Loading...
ResCheckREScheck Software Version 4.6.5 Compliance Certificate Project Bye Home Rennovation Project Energy Code:2015 IECC Location:Lake George,New York Construction Type:Single-family Project Type:New Construction Conditioned Floor Area:3,246 ft2 Glazing Area 31% Climate Zone:6 (7377 HDD) Permit Date: Permit Number: Construction site: 16 Knolls Road North Queensbury,NY 12804 Owner/Agent: Victor &Linda Bye 16 Knolls Road North Queensbury,NY 12804 Cannes Compliance:1.7%Better:Code Maximum UA:422 Your UA’ IV E | Designer/Contractor: Douglas W.Adams Saratoga Engineering &Design 74 Rolling Hills Drive Gansevoort,NY 12831 518-683-6899 saratogaengndesian@nycap,tr.com “The Better or Worse Than Code index reflects how case to compliance the house i based on cde trade-off rules. Med NY Sons taht of ety at of aa eve tos maumum code hoe Env i rersty Gross Ares Cavityoes ‘Wall 1-Existing 2x4 framed walls:Wood Frame,16"0.c. ‘Comment:186 x 8! ‘Window 1-TW210410-2:Wood Frame:Double Pane with Low-E ‘Comment:aty. ‘Window 2-4040:Vinyl/Fiberglass Frame:Double Pane with Low-E ‘Comment:aty. Window 3-1W20210:Wood Frame:Double Pane with Low-E Window 4-1W20410:Wood Frame:Double Pane with Low-E Window 5-90-C23-15: Door 1-6068:Glass Door 2-3/0%6/8:Solid ‘Comment:aty. Wall 4-New 2x6 framed walls:Wood Frame,16"0.c. ‘Comment:45'x 8 Window 6-TW210410-2:Wood Frame:Double Pane with Low-€ Comment:aty.=: Window 7-TW20410:Wood Frame:Double Pane with Low-E ‘Comment:qty.=2 Window 8-Flexiframe 1:Wood Frame:Double Pane with Low-E ‘Comment:qty.=2 jood Frame:Double Pane with Low-E CoCScSZ ahaa 1488225 0.0 0.05567 150 0.300 45 32 0.300 10 6 0.300 10 0.300 R 0.300 42 0.300 13 a 01704 360278 0.0 0.050 2 90 0.30027 20 0300-6 24 0270 «6 Project Title:Bye Home Rennovation Project, Data filename:C:\AutoCad Drawings\Wictor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 1 of10 ory mesPernOJ ienePeonCRS Window 9-Flexiframe 2:Wood Frame:Double Pane with Low-E 42 0.270 11 ‘Comment:qty.=2, Window 10-Flexiframe 3:Wood Frame:Double Pane with Low-E 19 0270 5 ‘Comment:aty. Door 3-6068:Glass.126 0.300 38 ‘Comment:aty. Celling 1:Flat Celling or Scissor Truss 2296 40.5 0.0 0.02967 Basement Wall 1:Masonry Block with Empty Cells.1860 22.5 0.0 0.085 a4 Wall height:9.0° Depth below grade:8. Insulation depth:8.0" Comment:186"x 10° Basement Wall 2:Wood Frame 450 22.5 0.0 0.086 21 Wall height:9.0° Depth below grade:8.0" Insulation depth:8.0 Comment:45°x 10" Compliance Statement:The proposed building design described here is consistent with the building plans,specifications,and other calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IEC requirements in REScheck Version 4.6.5 and to comply with the mandatory requirements listed in the REScheck Inspection Chec Douglas Adams SeName=Tite Signature Date Project Title:Bye Home Renovation Project Report date:01/02/20 Data filename:C:\AutoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Page 2 of 10 wi REScheck Software Version 4.6.5 Inspection Checklist Energy Code:2015 IECC Requirements:100.0%were addressed directly in the REScheck software Text in the "Comments/Assumptions”column is provided by the user in the REScheck Requirements screen.For each requirement,the user certifies that a code requirement will be met and how that is documented,or that an exception is being claimed,Where compliance is itemized in a separate table,a reference to that table is provided, Seaton F°"|pre-inspectionPian Review|Plans Verified|Field Verified|Compas|comments/Assumptionsregio103.Construction ravings and [complies Requrement wile met 103.documentation demonstrate does Not I[PRIp)energy code compliance for the °building envelope.Thermal envelope represented onconstructiondocuments, QNot Observable ONot Applicable 103.1,Construction drawings and Cicomptes 1032;documentation demonstrate Oboes not203.7,energy code compliance for TPR3}lighting and mechanical systems.Not Observable °Systems serving multiple CNet Applicable Gieling units must demonstrate omplance withthe lECe Commercial Provisions.ao/302.1,Heating and cooling equipment is Heating:Ocompties Requirement will be met.403.7 sized per ACCA Manual S based=Btu/hr_Oboes NotRay?ontoads calculated per ACCA”Cooling:Cooling [Not Observable DT Manual)or other method mae Por ct Observableapprovedbythecodeofficial.