ComCheck T
COMcheck Software Version 4.1.1.0
Envelope Compliance Certificate
Project Information FILE COPY
Energy Code: 2015 IECC
Project Title: West Glens Falls-WGFB-374
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: New Construction -_-..
Vertical Glazing/Wall Area: 12% ��, N 3v, j�,
a
Construction Site: Owner/Agent: Desigher/Con(ractor
221 Corinth Road Stewart's Shops Corp. St vart s 5hR,f, Comic] ' c ,
Queensbury, NY 12804 ti % ". in.t
its
Additional Efficiency Package(s) `'!,_ .. :4,4 4 )Is1
` "IReduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance catcto9s. g3 ,
Building Area Floor Area 8ff/'t` ,7. > ',� ` ,:
1-Retail : Nonresidential 4979
Envelope Assemblies
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factorial
Perimeter
Roof 1:Attic Roof with Wood Joists,[Bldg.Use 1 -Retail] 4979 49.0 0.0 0.021 0.021
Floor 1:Slab-On-Grade:Unheated,Vertical 4 ft.,[Bldg.Use 1 - 296 --- 10.0 0.480 0.540
Retail](c)
NORTH
Exterior Wall 1:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Retail] 1083 21.0 6.0 0.043 0.051
Window 1:Metal Frame with Thermal Break:Fixed,Perf.Specs.: 216 --- --- 0.360 0.360
Product ID na,SHGC 0.40,[Bldg.Use 1 -Retail](b)
Door 2:Glass(>50%glazing):Metal Frame,Entrance Door, Perf. 57 --- --- 0.360 0.770
Specs.:Product ID na,SHGC 0.40,[Bldg.Use 1 -Retail](b)
Door 3:Glass(>50%glazing):Metal Frame,Entrance Door,Perf. 57 --- --- 0.360 0.770
Specs.:Product ID na,SHGC 0.40,[Bldg. Use 1 -Retail](b)
EAST
Exterior Wall 3:Wood-Framed, 16"o.c.,[Bldg. Use 1 -Retail] 573 21.0 6.0 0.043 0.051
SOUTH
Exterior Wall 2:Wood-Framed, 16"o.c.,[Bldg. Use 1 -Retail] 1083 21.0 6.0 0.043 0.051
Door 1:Insulated Metal,Swinging,[Bldg.Use 1 -Retail] 21 --- --- 0.370 0.370
Door 4:Insulated Metal,Swinging,[Bldg.Use 1 -Retail] 21 --- --- 0.370 0.370
WEST
Exterior Wall 4:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Retail] 573 21.0 6.0 0.043 0.051
Window 2:Metal Frame with Thermal Break:Fixed,Perf.Specs.: 41 --- --- 0.360 0.360
Product ID na,SHGC 0.40,[Bldg.Use 1 -Retail](b)
Window 3:Metal Frame with Thermal Break:Fixed,Perf.Specs.: 41 --- --- 0.360 0.360
Product ID na,SHGC 0.40,[Bldg.Use 1 -Retail](b)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 1 of 18
Perm its\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
f i =
(a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope PASSES: Design 14% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed envelope systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist. ��
``�� 9
Name-Title Signature Date
/��of NEN/r
./ �0W IN irixqlS
co
rn
2N - C�
tad 09100 ee
A°PESSIO1.0/
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 2 of 18
Permits\374 WEST GLENS FALLS- Building Permit\374-COMCHECK.cck
{
COMcheck Software Version 4.1.1.0
11 Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC FILE COPYJ
Project Title: West Glens Falls-WGFB-374
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
221 Corinth Road Stewart's Shops Corp. Stewart's Shops Corp.
Queensbury, NY 12804
Additional Efficiency Package(s)
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Retail 4979 1.13 5646
Total Allowed Watts= 5646
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-Retail
LED 1:show room:LED Panel 40W: 2 62 39 2418
LED 2:4'strip/wrap:LED Other Fixture Unit 40W: 1 18 42 756
Total Proposed Watts= 3174
Interior Lighting PASSES: Design 44% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
fiCiL (.737;Y
Name-Title Signature Date
,c pF NEW y `� i��
MAP �pW IN kT �'Q
ey
5 kill_Ng" 73 IT ..,„tr? 0
lit W-1
�$ S. - asi`*�s15- . .,
°91096 ' Ia
44,
" s pr't •
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 3 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
•
1 • '
COMcheck Software Version 4.1.1.0
\/(1 rflr
Mechanical Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: West Glens Falls-WGFB-374
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
221 Corinth Road Stewart's Shops Corp. Stewart's Shops Corp.
Queensbury, NY 12804
Additional Efficiency Package(s)
Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations.
