Loading...
ResCheck REScheck Software Version 4.6.4 Compliance Certificate Project Foothills Builders Energy Code: 2015 IECC s fa 11 1 Location: Glens Falls, New York r� ° Construction Type: Single-family Project Type: New Construction fL MAR 1 1 2019 Jj Conditioned Floor Area: 1,422 ft2 Glazing Area 12% TOWN Oi -s: oa Climate Zone: 6 (7635 HDD) COMMUI Permit Date: -- - Permit Number: Construction Site: Owner/Agent: Designer/Contractor: Lot 14 John Clendon Danie W. Ryan P.E. Queensbury, NY 12804 206 Glens Street Suite 30 Glens Falls, NY 12801 ornpliance:Passes using UA trade-off Compliance: 1.3%Better Than Code Maximum UA. 232 Your UA: 229 The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules. It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home. Envelope Assemblies Gross Area Cavity Cont. Assembly or R-Value_ R-Value U-Factor UA Perimeter Ceiling 1: Flat Ceiling or Scissor Truss 1,422 38.0 0.0 0.030 43 Wall 1: Wood Frame, 16" o.c. 1,392 21.0 0.0 0.057 69 Window 1: Vinyl/Fiberglass Frame:Double Pane with Low-E 102 0.290 30 Door 1: Solid 18 0.140 3 Door 2: Glass 40 0.290 12 Door 3: Solid 20 0.240 5 Basement Wall 1: Solid Concrete or Masonry 1,531 0.0 19.0 0.039 59 Wall height: 7.8' Depth below grade: 6.8' Insulation depth: 7.8' Window 2: Vinyl/Fiberglass Frame:Double Pane 7 0.450 3 Window 3:Vinyl/Fiberglass Frame:Double Pane with Low-E 16 0.290 5 295.15-2-11 RC-0116-2019 Foothills Builders LLC 65 John Clendon Rd, Lot 14 Single Family 1422 s.f., Gar. 528 s.f. Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\lrobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 1 of10 Clendon\1418 Rescheck.rck Compliance Statement: The proposed building design described here is consistent with the building plans,specifications, and other calculations submitted with the permit application.The proposed b has been designed to meet the 2015 IECC requirements in REScheck Version 4.6.4 and to comply with the mandatory requ men listed in the REScheck Inspection Checklist. a e-Title ignature Da e 5 tL 2 �a 413, ' r 0Essrc. �� Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\Irobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 2 of10 Clendon\1418 Rescheck.rck REScheck Software Version 4.6.4 Inspection Checklist Energy Code: 2015 IECC Requirements: 0.0% were addressed directly in the REScheck software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section Plans Verified Field Verified # Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions & Req.ID 103.1, Construction drawings and � ❑Complies 103.2 documentation demonstrate a ❑Does Not [PR1]1 energy code compliance for the building envelope.Thermal ❑Not Observable envelope represented on ❑Not Applicable construction documents. 103.1, Construction drawings and ❑Complies 103.2, documentation demonstrate ❑Does Not 403.7 energy code compliance for [PR3]1 lighting and mechanical systems. ❑Not Observable 14, Systems serving multiple ❑Not Applicable dwelling units must demonstrate r",,e compliance with the IECC Commercial Provisions. ' �" 302,1, Heating and cooling equipment is Heating: Heating: ❑Complies 403.7 sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not [PR212 on loads calculated per ACCA Cooling: Cooling: Manual J or other methods ❑Not Observableppab approved by the code official. Btu/hr Btu/hr ;❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) 3 1Low Impact(Tier 3) Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\Irobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 3 of10 Clendon\1418 Rescheck.rck Section Foundation Inspection Plans Verified Field Verified Co' »plies? Comments/Assumptions fl& Req.I Value Value 402.1.1 Conditioned basement wall R- R- EComplies See the Envelope Assemblies [FO4]1 insulation R-value.Where interior R_ R- ❑Does Not table for values. insulation is used, verification _ may need to occur during ❑Not Observable Insulation Inspection. Not ❑Not Applicable required in warm-humid locations in Climate Zone 3. 