FM Inspections s
.< f
fi
Town of Queensbury- Building and Codes- Fire Marshal
742 Bay Road-(518)761-8256 Building (518)761-8206 Fire Marshal
Case Number: CC-0539-2018 Case Module: Permit
Inspection Date: Fri Sep 20, 2019 Inspection Status: Passed
Inspector: Mike Palmer Inspection Type: OCC-Inspections
Job Address: 59 WEST MOUNTAIN RD Parcel Number: 307.-1-29
Queensbury, NY 12804
Contact Type Company Name Name
Primary Owner East Slope Holding, LP
Architect AJA Architecture & Planning
Granted Permission East Slope Holding, LP
Applicant Spencer Montgomery
Checklist Item Status
Fire Marshal Passed
Exit Access Passed
Exit Enclosure Passed
Exit Discharge Passed
Locks and Latches Passed
Sign: Normal Passed
Page(1)
Sep 20,2019
Checklist Item Status
Sign: Backup Passed
Main Aisle Width Passed
Secondary Aisle Width Passed
Fire Extinguisher Hung Passed
Inspection of Extinguisher Passed
Evac Plan Passed
Truss ID Signage Passed
Emergency Lighting Interior Passed
Emergency Lighting Exterior Passed
Clearance to Electrical Passed
Electrical Wiring Enclosed/Labeled Passed
Sep 20,2019 Page(2)
Checklist Item Status
Combustibles in Equipment Rooms Passed
Storage Passed
Interior Finishes Passed
CO Detectors Passed
Clearance to Sprinkler/Ceiling Passed
Hood Installation Passed
8/20- need to verify fan override function
FIRE ALARM Annual Passed
Sprinkler System Annual Passed
Sprinkler FDC Passed
Kitchen Suppression Semi Annual Passed
8/20-function test was successful however shunt trip is required for electric outlets behind appliances
Hood Cleaning 3-6 Annual Passed
Knox Box: installed/checked Passed
Sep 20,2019 Page(3)
Checklist Item Status
Occupancy Cycle Passed
A
Palmer,Mike
Sep 20,2019 Page(4)
Town of Queensbury- Building and Codes- Fire Marshal
742 Bay Road-(518)761-8256 Building (518) 761-8206 Fire Marshal
Case Number: CC-0539-2018 Case Module: Permit
Inspection Date: Tue Aug 20, 2019 Inspection Status: Partial Pass
Inspector: Mike Palmer Inspection Type: OCC-Inspections
Job Address: 59 WEST MOUNTAIN RD Parcel Number: 307.-1-29
Queensbury, NY 12804
Contact Type Company Name Name
Primary Owner East Slope Holding, LP
Granted Permission East Slope Holding, LP
Architect AJA Architecture& Planning
Applicant Spencer Montgomery
Checklist Item Status
Fire Marshal Passed
Exit Access Passed
Exit Enclosure Passed
Exit Discharge Passed
Locks and Latches Passed
See email
Sign: Normal Passed
Aug 20,2019 Page(1)
Checklist Item Status
See email
Sign: Backup Passed
See email
Main Aisle Width Passed
Secondary Aisle Width Passed
Fire Extinguisher Hung Passed
Inspection of Extinguisher Passed
Evac Plan Passed
Truss ID Signage Passed
Emergency Lighting Interior Passed
See email
Emergency Lighting Exterior Passed
Seeemail
Clearance to Electrical Passed
Electrical Wiring Enclosed/Labeled Passed
See email
Aug 20,2019 Page(2)
Checklist Item Status
Combustibles in Equipment Rooms Passed
Storage Passed
Interior Finishes Passed
CO Detectors Passed
Clearance to Sprinkler/Ceiling Passed
Hood Installation Failed
8/20-cannot find make up air. If external to hood, show were it comes in and a balancing report
8/20- need to verify fan override function
8/20-need grease light test reports
FIRE ALARM Annual Passed
Sprinkler System Annual Passed
Sprinkler FDC Passed
Kitchen Suppression Semi Annual Failed
8/20-function test was successful however shunt trip is required for electric outlets behind appliances
Hood Cleaning 3-6 Annual Passed
Aug 20,2019 Page(3)
INSPECTION WORKSHEET1 1 • 1
Checklist Item Status
Knox Box: installed/checked Passed
Occupancy Cycle Passed
A
Palmer,Mike
Aug 20,2019 Page(4)
a ,
Town of Queensbury- Building and Codes- Fire Marshal
742 Bay Road-(518) 761-8256 Building (518)761-8206 Fire Marshal
Case Number: CC-0539-2018 Case Module: Permit
Inspection Date: Mon Aug 5, 2019 Inspection Status: Partial Pass
Inspector: Mike Palmer Inspection Type: OCC-Inspections
Job Address: 59 WEST MOUNTAIN RD Parcel Number: 307.-1-29
Queensbury, NY 12804
Contact Type Company Name Name
Applicant Spencer Montgomery