Mechanical Systems List
Quantity System Type&Description
1 HVAC System 1 (Single Zone):
Heating:2 each-Central Furnace,Electric,Capacity=5 kBtu/h
No minimum efficiency requirement applies
Cooling:2 each-Single Package Vertical AC Unit,Capacity=5 kBtu/h,Air-Cooled Condenser,Air Economizer
Proposed Efficiency=65.00 EER,Required Efficiency: 9.00 EER
Fan System: None
2 Water Heater 1:
Electric Storage Water Heater,Capacity:40 gallons
Proposed Efficiency:0.95 SL,%/h(if>12 kW),Required Efficiency:0.98 SL,%/h(if> 12 kW)
1 Water Heater 2:
Electric Storage Water Heater,Capacity:4 gallons
Proposed Efficiency:0.98 SL,%/h(if> 12 kW),Required Efficiency:7.05 SL,%/h(if>12 kW)
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in thet Inspection Checklist. �q
C; Li - 1� 1 TGr1.J � r , c/'f/!/
Name-Title Signature Date /
G�OFN�h� - 0
z 314 w
,h .gyp 'y,� z
rl
Ill 1-€."`‘ ,e. s'A4', u r.- '
n 0 !t04614,11 Xi M -as y f f-,
v41)A 91p9
r .
, 14 Ii, /40"*: t N „,L �
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 4 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
COMcheck Software Version 4.1.1.0
Inspection Checklist
Energy Code: 2015 IECC
IPA
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
&Req.ID
C103.2 Plans and/or specifications provide all ❑Complies 'Requirement will be met.
[PR1]i information with which compliance ❑Does Not
can be determined for the building
envelope and document where Not Observable
exceptions to the standard are ❑Not Applicable j
claimed.
C103.2 Plans, specifications,and/or ❑Complies Requirement will be met.
[PR2]i calculations provide all information ❑Does Not
with which compliance can be
determined for the mechanical ['Not Observable
systems and equipment and ENot Applicable
document where exceptions to the
'standard are claimed. Load
calculations per acceptable
engineering standards and
;handbooks.
C103.2 'Plans, specifications, and/or '❑Complies Requirement will be met.
[PR3]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the service water ['Not Observable
heating systems and equipment and ❑Not Applicable
document where exceptions to the
'standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C103.2 Plans, specifications, and/or i❑Complies ;Requirement will be met.
[PR4]i calculations provide all information ,❑Does Not
;with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
'the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
i
C402.4.1 ;The vertical fenestration area <= 30 '❑Complies 'Requirement will be met.
[PR10]1 percent of the gross above-grade wall ;❑Does Not
area.
❑Not Observable
❑Not Applicable
C402.4.1 The skylight area <= 3 percent of the ❑Complies Requirement will be met.
[PR11]1 gross roof area. ❑Does Not
['Not Observable
❑Not Applicable
C406 Plans, specifications,and/or ❑Complies Requirement will be met.
[PR9]' calculations provide all information 1DDoes Not
with which compliance can be
determined for the additional energy Not Observable
efficiency package options. Observable__,
Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 5 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
1 ' '
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 6 of 18
Permits\374 WEST GLENS FALLS- Building Permit\374-COMCHECK.cck
Section
Footing/Foundation Inspection Complies? Comments/Assumptions
& Req,ID
C303.2 Slab edge insulation installed per Complies Requirement will be met.
[FO4]2 manufacturer's instructions. ❑Does Not
❑Not Observable
❑Not Applicable
•
C303.2.1 Exterior insulation protected against ❑Complies Requirement will be met.
[FO6]1 damage, sunlight, moisture,wind, ❑Does Not
landscaping and equipment
maintenance activities. Not Observable
j❑Not Applicable
C402.2.5 Slab edge insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[FO3]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 Radiant heating systems panels ❑Complies Exception: Requirement does not apply.
[FO12]3 insulated to>=R-3.5 on face opposite ❑Does Not
space being heated. See the Envelope Assemblies table for values.
['Not Observable
❑Not Applicable
C403.2.4. Snow/ice melting system sensors for Complies Requirement will be met.
5, future connection to controls. Freeze EDoes Not
C403.2.4. protection systems have automatic
6 controls installed. ❑Not Observable
[FO9]3 ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 7 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Framing/Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C303.1.3 ;Fenestration products rated in ❑Complies ;Requirement will be met.
[FR12]2 accordance with NFRC. ❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3 ;Fenestration products are certified as EComplies Requirement will be met.
[FR13I1 :to performance labels or certificates ❑Does Not
provided.
❑Not Observable
❑Not Applicable
C402.4.3 Vertical fenestration SHGC value. ❑Complies ;See the Envelope Assemblies table for values.
[FR10]1 ❑Does Not
I❑Not Observable
❑Not Applicable
C402.4.3, ;Vertical fenestration U-Factor. ;❑Complies See the Envelope Assemblies table for values.
C402.4.3. ❑Does Not
4
[FR8]1 ;❑Not Observable
❑Not Applicable
C402.4.4 ;U-factor of opaque doors associated ❑Complies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ;❑Does Not
meets requirements.
❑Not Observable
❑Not Applicable
C402.5.7 Vestibules are installed on all building ❑Complies Requirement will be met.
