** **** IIIIII **** **** 111111 **** **** 111111 **** **** walls and c 0 0 111111 **** **** win **** **** IIIIII **** **** Him **** **** partitions d 0 0 111111 **** **** 111111 **** **** IIIIII **** **** 111111 **** **** e 0 0 111111 **** **** IIIIII **** **** IIIIII **** **** 1 I1111 **** **** f 0 0 111111 **** **** III!!! **** **** 111111 **** **** 111111 **** **** 6 Windows and a 3A0 39.7 ** 155 6149 **** 40 1587 **** 0 0 **** 15 595 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 45 **** 855 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 65 **** 4420 40 **** 2720 0 **** 0 15 **** 1020 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 ***" 0 South 34.0 45 **** 1530 0 **** 0 0 **** 0 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 84 2782 526 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 4459 24079 4548 1526 8240 1557 1566 8456 1597 201 1085 205 exposed b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 walls and c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 will 0 0 IIIIII 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 f 0 0 mill 0 0 111111 0 0 IIIIII 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 2824 6710 3169 0 0 0 1412 3355 1584 138 328 155 b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 c 0 0 IIIIII 0 0 111111 0 0 IIIIII 0 0 111111 0 0 d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 Ilan 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 111111 0 0 lulu 0 0 11 Floors a 1910 1.7 0 1412 2440 0 1412 2440 0 0 0 0 0 0 0 (Note:room b 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 perimeter c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 is displ. d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 IIIIII 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 147 11.7 239 35227 2796 40 5896 468 0 0 0 15 2211 175 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 77386 **** **** 18163 **** **** 11811 **** **** 4219 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 4874 **** 6% 1144 **** 6% 744 **** 6% 266 **** 15 Total loss=13+14 **** 82260 **** **** 19307 **** **** 12555 **** **** 4485 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 17843 **** **** 4744 **** **** 3182 **** **** 1555 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 873 5% **** 232 5% **** 156 5% **** 76 19 Total RSH gain=(17+18)*PLF 1.00 **** 18716 1.00 **** 4976 1.00 **** 3337 1.00 **** 1631 20 Air required(cfm) 933 933 219 248 142 166 51 81 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. .4C A wrugF+ttsoftm 2019-Mar-13 08:48:25 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ...langeworthy\Documents\York\14 JOHN CLENDON.rup Cale=MJ7 Front Door faces: N Right-J®Worksheet Job: LOT 14 JOHN GLENDON Entire House Date: Mar 13,2019 By: FOOTHILL BIULDERS Plan: 1418 MANUAL J:7th Ed. 1 Name of room Room5 Room6 Room7 Room8 2 Length of exposed wall 5.0 ft 34.0 ft 49.0 ft 14.0 ft 3 Room dimensions 9.0 x 5.0 ft 1.0 x 187.0 ft 1.0 x 598.0 ft 14.0 x 12.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 45 **** **** 306 **** **** 441 **** **** 126 **** **** Exposed b 0 0 IIIIII **** **** 111111 **** **** IIIIII **** **** IIIIII **** **** walls and c 0 0 IIIIII **** **** IIIIII **** **** IIIIII **** **** win **** **** partitions d 0 0 111111 **** **** min **** **** IIIIII **** **** IIIIII **** **** e 0 0 111111 **** **** Him **** **** IIIill **** **** 111111 **** **** f 0 0 IIIIII **** **** I III II **** **** urn **** **** 111111 **** **** 6 Windows and a 3A0 39.7 ** 0 0 **** 15 595 **** 45 1785 **** 30 1190 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** d0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 0 **** 0 15 **** 285 30 **** 570 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 South 34.0 0 **** 0 15 **** 510 30 **** 1020 0 **** 0 Horz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 84 2782 526 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 