303.2 Conditioned basement wall ❑Complies [FO5]1 insulation installed per EDoes Not manufacturer's instructions. E4, ['Not Observable ❑Not Applicable 402.2.9 Conditioned basement wall ft ft ;❑Complies See the Envelope Assemblies (FO6]1 insulation depth of burial or ❑Does Not table for values. distance from top of wall. ❑Not Observable ❑Not Applicable 303.2.1 A protective covering is installed = ''' ' --❑Complies [F01l]2 to protect exposed exterior ❑Does Not AA' insulation and extends a [Not Observable minimum of 6 in. below grade. ENot Applicable 403.9 Snow-and ice-melting system ' ❑Complies [F01212 controls installed. x ❑Does Not t,1°!"❑Not Observable ti:3 ❑Not Applicable Additional Comments/Assumptions: 0 High Impact(Tier 1) ©Medium Impact(Tier 2) ©Low Impact(Tier 3) Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\lrobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 4 of10 Glendon\1418 Rescheck.rck Section Plans Verified Fieid Verified # Framing!Rough-in InspectionValue Value Complies? 1 Comments/Assumptions & Req.i� 402.1.1, Door U-factor. , U- U ❑Complies See the Envelope Assemblies 402.3.4 ❑Does Not table for values. [FR1]1 t ❑Not Observable ENot Applicable 402.1.1, Glazing U factor(area-weighted U U- ❑Complies See the Envelope Assemblies 402.3.1, average). ❑Does Not table for values. 402.3.3, 402.3.6, ❑Not Observable 402.5 ❑Not Applicable [FR2]i 303.1.3 U factors of fenestration products i' ❑Complies [FR4]i are determined in accordance fib, t = ❑Does Not with the NFRC test procedure or ��� yap i(i�' taken from the default table. ❑Not Observable �zp ❑Not Applicable 402.4.1.1 mm Air barrier and thermal barrier ❑Complies [FR23]i installed per manufacturer's �)� -= ❑Does Not instructions. aiir' V � rlwG , ,� = ❑Not Observable ❑Not Applicable 402.4.3 Fenestration that is not site built i' ❑Coe lies [FR20]i is listed and labeled as meeting ���d"'� ` �;�i,��� rr1 ❑Does Not AAMA/WDMA/GSA 101/l.5.2/A440 � ,i1 °` : ' or has infiltration rates per NFRC ���r ❑Not Observable 400 that do not exceed code � �� (� 07 �1 �,. ❑Not Applicable :limits. r1��l�it`,l"� 402,4.5 IC-rated recessed li htin fixtures ,'' °�?_°m . , ~._ g g ?❑Complies [FR16]2 sealed at housing/interior finish . 7. ❑Does Not and labeled to indicate <_2.0 cfm `' '` _ �'��:��� leakage at 75 Pa. '` ^° �1 '❑Not Observable -b, ❑Not Applicable 403.2.1 Supply and return ducts in attics ❑Complies [FR12]� insulated >= R 8 where duct is �' �❑Does Not >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and ❑Not Observable return ducts in other portions of ;,, ❑Not Applicable the building insulated >= R-6 for diameter>= 3 inches and R 4.2 for<. 3 inches in diameter. 409.3.3.5 Buildng cavities are not used as ��:„., } A����i, d' ❑Complies [FR15h ducts or plenums. �, � ���M:]'� ,y F❑Does Not ����� �l � � ���u ❑Not Observable � � ������ ❑Not Applicable 403.4 HVAC piping conveying fluids R- R- ❑Complies [FR17)z above 105 °F or chilled fluids ❑Does Not below 55 °F are insulated to __R- *' ❑Not Observable ', 3. ENot Applicable 403.4.1 Protection of insulation on HVAC a�` �4�fi' :.