[FR17]3 entrances. Doors have self-closing ❑Does Not
devices.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 8 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C404.5, 'Heated water supply piping conforms ❑Complies Exception: Requirement does not apply.
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details.
[PL613 ['Not Observable
❑Not Applicable
C404.5, Heated water supply piping conforms ❑Complies ;Requirement will be met.
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 =requirements. Refer to section details.
[PL6]3 Not Observable
❑Not Applicable
C404.5, ;Heated water supply piping conforms ❑Complies ;Requirement will be met.
C404.5.1, 'to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details.
[PL6]3 ['Not Observable
❑Not Applicable
C404.6.3 :Pumps that circulate water between a ❑Complies =Exception: Requirement does not apply.
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating Not Observable
cycle. ❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies Exception: Requirement does not apply.
[PL713 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating Not Observable
cycle. .❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies Exception: Requirement does not apply.
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to •
<= 5 minutes after end of heating Not Observable
cycle. ❑Not Applicable
C404.7 Water distribution system that pumps ❑Complies Exception: Requirement does not apply.
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source
through a cold-water supply pipe is a Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
C404.7 Water distribution system that pumps ;❑Complies Exception: Requirement does not apply.
[PL8]3 water from a heated-water supply I❑Does Not
pipe back to the heated-water source
through a cold-water supply pipe is a Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F. •
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 9 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
# Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C404.7 ;Water distribution system that pumps ❑Complies Exception: Requirement does not apply.
[PL8]3 I water from a heated-water supply '❑Does Not
pipe back to the heated-water source
;through a cold-water supply pipe is a ❑Not Observable
demand recirculation water system. ;❑Not Applicable
Pumps within this system have
controls that start the pump upon
'receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
;104°F.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 10 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
•
Section
Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req ID
C402.2.6 ;Thermally ineffective panel surfaces of ❑Complies 'Exception: Requirement does not apply.
[ME41]3 ;sensible heating panels have ❑Does Not
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
C402.5.5, Stair and elevator shaft vents have ❑Complies :Exception: Requirement does not apply.
C403.2.4. motorized dampers that automatically ❑Does Not
3 ;close.
[ME3]3 ❑Not Observable
❑Not Applicable
C402.5.5, Outdoor air and exhaust systems have ❑Complies Exception: Gravity dampers acceptable for exhaust and relief
C403.2.4. motorized dampers that automatically ❑Does Not dampers.
3 shut when not in use and meet
[ME58]3 maximum leakage rates. Check ❑Not Observable
gravity dampers where allowed. ❑Not Applicable
C403.2.12 HVAC fan systems at design ❑Complies Exception: Requirement does not apply.
.1 conditions do not exceed allowable ❑Does Not
[ME65]3 fan system motor nameplate hp or fan ❑Not Observable See the Mechanical Systems list for values.
system bhp.
❑Not Applicable
C403.2.12 Fans have efficiency grade(FEG) >= ❑Complies Exception: Fans integral to equipment listed under Section
.3 67.The total efficiency of the fan at ❑Does Not C403.2.3.
[ME117]2 the design point of operation <= 15%
of maximum total efficiency of the ENot Observable
fan. ❑Not Applicable
C403.2.13 Unenclosed spaces that are heated EComplies Exception: Requirement does not apply.
[ME71]2 use only radiant heat. ❑Does Not
❑Not Observable
❑Not Applicable
C403.2.3 HVAC equipment efficiency verified. ❑Complies 'See the Mechanical Systems list for values.
[ME55]2 ❑Does Not
['Not Observable
❑Not Applicable
C403.2.6. Demand control ventilation provided ❑Complies ;Requirement will be met.
1 for spaces>500 ft2 and >25 ❑Does Not
[ME59]1 people/1000 ft2 occupant density and
served by systems with air side Not Observable
economizer, auto modulating outside ❑Not Applicable
air damper control, or design airflow
>3,000 cfm.
C403.2.6. Enclosed parking garage ventilation ❑Complies Exception: Requirement does not apply.
2 has automatic contaminant detection ❑Does Not
[ME115]3 and capacity to stage or modulate
fans to 50%or less of design capacity. ❑Not Observable
❑Not Applicable
C403.2.7 Exhaust air energy recovery on ❑Complies Exception: Requirement does not apply.
[ME57]i systems meeting Table C403.2.7(1) ❑Does Not
and C403.2.7(2). ❑Not Observable
❑Not Applicable
C403.2.8 Kitchen exhaust systems comply with ❑Complies Exception: Requirement does not apply.
[ME11613 replacement air and conditioned ❑Does Not
supply air limitations, and satisfy hood
rating requirements and maximum Not Observable
exhaust rate criteria. ;❑Not Applicable
C403,2.9 HVAC ducts and plenums insulated. ❑Complies Requirement will be met.