45 243 46 291 1571 297 312 1685 318 96 518 98 exposed b 0 0 nnn 0 0 IIIIII 0 0 null 0 0 null 0 0 walls and c 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 partitions d 0 0 111111 0 0 IIIIII 0 0 111111 0 0 IIIIII 0 0 e 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 IIIIII 0 0 f 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 45 107 50 187 444 210 598 1421 671 168 399 188 b 0 0 111111 0 0 null 0 0 111111 0 0 111111 0 0 C 0 0 111111 0 0 111111 0 0 IIIIII 0 0 111111 0 0 d 0 0 111111 0 0 hull 0 0 will 0 0 111111 0 0 e 0 0 111111 0 0 nun 0 0 null 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 111111 0 0 IIIIII 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 (Note:room b 0 0 111111 0 0 IIIIII 0 0 IIIIII 0 0 111111 0 0 perimeter c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 is displ. d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 111111 0 0 lung 0 0 111111 0 0 111111 0 0 floors) f 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 147 11.7 0 0 0 15 2211 175 129 19014 1509 30 4422 351 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 350 **** **** 4822 **** **** 26686 **** **** 6529 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** **** 0 **** **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** **** 0 **** 14 Duct loss 6% 22 **** 6% 304 **** 6% 1681 **** 6% 411 **** 15 Total loss=13+14 **** 372 **** **** 5125 **** **** 28367 **** **** 6941 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 **** 0 0 **** 0 0 **** 0 17 Subtot RSH gain=7+8..+12+16 **** **** 96 **** **** 1192 **** **** 4329 **** **** 1207 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 **** **** 0 **** **** 0 **** **** 0 Cooling redistribution **** **** 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 5 5% **** 58 5% **** 212 5% **** 59 19 Total RSH gain=(17+18)*PLF 1.00 **** 101 1.00 **** 1250 1.00 **** 4540 1.00 **** 1266 20 Air required(cfm) 4 5 58 62 322 226 79 63 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. �4C P WrigtetSO 2019-Mar-13 08:48:25 Right-Suite®Universal 2017 17.0.16 RSU25116 Page 2 ...langeworthy\Documents\York\14 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N Right-JO Worksheet Job: LOT 14 JOHN CLENDON Entire House Date: Mar 13,2019 FOOTHILL BIULDERS Plan: 1418 MANUAL J:7th Ed. 1 Name of room Room9 Room10 Room11 Room12 2 Length of exposed wall 20.0 ft 18.0 ft 10.0 ft 0 ft 3 Room dimensions 8.0 x 12.0 ft 8.0 x 10.0 ft 10.0 x 3,0 ft 10.0 x 7.0 ft 4 Ceilings Condit.Option 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool 9.0 ft heat/cool TYPE OF CST HTM Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) Area Load(Btuh) EXPOSURE NO. Htg Clg (ft*) Htg Clg (ft2) Htg Clg (ft2) Htg Clg (ft2) Htg Clg 5 Gross a 12E3 5.4 1.0 180 **** **** 162 **** **** 90 **** **** 0 **** **** Exposed b 0 0 111111 **** **** non **** **** IIIIII **** **** IIIIII walls and c 0 0 I!!!!! **** **** IIIIII **** **** min **** **** 111111 **** ******* partitions d 0 0 111111 **** **** 111111 **** **** **** ****111111 111111 **** **** e 0 0 111111 **** **** 111111 **** *** IIIIII 111111 f 0 0 IIIIII **** **** IIIIII **** **** IIIII1 **** **** IIIIII **** **** 6 Windows and a 3A0 39.7 ** 10 397 **** 0 0 **** 0 0 **** 0 0 **** glass doors b 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** **** Heating c 0 ** 0 0 **** 0 0 **** 0 0 0 0 **** d 0 ** 0 0 **** 0 0 **** 0 0 0 0 e 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** f 0 ** 0 0 **** 0 0 **** 0 0 **** 0 0 **** 7 Windows and North 19.