——Applic Additional Comments/Assumptions: [i]Figh impact(Tier i)”[2[Medium impact (Tier 2)[3 [Low impact (ier3)|Project Title:Bye Home Rennovation Project Data filename:C:\AutoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 3 of10 303.21 A protective covering is installed [FOL1P to protect exposed exterior 6 insulation and extends a minimum of 6 in,below grade, 1403.9 Snow-and ice-mel [FOI2P controls installed. @ Not Applicable ‘Gcomplies‘Ooes Not Not ObservableOotApplicable Cicomplies Oboes Not Not observable ONot Applicable SeaionaE"soundaton neecin 4 Plans Verified|Field verited|complies?|Comments/Assumptions '402.1.1 Conditioned basement wall Re Ocomplies ‘See the Envelope Assemblies. {(FO4}’insulation R-value.Where interior —_does Not (able for vatues. insulation &eaed:venscauan —ray taal rossi arin iNet observable Insulation Inspection.Not Oot ApplicableeaeeeePease303.2 Conditioned basement wall complies “Requirement will be met.(FOS!insulation installed per Oboes NotareeeeoemNotApplicable 402.2.9 Conditioned basement wall ft complies ‘See the Envelope Assemblies {FOS}!insulation depth of burial or =Coes Not ‘able for values.ea nee con ee Requirement will bemet. Requirement wilbe met Additional Comments/Assumptions: Impact (Tier 1)Z]Medium impact (Low impact (Tier 3) Project Title:Bye Home Rennovation Project Data filename:C:\AutoCad Drawings\WVictor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 4 of 10 piping conveying fluids |eramioa 1 Roustvin inspection]P45 Verified|Field verted Comptes?|Comments/ssumptins |2021.1,Door U-ectr.~v Clcomplies See the Envelope asembes i402 3.4 Oboes not ble orate.[as CiNot ObservableleNotApplicable 1202.11,GlazingUfactor(areaweighted U__Clcomplies See the Envalpe Asombes 202.31,average).Fioceener ——tahieforvaues 42233.[Net Observable treo CiNot Applicable~Wtactors of fenestration products |Clcomplies are determinedinaccordanceClpoesNotwiththeNFRCtestprocedureortakenfromthedefaulttable.(Not Observable ONot Applicable '402.4.1.1 Air barrier and thermal barrier complies Requirement will be met. [FR23}'installed per manufacturer's Oboes Not e porns,(CiNot Observable _ot Applicable ‘402.43 Fenestration that is not site built Cicomplies Requirement will be met. |[FR20P is listed and labeled as meeting Odoes Not ‘RAMA MDMAICSA 101/15.2/4480”‘or has infiltration rates per NFRC |CINot Observable 400 that do not exceed code ONot Applicable tims.os Cie|402.4.5 —_IC-rated recessed lighting fixtures complies Requirement will be mé(reas)Clooes Notandlabeledtindicate22.0 cfm theeseTeokageat75Pa,Oot Applicab! /403.3.1 Supply and return ducts in attics complies Exception:Ducts located TFR12}insulated >=R-8 where duct is Oboes Not completely inside the e >=3inchesindiameterand>=building envelope. ®R-6 where <3 inches.Supply and CINot Observable return ducts in other portions of ‘ONot Applicable the building insulated>=Re for Glameter >=3 inches and fea.2foreinchesinameter L _|403.3.5 Building cavities are not used as complies Requirement will be met. IFRISP ducts or plenums,Oboes Not @ (CNot Observable ONot Applicable IFR17P above 105 °F or chilled fluidsSeow55Fareaubtedfer eg dia aiseOotApplicable /403.4.1 Protection of insulation on HVAC Ocompties Requirement will be met. (FR24 piping.Oboes Not ®{Not ObservablenotApplicable 46353 Hot water pipes are insulated to ~~Elcomplies Requirement will be met. (FRI8P==R-3.Oboes Not @ (Not ObservableOotApplicable /403.6 ‘Automatic or gravity dampers are complies Requirement will be met. [FRI9P istalled on all outdoor air Oboes Notintakesandexhausts.nor observable Impact (Tier i),Low impact (Tier 3) Project Title:Bye Home Rennovation Project Data filename:C:\autoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 5 of 10 Additional Comments/Assumptions: [T]Highimpactier1)2]Medium impact (ier2)—[3][Lowimpact ter 3)—] Project Title:Bye Home Rennovation Project Report date:01/02/20 Data filename:C:\AutoCad Drawings\WVictor &Linda Bye\322-18 REScheck.rck Page 6 of10 Seetion entgin,statontnspection any foced|Pet Yeates comptes?