[ME60]2 Where ducts or plenums are installed ❑Does Not
in or under a slab,verification may
need to occur during Foundation ['Not Observable
Inspection. ❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 11 of 18
Permits\374 WEST GLENS FALLS- Building Permit\374-COMCHECK.cck
•
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req,ID
C403.2.9 Ducts and plenums sealed based on ❑Complies Requirement will be met.
[ME10]z static pressure and location. '❑Does Not
DNot Observable
Not Applicable
C403.2.9. :Ductwork operating >3 in. water ;❑Complies Exception: Requirement does not apply.
1.3 'column requires air leakage testing. ❑Does Not
[ME11]3 ❑Not Observable
❑Not Applicable
C403.4.4. ;Multiple zone VAV systems with DDC '❑Complies ;Exception: Requirement does not apply.
6 of individual zone boxes have static ❑Does Not
[ME110]3 pressure setpoint reset controls. See the Mechanical Systems list for values.
['Not Observable
❑Not Applicable
C408.2.2. ;Air outlets and zone terminal devices '❑Complies Exception: Requirement does not apply.
1 :have means for air balancing. DDoes Not
[ME53]3 Not Observable
❑Not Applicable
C403.5, I Refrigerated display cases, walk-in 'DComplies Requirement will be met.
C403.5.1, !coolers or walk-in freezers served by ;❑Does Not
C403.5.2 ;remote compressors and remote
[ME123]3 :condensers not located in a DNot Observable
condensing unit, have fan-powered ❑Not Applicable
condensers that comply with Sections
C403.5.1 and refrigeration compressor'
systems that comply with C403.5.2..
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 12 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req ID
C405.2.1 Lighting controls installed to uniformly Complies Requirement will be met.
[EL15]' reduce the lighting load by at least ❑Does Not
50%. ❑Not Observable
;❑Not Applicable
C405.2.1 Occupancy sensors installed in ❑Complies Requirement will be met.
[EL18]1 required spaces. ❑Does Not
❑Not Observable
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies Requirement will be met.
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and •
[EL23]2 visible to occupants. ENot Observable
❑Not Applicable
C405.2.2. ;Automatic controls to shut off all ❑Complies Requirement will be met.
1 !building lighting installed in all ❑Does Not
[EL22]2 buildings.
['Not Observable
❑Not Applicable
C405.2.3 Daylight zones provided with ;❑Complies Requirement will be met.
[EL16]2 I individual controls that control the ❑Does Not
lights independent of general area
;lighting. ❑Not Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are ❑Complies ;Exception: Requirement does not apply.
C405.2.3. equipped with required lighting ❑Does Not
1, controls.
C405.2.3. ['Not Observable
2 ❑Not Applicable
[EL20]1
C405.2.3, Enclosed spaces with daylight area ❑Complies Exception: Requirement does not apply.
C405.2.3. under skylights and rooftop monitors EDoes Not
1, are equipped with required lighting
C405.2.3. controls. Not Observable
3 ❑Not Applicable
[EL21]1
C405.2.4 Separate lighting control devices for EComplies Requirement will be met.
[EL411 specific uses installed per approved ❑Does Not
lighting plans.
['Not Observable
❑Not Applicable
C405.2.4 Additional interior lighting power ❑Complies Requirement will be met.
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and [Not Observable
separated from general lighting. ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per ElComplies Requirement will be met.
[EL6]'- face. ❑Does Not
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 13 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Insulation Inspection Complies? Comments/Assumptions
& Req.ID
C303.1 Roof insulation installed per ❑Complies Requirement will be met.
[IN3]1 manufacturer's instructions. Blown or ❑Does Not
poured loose-fill insulation is installed
only where the roof slope is<=3 in Not Observable
12. ❑Not Applicable
C303.1 'Building envelope insulation is labeled ❑Complies Requirement will be met.
[IN10]2 with R-value or insulation certificate ❑Does Not
providing R-value and other relevant
data. :Not Observable
❑Not Applicable
C303.2 Above-grade wall insulation installed ❑Complies Requirement will be met.
[IN7]1 per manufacturer's instructions. ❑Does Not
['Not Observable
❑Not Applicable
C303.2.1 Exterior insulation is protected from ❑Complies ;Requirement will be met.
[IN14]2 damage with a protective material. ❑Does Not
Verification for exposed foundation
insulation may need to occur during ❑Not Observable
Foundation Inspection. ❑Not Applicable
C402.2.1 ;Insulation intended to meet the roof ❑Complies Requirement will be met.
[IN17]3 insulation requirements cannot be ❑Does Not
installed on top of a suspended
ceiling. Mark this requirement Not Observable
compliant if insulation is installed ❑Not Applicable
accordingly.
C402.2.3 Above-grade wall insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN6]1 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.5 Floor insulation R-value. ❑Complies See the Envelope Assemblies table for values.
[IN8]2 ❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6 ;Radiant panels and associated ❑Complies !Exception: Requirement does not apply.