� ❑Complies [FR24]i piping. ' �,7�a, . a try N� ;a,'�6� ❑DoesNot Ai Observable ❑Not Applicable 403.5.3 Hot water pipes are insulated to R- R- ❑Complies [FRli3) >_R-3. '❑Does Not [Not Observable j❑Not Applicable 403,E Automatic or gravity dampers are u�_���' ❑Complies [FR19)� installed on all outdoor air y ❑Does Not intakes and exhausts. i ' �t� � W ;,_,:❑Not Observable i; tir-; s_ �! (❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\Irobision\Dropbox\DWRPE Engineering\Active Projects\1418 FHB Lot 14 John Page 5 of10 Glendon\1418 Rescheck.rck Section > Plans verified Field Verified P p Insulation Inspection Com lies? CommentsfAssurn bons & Req.ipValue Value 303.1 All; installed insulation is labeledi. ❑Complies [IN13)2 or the installed R-values �a r ,ODoes Not provided. �1 ❑Not Observable ❑Not Applicable 402.1.1, Wall insulation R-value. If this is a R- R- EComplies See the Envelope Assemblies 402.2.5, mass wall with at least 1/2 of the ❑ Wood Wood ❑Does Not table for values. 402.2.6 wall insulation on the wall Mass ❑ Mass ❑Not Observable [IN3]1 exterior,the exterior insulation requirement applies(FR10). ❑ Steel ❑ Steel ❑Not Applicable 303.2 Wall insulation is installed per �� ❑Complies [IN4]1 manufacturer's instructions. �, 7 ❑Does Not a " ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\lrobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 7 of10 Clendon\1418 Rescheck.rck Section Plans Verified Field Versified # Final Inspection Provisions Value Value Complies? CommentslAssumptions & Req,ID� 402.1.1, Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies 402.2.1, ❑ Wood ❑ Wood ❑Does Not table for values. 402.2.2, III Steel ❑ Steel ❑Not Observable 402.2.6 [F11]1 ❑Not Applicable 303.1.1.1,;Ceiling insulation installed per ,i ❑Complies 303.2 manufacturer's instructions. R 44 1;i ❑Does Not [F12]1 Blown insulation marked every }ids z ��r � � - 1 `*P Not Observable 300 ft . rj � �� ❑Not Applicable 402.2.3 Vented attics with air ermeable 4ia4 ❑Complies p i F �o-4"�i'�CG? � %, �j�. [F122]2 insulation include baffle adjacent 4� < 1) 'm�p�dr„ ; ❑Does Not to soffit and eave vents that ,; extends over insulation. ❑Not Observable �a, N,,.. h01. sti,"a❑Not Applicable 402.2.4 Attic access hatch and door R- R- ❑Complies [F13]1 insulation >_R-value of the ❑Does Not adjacent assembly. ❑Not Observable ❑Not Applicable 402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = ❑Complies [F117]1 ach in Climate Zones 1-2, and ❑Does Not <=3 ach in Climate Zones 3-8. ['Not Observable ❑Not Applicable ft2 ❑ 403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 ❑Complies [F14]1 cfm/100 ft2 across the system or . ft2 Does Not <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in ❑Not Observable tests,verification may need to ❑Not Applicable occur during Framing Inspection. 403.3.2 ,Ducts are pressure tested to cfm/100 cfm/100 ❑Complies [FI27]1 determine air leakage with ft2 ft2 ❑Does Not either: Rough-in test:Total leakage measured with a Not Observable pressure differential of 0.1 inch ❑Not Applicable w.g. across the system including the manufacturer's air handler enclosure if installed at time of test. Postconstruction test:Total :leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer's air handler enclosure. 403.3.2.1 Air handler leakage designated ❑Complies [F124]1 by manufacturer at <=2%of ��' a,4 ❑Does Not design air flow. 4 +� iok��;❑Not Observable "r°❑Not Applicable 403.1.1 Programmable thermostats y❑Complies [Fi9]2 installed for control of primary . "� ❑Does Not heating and cooling systems and �,, _-- initially set by manufacturer to Not Observable °" ❑Not Applicable :code specifications. ,�� -4 403�1.2 Heat pump thermostat installed �i�litm ose.z� ��= ❑Complies [Fib ]2 on heat pumps. ❑Does Not 9 �•�s❑Not Observable �4 ❑Not Applicable 403.5.1 Circulating service hot water ❑Complies [FI11]2 systems have automatic or. ��;,� 1s i. ❑Does Not accessible manual controls. "' i�" � � ❑Not Observable 04v- ❑Not Applicable ©Low Impact(Tier 3) ElHigh Impact(Tier 1) ®Medium Impact(Tier 2) Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\Irobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 8 of10 Clendon\1418 Rescheck.rck • Section Plans Vert Field Verified # Final Mspection Provisions Value Value Complies? Comm & Req.lD 403.6.1 All mechanical ventilation system ". ❑Complies (F(25] fans not part of tested and listed ' ❑Does Not HVAC equipment meet efficacy and air flow limits. a ENot Observable _ ON Applicable 403.2 Hot water boilers supplying heat ' Complies EFI26]� through one or two-pipe heating �, _ ❑Does Not systems have outdoor setback %" ";:il, f control to lower boiler water ;) . v❑Not Observable temperature based on outdoor �i ❑Not Applicable tem erature. '.