|CommentiAssumptions 1D 303.1 All installed insulation is labeled complies Requirement will be met. |(IN13P —_or the installed R-values Oboes Not 8 pees)(Not ObservableOotApplicable ‘Wall insulation R-value.If this is a R-Oicomplies -—“See the Envelope Assemblies — —__oO mae wal wih at east othe"(Wana Wood Coes Not able fr values well inside son On Ue ar Ci Mass C Mass (Not ObservableSeer,the exterior insulation 1 Meee Oye Des oeeratrequirementapplies(FR10).plicable 303.2 ‘Wall insulation is installed per ze Cicompi "Requirement will be met. uinay ‘manufacturer's instructions.Oboes Not {Not ObservableNotApplicable ‘Additional Comments/Assumptions: [i ]Righ impact (ier) [2 [Mediumimpact(Tier 2)[3 [Low impact Tier3) Project Title:Bye Home Renovation Project Report date:01/02/20 Data filename:C:\AutoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Page 7 of 10 Section J"|Final inspection Provisions|Plans Verified|Field Veried|Compies?Ceeanego|oe4021.1,Ceiling insulation R-value.Re R See the Envelope Assembles 4022.1,(Wood (0 Wood table for values eae Steet O Steel Not ObservableriNotApplicable 303.1.1.1,Ceiling insulation installed per ee Gicomplies Requirement will be met. 303.2”manufacturer's instructions.Dooes Not {FIZ}!Blown insulation marked every Fae catesaeDotApplicable 1402.23.Vented attics with air permeable complies Exception:Requirement is[F122 insulation include baffle adjacent Clooes Not ——~not applicable. to soffit and eave vents thatPeataan Not observableneoer.Not Applicable -4022.4 Attic access hatch and door Cicomplies Requirement will be met. [FI3}"insulation 2R-value of the Ciboes Not adjacent assembly.eyOnotApplicable '402.4.1.2 Blower door test @ 50 Pa.‘ACH 50 =‘ACH 50 Cicomplies Requirement will be met.[FIT achin Climate Zones 1-2,and Coes Not <=3 ach in Climate Zones 3-8,eonsCiNotApplicable {402,42 Wood-burming fireplaces have Cicomplies Exception:Requirement is[IBF tight fitting flue dampers and Coes Not not applicable. outdoor air for combustion.PasasseneNotApplicable '403.3.4 Duct tightness test result of <=4 ‘cfmy100 ‘fm/100 Complies Exception:All ducts and air {Fa}cfny/100 fe2 across the system or Cioves not handlers are located within <=3 cfm/100 f2 without a conditioned space, handler @ 25 Pa.For rough-in peice Observetests,veifcation may need to lot Applicable ‘occur during Framing inspection.i -[403.33 Ducts are pressure tested to efmi00 efmj100 complies ‘Exception:All ducts and air [FI271*determine air leakage with ez me Cdoes Not —_—=handlers are located within ether:Roupintet Total Net observable conditioned space. pressure differential of 0.1 inch Not Applicable Wg.across the system includingthemanufacturersairhandler enclosure if installed at time oftest,Posteonstruction test:Total leakage measured with a pressure differential of 0.2 inch Wig.across the entire system including the manufacturers ar handler enclosure.