[IN18]3 components, designed for heat DDoes Not
;transfer from the panel surfaces to the
occupants or indoor space are ['Not Observable
insulated with a minimum of R-3.5. ❑Not Applicable
C402.2.2 Roof R-value. For some ceiling ;❑Complies See the Envelope Assemblies table for values.
[IN2]1 systems,verification may need to ;❑Does Not
occur during Framing Inspection.
['Not Observable
❑Not Applicable
C402.5.1. All sources of air leakage in the ❑Complies Requirement will be met.
1 building thermal envelope are sealed, Does Not
[IN1]1 caulked,gasketed,weather stripped
or wrapped with moisture vapor- ['Not Observable
permeable wrapping material to ❑Not Applicable
minimize air leakage.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 14 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M instructions for ❑Complies Requirement will be met.
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated
[FI17]3 representative. ❑Not Observable
ENot Applicable
C303.3, Furnished O&M manuals for HVAC ❑Complies 'Requirement will be met.
C408.2.5. :systems within 90 days of system ❑Does Not
3 ;acceptance.
[F18]3 [Not Observable
❑Not Applicable
C402.5 Building envelope contains a ;❑Complies Requirement will be met.
[FI55]1 continuous air barrier that has been ❑Does Not
tested and deemed to limit air leakage;❑Not Observable
<= 0.40 cfm/ft2.
❑Not Applicable
C402.5.6 Weatherseals installed on all loading ❑Complies Exception: Requirement does not apply.
[FI37]1 dock cargo doors. ❑Does Not
❑Not Observable
❑Not Applicable
C403.2.2 HVAC systems and equipment ❑Complies Requirement will be met.
[FI27]3 capacity does not exceed calculated ❑Does Not
loads.
❑Not Observable
❑Not Applicable
C403.2.4. :Heating and cooling to each zone is ❑Complies Requirement will be met.
1 :controlled by a thermostat control. ❑Does Not
[F147]3 !Minimum one humidity control device
per installed Not Observable
:humidification/dehumidification ❑Not Applicable
system.
C403.2.4. Thermostatic controls have a 5 °F ❑Complies Exception: Manual changeover thermostats.
1.2 deadband. ❑Does Not
[FI38]3 ❑Not Observable
❑Not Applicable
C403.2.4. (Temperature controls have setpoint '❑Complies Requirement will be met.
1.3 overlap restrictions. ❑Does Not
[FI20]3 ❑Not Observable
❑Not Applicable
C403.2.4. Each zone equipped with setback ❑Complies Requirement will be met.
2 controls using automatic time clock or ❑Does Not
[F139]3 programmable control system.
❑Not Observable
❑Not Applicable
C403.2.4. 'Automatic Controls: Setback to 55°F ❑Complies Requirement will be met.
2.1, (heat)and 85°F(cool); 7-day clock, 2- ❑Does Not
C403.2.4. hour occupant override, 10-hour
2.2 backup Not Observable
[F140]3 ❑Not Applicable
C404.3 Heat traps installed on supply and ❑Complies Requirement will be met.
[FI11]3 discharge piping of non-circulating ❑Does Not
systems.
❑Not Observable
❑Not Applicable
C404.3 Heat traps installed on supply and ❑Complies Requirement will be met.
[FI11]3 discharge piping of non-circulating Oboes Not
systems.
❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 15 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C404.4 ;All piping insulated in accordance with ❑Complies Requirement will be met.
[F125]2 I section details and Table C403.2.10. ❑Does Not
:Not Observable
DNot Applicable
C404.4 ;All piping insulated in accordance with ;❑Complies Requirement will be met.
[F125]2 ;section details and Table C403.2.10. ;❑Does Not
ENot Observable
DNot Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts ❑Not Observable,
are less than or equal to allowed ;DNot Applicable
watts.
C408.2.1 Commissioning plan developed by ❑Complies Requirement will be met.
[F128]1 registered design professional or ❑Does Not
approved agency.
;DNot Observable
;❑Not Applicable
C408.2.3. HVAC equipment has been tested to ❑Complies Requirement will be met.
1 ensure proper operation. ❑Does Not
[F131]1 ❑Not Observable
❑Not Applicable
C408.2.3. HVAC control systems have been ❑Complies Requirement will be met.
2 tested to ensure proper operation, ❑Does Not
[F110]1 calibration and adjustment of controls.
❑Not Observable
❑Not Applicable
C408.2.4 Preliminary commissioning report ❑Complies Requirement will be met.
[FI29]1 completed and certified by registered ❑Does Not
design professional or approved
agency. [Not Observable
❑Not Applicable
C408.2.5. ;Furnished HVAC as-built drawings ❑Complies Requirement will be met.
1 'submitted within 90 days of system ❑Does Not
[F17]3 acceptance.
['Not Observable
❑Not Applicable ;
C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met.
1 electric power systems within 90 days Does Not
[F116]3 of system acceptance.
DNot Observable
DNot Applicable
C408.2.5. An air and/or hydronic system ❑Complies Requirement will be met.
3 balancing report is provided for HVAC ❑Does Not
[FI43]1 systems.