°` "Ii.r 4035,1.1 :Heated water circulation systems ❑Complies [Fl28J� have a circulation pump.The ��` r ['Does Not system return pipe is a dedicated return pipe or a cold water supply ❑Not Observable pipe. Gravity and thermos ❑Not Applicable syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop t is at set-point temperature and " no demand for hot water exists s � _ 4a� .2v,a�. ; 403.5.1,2 Electric heat trace systems (Fl29]� comply with IEEE 515.1 or UL ❑Does Not 515. Controls automatically " �'� adjust the energy input to the e� "� �., �, F❑Not Observable heat tracing to maintain the .i ° d tip= `❑Not Applicable desired water temperature in the : ' !, piping. }* 403.5.2 Water distribution systems that �� �" ,� ei❑Complies (FI303� have recirculation pumps that ..!hfl,!.c . h N a,.;a`= ❑Does Not pump water from a heated water �'h��'� �� ;;" r � .q supply pipe back to the heated ❑Not Observable ' water source through a cold 'a,„, ,," ❑Not Applicable water supply pipe have a demand recirculation water �� system. Pumps have controls �� sP"�b'� that manage operation of the pump and limit the temperature 4 of the water entering the cold water piping to 104°F' 403,5.4 Drain water heat recovery units1(p _ " r � ❑Complies [E131] tested in accordance with CSA "� 4,@ a ;.�-❑Does Not B55.1. Potable water-side 'r pressure loss of drain water heat ❑Not Observable recovery units < 3 psi for ❑Not Applicable individual units connected to one or two showers. Potable water- side pressure loss of drain water ` heat recovery units < 2 psi for individual units connected to ,)i' three or more showers. ,. , 404.1 75%0 of lamps in permanents �' <❑Complies [Fl6]� fixtures or 75%of permanent ❑Does Not fixtures have high efficacy lamps. Does not apply to low-voltage ,iaµ `,,� .. `❑Not Observable lighting. ,,, ❑Not Applicable 404.1.1 Fuel gas lighting systems have �; ia ❑Complies [Fl23]3 no continuous pilot light. -T� <❑Does Not "kl,� 4r 4a �, ❑Not Observable �� "=' � y. ❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Foothills Builders. Report date: 03/03/19 Data filename: C:\Users\Irobison\Dropbox\DWRPE Engineering\Active Projects\1418 FHB Lot 14.10h n Page 9 of 10 Clendon\1418 Rescheck.rck Section Plans Verified Field Verified Final Inspection Provisions Value Value Complies? Comments/Assumptions &Req.l0 401.3 Compliance certificate posted. ❑Complies [F17]2 ❑Does Not ENot Observable ❑Not Applicable 303.3 Manufacturer manuals for ❑Complies [F118]3 mechanical and water heating " ;" ❑Does Not systems have been provided. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: r1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) , Project Title: Foothills Builders Report date: 03/03/19 Data filename: C:\Users\lrobision\Dropbox\DWRPE Engineering\Active Projects\1418 - FHB - Lot 14 John Page 10 of10 Clendon\1418 Rescheck.rck 2015 IECC Energy j, Efficiency Certificate Insulation Rating R-Value Above-Grade Wall 21.00 Below-Grade Wall 19.00 Floor 0.00 Ceiling / Roof 38.00 Ductwork (unconditioned spaces): Glass&Door Rating U-Factor SHGC Window 0.29 Door 0.29 Heating&Cooling Equipment Efficiency Heating System: Cooling System: Water Heater: k..rr Name: Date: Comments