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 glass doors NE/NW 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Cooling E/W 68.0 10 **** 680 0 0 0 **** 0 0 **** 0 SE/SW 0 0 **** 0 0 **** 0 0 0 0 * 0 South 34.0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Holz 0 0 **** 0 0 **** 0 0 **** 0 0 **** 0 8 Other doors a 10D0 33.1 6.3 0 0 0 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 Net a 12E3 5.4 1.0 170 918 173 162 875 165 90 486 92 0 0 0 exposed b 0 0 111111 0 0 min 0 0 111111 0 0 111111 0 0 walls and c 0 0 HMI 0 0 111111 0 0 111111 0 0 111111 0 0 partitions d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 f 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 10 Ceilings a 16G0 2.4 1.1 96 228 108 80 190 90 30 71 34 70 166 79 b 0 0 111111 0 0 nun 0 0 111111 0 0 111111 0 0 c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 d 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 e 0 0 min 0 0 111111 0 0 111111 0 0 111111 0 0 f 0 0 !I!!!! 0 0 111111 0 0 111111 0 0 111111 0 0 11 Floors a 1910 1.7 0 0 0 0 0 0 0 0 0 0 0 0 0 111111 111111 111111 0 0 111111 0 0 (Note:room b 0 0 0 0 0 0 perimeter c 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 is displ. d 0 0 min 0 0 111111 0 0 111111 0 0 111111 0 0 for slab e 0 0 111111 0 0 111111 0 0 111111 0 0 111111 0 0 floors) f 0 0 !i!!!! 0 0 111111 0 0 111111 0 0 111111 0 0 12 Infiltration a 147 11.7 10 1474 117 0 0 0 0 0 0 0 0 0 Ventilation 0 0 0 0 0 0 0 0 13 Subtotal loss=6+8..+11+12 **** 3017 **** **** 1065 **** **** 557 **** **** 166 **** Less external heating **** 0 **** **** 0 **** **** 0 **** **** 0 **** Less transfer **** 0 **** **** 0 **** ** 0 **** 0 **** Heating redistribution **** 0 **** **** 0 **** **** 0 **** 0 **** 14 Duct loss 6% 190 **** 6% 67 **** 6% 35 **** 6% 10 15 Total loss= 13+14 **** 3207 **** **** 1132 **** **** 592 **** **** 177 **** 16 Int.gains: People @ 300 0 **** 0 0 **** 0 0 **** 0 0 **** 0 Appl. @ 1200 0 **** 0 0 * 0 0 * 0 0 * 0 17 Subtot RSH gain=7+8..+12+16 **** **** 1078 **** **** 255 **** **** 125 **** **** 79 Less external cooling **** **** 0 **** **** 0 **** **** 0 **** **** 0 Less transfer **** **** 0 * 0 0 0 ** Cooling redistribution 0 **** **** 0 **** **** 0 **** **** 0 18 Duct gain 5% **** 53 5% **** 12 5% **** 6 5% **** 4 19 Total RSH gain=(17+18)*PLF 1.00 **** 1131 1.00 **** 267 1.00 **** 132 1.00 **** 82 20 Air required(cfm) 36 56 13 13 7 7 2 4, Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. Wr1 htsoft° g 2019-Mar-13 08:48:25 9 Ri ht-Suite®Universal 2017 17.0.16 RSU25116 Page 3 A�_A ....langeworthy\Documents\York\14 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N EXHAt1S t b v s a=eue:a 1 ,77((--J+ :_ TABLE M1507.3.3(1) ---,=-:', CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS !4i 9 DWELLING UNIT NVi4SER OF BEDROOMS ` 'l:. FLOOR AREA 0-1 2_3 r 4-5 I 6-7 i >7--- __'- t`'.:l.. (square feet) Airflow in CFM '- <1,500 30 45 60 75 ______9a Jax. 1,501-3,000 45 60 75 90 105 3,001—4,500 60 75 90 105 120 - - 4,501—6,000 75 90 105 120 135 'T 6,001-7,500 90 105 120 135 150 >7,500 105 120 1 135 I50 165 k., For SI: 1 square foot=0.0929 rn,1 cubic foot per minute=0.0004719 mils. F-1 w, TABLE M15a7.3.3(2) 1. i INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORS',b ;Oil?' RUN-TIME PERCENTAGE IN EACH 4-HOUR x`1' SEGMENT 25% 33% 50% 66% 75% 1 "'r,'t`i'% Factor' 4 3 2 1.5 1.3 :3,4. r y a. For ventilation system run time values between those given,the factors are permitted to be determined by interpolation. g-'^4ry-' b.Extrapolation beyond the table is prohibited. i 4:—akr TABLE M1507.4 P i2``:' M1507.4 Loc.! exhaust rates. Local exhaust systems shall MINIMUM REQUIRED LOCAL EXHAUST RATES F be designed to have the capacity to exhaust the minimum air ONE-AND TWO-FAMILY DWELLINGS vs,-2a1 flow rate determined in accordance with Table M1507.4. AREA TO BE EXHAUST RAZES R°F; EXHAUSTED y r r Kitchens 100 cfm intermittent or 25 cfm co' G, . li- '> Bathrooms-Toilet Mechanical exhaust capacity ofl -p, Rooms intermittent or 20 cfm continuo g r .g For SI: 1 cubic foot per minute=0.0004719 m3/s. S"', jl i I, i k FM y 11: t yy,, ��..tzJ��:z Ili i ' 1 c. ;EC _ h T• ' It - _...--_ -- t 2015INTERNATIO0t .