DNot Observable
DNot Applicable
C408.2.5. Final commissioning report due to ❑Complies Requirement will be met.
4 building owner within 90 days of ❑Does Not
[F130]1 receipt of certificate of occupancy.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
DNot Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 16 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: West Glens Falls-WGFB-374 Report date: 05/13/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 17 of 18
Permits\374 WEST GLENS FALLS-Building Permit\374-COMCHECK.cck
COMcheck Software Version 4.1.1.0
'
%,.
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Glens Falls National
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
221 Corinth Rd Stewart's Shops Corp.
Queensbury, NY 12804 Ballston Spa, NY 12020
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Office 1283 0.82 1052
Total Allowed Watts= 1052
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp I Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Office(1283 sq.ft.)
LED 1:2 x 2 Bank:LED Panel 40W: 1 19 40 760
LED 5:LED can light:LED Undercabinet Unit 12W: 1 5 12 60
Total Proposed Watts= 820
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any
applicable mandatory requirements listed in the Inspection Ch st.
1/1-5 B
Name-Title Signature Date
nzft 'en '
* ® I 4 b4 +• �. * (%; ", ;, kl r
( 1 1, r �j dw % t•
40 £ tYz
1- ,1
190FESSIO4
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 1 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
11116- COMcheck Software Version 4.1.1.0
Mechanical Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: Glens Falls National
Location: Glens Falls, New York
Climate Zone: 6a
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
221 Corinth Rd Stewart's Shops Corp.
Queensbury, NY 12804 Ballston Spa, NY 12020
Mechanical Systems List
Quantity System Type&Description
1 HVAC System 3(Single Zone):
Heating: 1 each-Duct Furnace,Propane,Capacity=130 kBtu/h
Proposed Efficiency=95.50%Ec,Required Efficiency: 80.00%Ec
Cooling: 1 each-Single Package Vertical AC Unit,Capacity=36 kBtu/h,Air-Cooled Condenser,No Economizer,Economizer
exception:Heat Recovery System
Proposed Efficiency=14.00 EER,Required Efficiency: 9.00 EER
Fan System: None
1 Water Heater 1:
Electric Instantaneous Water Heater,Capacity:4 gallons
Proposed Efficiency:7.05 SL,%/h(if> 12 kW), Required Efficiency:7.05 SL,%/h(if>12 kW)
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable manda ory
requirements listed in the Inspection Checklist.
Seri- r . IL 1-ri..i,► / - = ' /r /�
Name-Title Signature Date '
4,0F NEW y
tpI. ��.1
R�ESSION� o,..7))
= s e b 0 9:,:i .. ' /
y�} P
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 2 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
COMcheck Software Version 4.1.1.0
Inspection Checklist
Energy Code: 2015 IECC
irdt
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or ❑Complies ;Requirement will be met.
[PR2]1 .calculations provide all information ❑Does Not
with which compliance can be
determined for the mechanical ['Not Observable
I systems and equipment and ❑Not Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
;handbooks.
C103.2 ;Plans, specifications, and/or ❑Complies Requirement will be met.
[PR3]1 .calculations provide all information ❑Does Not
with which compliance can be
I determined for the service water ❑Not Observable
heating systems and equipment and ❑Not Applicable ;
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C103.2 Plans, specifications, and/or ❑Complies !Requirement will be met.
[PR4]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment I❑Not Applicable
and document where exceptions to
;the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 3 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
Section
# Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID
C403.2.4. Snow/ice melting system sensors for ❑Complies Requirement will be met.
5, ;future connection to controls. Freeze ❑Does Not
C403.2.4. protection systems have automatic
6 controls installed. Not Observable
[FO913 ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 4 of 11
Permits\374 WEST GLENS FALLS- Building Permit\374-Bank fit-up.cck
Section
# Plumbing Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C404.5, Heated water supply piping conforms ❑Complies Requirement will be met.
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details.
[PL613 ❑Not Observable,
❑Not Applicable
C404.5, Heated water supply piping conforms EComplies Requirement will be met.
C404.5.1, to pipe length and volume '❑Does Not
C404.5.2 requirements. Refer to section details.
[PL6]3 ❑Not Observable
❑Not Applicable
C404.6.3 Pumps that circulate water between a ❑Complies Exception: Requirement does not apply.
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating ['Not Observable
I cycle. ElNot Applicable
C404.6.3 Pumps that circulate water between a ❑Complies Exception: Requirement does not apply.
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating [Not Observable
cycle. ❑Not Applicable
C404.7 'Water distribution system that pumps ❑Complies Exception: Requirement does not apply.
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source
through a cold-water supply pipe is a ❑Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
C404.7 Water distribution system that pumps `❑Complies Exception: Requirement does not apply.
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source
through a cold-water supply pipe is a ,❑Not Observable
demand recirculation water system. ❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 5 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C402.2.6 Thermally ineffective panel surfaces of DComplies Exception: Requirement does not apply.