__'403.32.1 Air handler leakage designated Cicomplies Requirement will be met. [F124}°by manufacturer at <=2%of Cidoes Not design airflow.SareeNotApplicable |{403,1.1 Programmable thermostats Cicomplies Requirement will Be met. [IOP installed for contro of primary Cidoes Not heating and cooling systems and sonalMealystbmanurenotobservable code specifications.INot Applicable [403.1.2 Heat pump thermostat installed complies Exception:Requirement is IFO}?on heat pumps.Qlooes Not ——_—nat applicable. Not observableNotApplicable [TJHigh impact(fier) [2 [Medium impact (Tier2) [3 [Lowimpact(Tier 3)|Project Title:Bye Home Rennovation Project Data filename:C:\AutoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 8 of10 ‘Section Does not apply to low-voltage lighting Plans Verified|Field Verifieden'403.5.1 Circulating service hot water ‘complies Exception:Requirement is|[Fniy’systems have automatic or does Nat not applicable‘accessible manual controls,Ser eeoe '403.6.1 All mechanical ventilation system _ Exception:Requirement is[F125]?fans not part of tested and listed ‘not applicableata!hor ober[aes Not Applicable 403.2,Hot water boilers supplying heat complies[FI26P through one-or two-pipe heating Coes Not not applicable.systems have outdoor setback Control to lower boiler water Not Observable temperature based on outdoor Bnot Applicable temperature.s'403.5.1.1 Heated water circulation systems complies Exception:Requirement[F128]?have a circulation pump.The Ddoes Not not applicable,system return pipe is a dedicated return pipe or a cold water supply (Not Observable pipe.Gravity and thermos-‘Oot applicable Syphon circulation systems arenotpresent.Controls for ‘irculating hot water system pumps start the pump with signal for hot water demand within the ‘occupancy.Controls ‘automatically turn off the pumpwhenwaterisincirculationloop is at set-point temperature and|____nodemandforhotwaterexists. '403.5.1.2 Electric heat trace systems complies Exception:Requirement is,(F129 comply with IEEE 515.1 or UL ‘Oboes Not ‘not applicable.515.Controls automatically ‘adjust the energy input to the IC)Net Observable heat tracing to maintain the OWNot Applicable desired water temperature in the Siping, '403.5.2 Water distribution systems that Cicomplies i Requirement isF130)have recirculation pumps that Toes Not nat applicable. pump water from a heated water supply pipe back to the heated CNet Observable water source through a cold Not Applicable water supply pipe have a ‘demand recirculation water system.Pumps have controlsthatmanageoperationofthe pump and limit the temperatureofthewaterenteringthecold water piping to 104°F,bela'403.5.4 Drain water heat recovery units complies fequirement is[FIP tested in accordance with CSA Toes Not not applicable.55,1.Potable water-side pressure loss of drain water heat ICINot Observable recovery units <3 psi for Clot Applicable individual units connected to one for two showers.Potable water-side pressure loss of drain water heat recovery units <2 psi for individual units connected to three or more showers. 1404.1 75%of lamps in permanent complies Requirement will be met.Fie}!fixtures or 75%of permanent Coes Notfixtureshavehighefficacylamps.Pua ceeeoeONotApplicable [Impact (Tier 1)[2 [Medium impact (Tier 2)Low Impact (Tier 3) Project Title:Bye Home Rennovation Project Data filename:C:\AutoCad Drawings\Wictor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 9 of 10 2015 IECC Energy Efficiency Certificate Cea Car ‘Above-Grade Wal 22.50 Below-Grade Wal 22.50 Floor 0.00 Celling /Roof 40.50 Ductwork (unconditioned spaces):Cer ccs‘Window 0.30 Door 0.30tteEee Nam Date: SectionSP rina inspection Provisions|Mang etied |Fisigvsrted |comptes|commens/Assumptionsfae| |404.1.1 Fuel gas lighting systems have complies Exceptic Requirement is[FI23P —_no continuous pilot light.Oboes Not not applicable. °Not observate ON ble 401.3 ‘Compliance certificate posted.complies Requirement will be met.FP Oboes Not CiNot observable .Not Applicable |303.:complies |[FI48P mechanical and water heating Odoes NotSeteotepredeeOotApplicable Additional Comments/Assumptions: 1 High impact(ier 3)[2Mediumimpact ier)[3]low impact(ier3)|Project Title:Bye Home Rennovation Project Data filename:AutoCad Drawings\Victor &Linda Bye\322-18 REScheck.rck Report date:01/02/20 Page 10 of10,