- I 95 MAX . .. . HEAT RECOVERY VENTILATOR y ENGINEERING DATA THERMALLY CONDUCTIVE,PATENTED DEFROST ThThe crossIUM-flow heat reecoveerryEcore transfers heat between the two airstreams.It is easily Recirculating damper defrost system. CAFFg�,EiiTH removed for cleaning or service. CASE I Twenty gauge prepainted galvanized steel for superior corrosion resistance.Insulated to MOTORS AND BLOWERS prevent exterior condensation.Drain connections 2-1/2 in.(12 mm)OD.Balancing ports Each airstream has one centrifugal blower driven by a common PSC motor with multiple are located on door. fan speed operations. ELECTRONICS FILTERS The DXPLO2 control included with the unit can be wall mounted in a central location of Washable air filters in exhaust and supply air streams. the home.3 wire 20 gauge(min.)100 ft length(max.). MOUNTING Four threaded inserts at corners of the cabinet designed to accept the"s"hooks and WARRANTY hanging straps supplied with the unit. into carry a lifetime warranty on the HRV core and a 5 year replacement parts warranty. OPTIONAL ACCESSORIES: Dual Hood Weather Hood TechGrille Terminator 99-190 99-185 99-EAG4 99-194 Fitting 99-186 r 99-EAGS 99-TM4 99-187 99-EAG6 t( 99-TMSla - 99-EAGS \: 99-TM6 LIFEBREATH CONTROL OPTIONS TIMER OPTIONS FEATURES 99-DXPLO2 99-BCO2 99-6CO3 99-BCO4 99 DETO3-Lifebreath 20/40/60 Minute Timer Initiates high speed Ventilation for 20,40 or 60 ✓ minutes.3 wire connection. 5 speed fan operation on each mode 99-DET02 2 speed fan operation(Low/High) V '/ Wireless Lifebreath 20/40/60 Minute Timer Continuous low speed fan operation ✓ Initiates high speed Ventilation for 20,40 or 60 minutes.Wirelessly connects to main control for Humidity control through adjustable Dehumidistat ✓ ✓ ✓ ease of installation.40'approximate range. Excusive to Lifebreath. Large digital LCD screen ✓ 99-RX02-Wireless Lifebreath Repeater LED status indicator lights ✓ V V Extends range of 99-DET02 Wireless Timers.Plugs into 120V power outlet.Wirelessly connects to Continuous Ventilation ✓ ✓ main control and 99-DET02.Install at halfway V ✓ point between timer and main wall control if timer Continuous Recirculationis out of range. 20 0N/40 OFF V 0 10 0N/50 OFF ✓ 2t- .7Z 20 ON/40 Recirculation ✓ ✓ ✓ 20/40/60 min.High speed override button ✓ 99 DXPLO2 99 DET02 Compatible with 99-DET02 Wireless Timer ✓ ✓ V V ., 3 wire connection V V V V LIFEBREATH°f III IF Indoor Air Systems 69-9SMAX(01-01-18) www.lifebreath.com .., . , ,, 95 MAX f HEAT RECOVERY VENTILATOR PERFORMANCE (Hill CERTIFIED) 0.1(25) 0.2(SO) 0.3(75) 0.4(100) 0.5(125) ELECTRICAL SPECIFICATIONS IN.NA(PA) [FM IL.s) CFM(Vs) CFM(L s) CFM(L s) CFM(L s) VAC @ 60Ht 120 Net Supply Airflow 68(32) 66(311 64(30) 59(28) 55(26) Watts I Low Speed 59 LIFEBR .,,,ririlJ Gross Supply Airflow 16(36) 12(34) 10 j33) 66(31) 61(29) Watts I High Speed 89 I. Gross Exhaust Airflow 87(41) 85(40) 83(39) 78(37) 16(36) Amp Rating 9 Sensible Effectiveness(ASE) no WEIGHT: @ 60 CFM(28 Us) 32°F(0°C) 88% 70 S2 LEIS(23°6 KG) Sensible Efficiency(SRE) 32°F(0°C) 15% 60 SHIPPING WEIGHT: @ 60 CFM(28 Us) I 4a 30 NOTE: @ 61 CFM(29 Us) -13°F(-25°C) 68°7D Front clearance of 25 in.(635 mm)is 20 recommended for servicing unit.Round duct io connections are 5 in.(127 mm)and oval collars use 6 in.(152 mm)connections. 0.1 0.2 0.3 0.4 0.5 0.6 Is �� �... I@O o CAI Static Pressure(in w.g.) us NV i 9001 .- .;,..::., .....pCERTIFIED IMMURED DIMENSIONS FRONT VIEW TOP VIEW 44 b4 ram„ r=a, 5 in.(127 mm) A A --„\/ Round Collars Stale air to outside Blower I I E /� Fresh air from outside E o Stale air from inside Removable Heat — — `n F I y Fresh air to inside Recovery Core V * ) • N 6 in.(152 mm) Round Collars Condensate Drain 14 181/2 in.(469 mm) Oats: WARRANTY Contractor: Units carry a lifetime warranty Tag: on the HMV r nip and a 5 year replar_nment carts warranty. Project. Qty: Supplier: Quote#: All units conform to CSA and UL standards Engineer: ea Control: Submitted By: LIFEBRERTiHK Ilif Indoor Air Systems Timer: Timer Qty: 69-9SMAX(01-01-18) www.lifebreath.com