[ME41]3 sensible heating panels have ❑Does Not
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
C403.2.12 HVAC fan systems at design DComplies Requirement will be met.
.1 conditions do not exceed allowable ❑Does Not
[ME65]3 fan system motor nameplate hp or fan ❑Not Observable See the Mechanical Systems list for values.
system bhp.
❑Not Applicable
C403.2.12;Fans have efficiency grade(FEG) >= DComplies Exception: Fans included in equipment having certified seal
.3 ;67.The total efficiency of the fan at DDoes Not for air or energy performance of the equipment package.
[ME117]2 ;the design point of operation <= 15%
of maximum total efficiency of the ['Not Observable
Ifan. ;❑Not Applicable
C403.2.13 Unenclosed spaces that are heated DComplies Exception: Requirement does not apply.
[ME71]2 use only radiant heat. ❑Does Not
❑Not Observable
❑Not Applicable
C403.2.3 ;HVAC equipment efficiency verified. DComplies 'See the Mechanical Systems list for values.
[ME55]2 I DDoes Not
;❑Not Observable
DNot Applicable
C403.2.6. Demand control ventilation provided DComplies Exception: Systems with energy recovery.
1 for spaces>500 ft2 and >25 DDoes Not
[ME59]1 people/1000 ft2 occupant density and
served by systems with air side ['Not Observable
economizer, auto modulating outside ❑Not Applicable
air damper control, or design airflow
>3,000 cfm.
C403,2.6. ;Enclosed parking garage ventilation ❑Complies Exception: Requirement does not apply.
2 ;has automatic contaminant detection ❑Does Not
[ME115]3 and capacity to stage or modulate
;fans to 50%or less of design capacity. Not Observable
❑Not Applicable
C403.2.7 Exhaust air energy recovery on DComplies Requirement will be met.
[ME57]1 systems meeting Table C403.2.7(1) DDoes Not
and C403.2.7(2).
ENot Observable
❑Not Applicable
C403.2.8 Kitchen exhaust systems comply with DComplies Exception: Requirement does not apply.
[ME116]3 replacement air and conditioned DDoes Not
supply air limitations, and satisfy hood
rating requirements and maximum ['Not Observable
exhaust rate criteria. ❑Not Applicable
C403.2.9 ;HVAC ducts and plenums insulated. ;DComplies Requirement will be met.
[ME60j2 'Where ducts or plenums are installed !DDoes Not
in or under a slab,verification may
;need to occur during Foundation ❑Not Observable
Inspection. DNot Applicable
C403,2.9 Ducts and plenums sealed based on DComplies Requirement will be met.
[ME10]z static pressure and location. DDoes Not
❑Not Observable
❑Not Applicable .
C403.2.9. Ductwork operating >3 in.water DComplies Requirement will be met.
1.3 column requires air leakage testing. DDoes Not
[ME11]3 [Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 6 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
Section
Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C403.4.4. Multiple zone VAV systems with DDC ❑Complies ;Exception: Requirement does not apply.
6 lof individual zone boxes have static ❑Does Not
[ME110]3 pressure setpoint reset controls. See the Mechanical Systems list for values.
❑Not Observable;
❑Not Applicable
C408.2.2. Air outlets and zone terminal devices ❑Complies ;Exception: Fans with fan motors of 1 hp (0.74 kW)or less.
1 have means for air balancing. ❑Does Not
[ME53]3 ❑Not Observable!
❑Not Applicable
C403.5, Refrigerated display cases, walk-in ❑Complies ;Exception: Requirement does not apply.
C403.5.1, !coolers or walk-in freezers served by ❑Does Not
C403.5.2 remote compressors and remote
[ME123]3 condensers not located in a ENot Observable
condensing unit, have fan-powered 1,—Not Applicable
condensers that comply with Sections
;C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 7 of 11
Permits\374 WEST GLENS FALLS- Building Permit\374-Bank fit-up.cck
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.1 Lighting controls installed to uniformly ❑Complies Requirement will be met.
[EL15]1 reduce the lighting load by at least ❑Does Not
50%.
DNot Observable;
❑Not Applicable
C405.2.1 Occupancy sensors installed in ❑Complies !Requirement will be met.
[EL18]1 required spaces. ❑Does Not
[Not Observable
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies Requirement will be met.
C405.2.2. per approved lighting plans and all ❑Does Not
3 manual controls readily accessible and
[EL23]2 visible to occupants. ❑Not Observable
ENot Applicable
C405.2.2. Automatic controls to shut off all DComplies Requirement will be met.
1 building lighting installed in all ❑Does Not
[EL22]2 buildings.
DNot Observable
❑Not Applicable
C405.2.3 Daylight zones provided with ❑Complies Exception: Requirement does not apply.
[EL16]2 :individual controls that control the ❑Does Not
lights independent of general area
;lighting. ❑Not Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are ❑Complies Exception: Requirement does not apply.
C405.2.3. equipped with required lighting ❑Does Not
1, controls.
C405.2.3. DNot Observable
2 ❑Not Applicable
[EL20]1
C405.2.3, Enclosed spaces with daylight area ❑Complies :Exception: Requirement does not apply.
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, are equipped with required lighting
C405.2.3. controls. ❑Not Observable
3 ❑Not Applicable
[EL21]1
C405.2.4 Separate lighting control devices for ❑Complies 'Requirement will be met.
[EL4]1 specific uses installed per approved ❑Does Not
lighting plans.
DNot Observable
DNot Applicable
C405.2.4 Additional interior lighting power ❑Complies Requirement will be met.
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and DNot Observable
separated from general lighting. DNot Applicable
C405.3 'Exit signs do not exceed 5 watts per ;❑Complies Requirement will be met.
[EL6]1 face. !❑Does Not
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 8 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M instructions for Complies Requirement will be met.
C408.2.5. systems and equipment to the EDoes Not
2 building owner or designated
[FI17]3 representative. ['Not Observable
ENot Applicable
C303.3, Furnished O&M manuals for HVAC ;EComplies Requirement will be met.
C408.2.5. systems within 90 days of system :EDoes Not
3 acceptance.
[F18]3 '❑Not Observable
❑Not Applicable
C403.2.2 HVAC systems and equipment EComplies Requirement will be met.
[FI27]3 capacity does not exceed calculated EDoes Not
loads.
['Not Observable
❑Not Applicable
C403.2.4. Heating and cooling to each zone is EComplies Requirement will be met.
1 controlled by a thermostat control. EDoes Not
[F147]3 Minimum one humidity control device
per installed ['Not Observable
humidification/dehumidification ENot Applicable
system.
C403.2.4. Thermostatic controls have a 5 °F ❑Complies Requirement will be met.
1.2 deadband. EDoes Not
[FI38]3 ['Not Observable
❑Not Applicable
C403.2.4. Temperature controls have setpoint EComplies Requirement will be met.
1.3 overlap restrictions. EDoes Not
[F120]3 ENot Observable
ENot Applicable
C403.2.4. Each zone equipped with setback ;EComplies Exception: Requirement does not apply.
2 controls using automatic time clock or i❑Does Not
[F139]3 programmable control system.
ENot Observable;
❑Not Applicable
C403.2.4. Automatic Controls: Setback to 55°F EComplies Requirement will be met.
2.1, (heat) and 85°F(cool); 7-day clock, 2- EDoes Not
C403.2.4. hour occupant override, 10-hour
2.2 backup Not Observable
[F140]3 ENot Applicable
C404.3 Heat traps installed on supply and EComplies Requirement will be met.
[F111]3 discharge piping of non-circulating ElDoes Not
systems.
ENot Observable
ENot Applicable
C404.4 All piping insulated in accordance with EComplies Requirement will be met.
[F125]2 section details and Table C403.2.10. EDoes Not
['Not Observable
ENot Applicable
C405.4.1 Interior installed lamp and fixture EComplies See the Interior Lighting fixture schedule for values.
[F118)1 lighting power is consistent with what EDoes Not
is shown on the approved lighting
plans, demonstrating proposed watts [(Not Observable
are less than or equal to allowed Observable,_._,
Applicable
watts.
C408.2.1 Commissioning plan developed by EComplies Requirement will be met.
[F128)1 registered design professional or EDoes Not
approved agency.
ENot Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 9 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
C408.2.3. 'HVAC equipment has been tested to Complies Requirement will be met.
1 !ensure proper operation. ❑Does Not
[FI31]1 [Not Observable
❑Not Applicable
C408.2.3. HVAC control systems have been ❑Complies Requirement will be met.
2 tested to ensure proper operation, ❑Does Not
[FI10]1 calibration and adjustment of controls.
['Not Observable
❑Not Applicable
C408.2.4 Preliminary commissioning report Complies Requirement will be met.
[FI29]1 completed and certified by registered ❑Does Not
design professional or approved
agency. ❑Not Observable
❑Not Applicable
C408.2.5. Furnished HVAC as-built drawings ❑Complies Requirement will be met.
1 submitted within 90 days of system ❑Does Not
[F17]3 acceptance.
❑Not Observable
❑Not Applicable
C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met.
1 electric power systems within 90 days ❑Does Not
[FI16]3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.2.5. An air and/or hydronic system °❑Complies Requirement will be met.
3 balancing report is provided for HVAC ❑Does Not
[FI43]1 systems.
❑Not Observable
❑Not Applicable
C408.2.5. Final commissioning report due to ❑Complies Requirement will be met.
4 building owner within 90 days of ❑Does Not
[F130]1 receipt of certificate of occupancy.
❑Not Observable
DNot Applicable
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Glens Falls National Report date: 05/14/19
Data filename: G:\Facility\Shop Construction\374 WEST GLENS FALLS\374 WEST GLENS FALLS-Applications ar Page 10 of 11
Permits\374 WEST GLENS FALLS-Building Permit\374-Bank fit-up.cck