Primary Owner East Slope Holding, LP
Architect AJA Architecture& Planning
Granted Permission East Slope Holding, LP
Checklist Item Status
Fire Marshal Passed
Exit Access Passed
Exit Enclosure Passed
Exit Discharge Passed
Locks and Latches Passed
See email
Sign: Normal Passed
Aug 05,2019 Page(1)
f�
Checklist Item Status
See email
Sign: Backup Passed
See email
Main Aisle Width Passed
Secondary Aisle Width Passed
Fire Extinguisher Hung Failed
See email
Inspection of Extinguisher Failed
See email
Evac Plan Passed
Truss ID Signage Failed
See email
Emergency Lighting Interior Passed
See email
Emergency Lighting Exterior Passed
Seeemail
Clearance to Electrical Passed
Electrical Wiring Enclosed/Labeled Passed
See email
Aug 05,2019 Page(2)
Checklist Item Status
Combustibles in Equipment Rooms Passed
Storage Passed
Interior Finishes Passed
CO Detectors Passed
Clearance to Sprinkler/Ceiling Passed
Hood Installation Failed
See email-cannot find make up air. If external to hood, show were it comes in and a balancing report
FIRE ALARM Annual Passed
See email
Sprinkler System Annual Passed
See email
Sprinkler FDC Passed
Kitchen Suppression Semi Annual Failed
See email
Hood Cleaning 3-6 Annual Passed
Knox Box: installed/checked Passed
Aug 05,2019 Page(3)
Checklist Item Status
Occupancy Cycle Passed
A
Palmer,Mike
Aug 05,2019 Page(4)
Town of Queensbury-Building and Codes- Fire Marshal
742 Bay Road-(518)761-8256 Building (518)761-8206 Fire Marshal
Case Number: CC-0539-2018 Case Module: Permit
Inspection Date: Fri Jun 28, 2019 Inspection Status: Failed
Inspector: Mike Palmer Inspection Type: OCC-Inspections
Job Address: 59 WEST MOUNTAIN RD Parcel Number: 307.-1-29
Queensbury, NY 12804
Contact Type Company Name Name
Architect AJA Architecture & Planning
Applicant Spencer Montgomery
Granted Permission East Slope Holding, LP
Primary Owner East Slope Holding, LP
Checklist Item Status
Fire Marshal Passed
Exit Access Passed
Exit Enclosure Passed
Exit Discharge Passed
Locks and Latches Failed
See email
Sign: Normal Failed
Jun 28,2019 � ��� a� Page(i)
Checklist Item Status
See email
Sign: Backup Failed
See email
Main Aisle Width Passed
Secondary Aisle Width Passed
Fire Extinguisher Hung Failed
See email
Inspection of Extinguisher Failed
See email
Evac Plan Passed
Truss ID Signage Failed
See email
Emergency Lighting Interior Failed
See email
Emergency Lighting Exterior Failed
Seeemail
Clearance to Electrical Passed
Electrical Wiring Enclosed/Labeled Failed
See email
Jun 28,2019 Page(2)
Checklist Item Status
Combustibles in Equipment Rooms Passed
Storage Passed
Interior Finishes Passed
CO Detectors Passed
Clearance to Sprinkler/Ceiling Passed
Fuel Pump Warning Signs Failed
Hood Installation Failed
See email
FIRE ALARM Annual Failed
See email
Sprinkler System Annual Failed
See email
Sprinkler FDC Passed
Kitchen Suppression Semi Annual Failed
See email
Hood Cleaning 3-6 Annual Passed
Jun 28,2019 Page(3)
,'408i
Checklist Item Status
Knox Box: installed/checked Passed
Occupancy Cycle Passed
A
Palmer,Mike
Jun 28,2019 Page(4)
F -. # '
�. [t t i 1f.
Town of Queensbury
FIRE MARSHAL'S OFFICE
FIRE ALARM SYSTEM INSPECTION
DATE: ✓1 �Ll FA CONTRACTOR � ' ~I r
LOCATION: V;c7l 'Anl-' CENTRAL STATION TIE IN AND CONFIRMED
COPY OF LICENSE
FIRE ALARM PLANS AND CUT SHEETS PROVIDED
RECORD OF COMPLETION PROVIDED
NFPA 72 INSPECTION REPORT PROVIDED
FIRE DEVICES VISIBLE
DO NOT RESET STICKER ON PANEL
ZONE CHART PROVIDED
STROBE FUNCTION ON SILENCE ACTIVE/ DISABLED
ALL REQUIED KEYS PROVIDED
FUNCTION TEST: PULL STATION
SMOKE DETECTOR
HEAT DETECTOR
HORN STROBE
HVAC SHUTDOWN
ANSUL TIE IN
FUEL ISLAND TIE IN
TAMPER
i
FLOW +f�
i
CO DETECTION _
PROTECTION SYSTEM
NEW YORK FIRE&SECURITY INSPECTION REPORT
4 Glens Falls Technical Park
Glens Falls,NY 12801-3802 DATE OF ORDER 6-13-2019 WORK ORDERED BY
(518)798.9551 ORDER TAKEN BY PHONE
Fax(518)792-5199
P.G.NO
West Mt Ski Area JOBNAMEING _
59 West Mt Rd "LOCATION Acct#OJ2838
Queensbury NY 12804 INSTALLATION DATE LAST INSPECTION
11-8-2018
INVOICE GATE JOB PHONE
INSPECTION
INFORMATION SYSTM INFORMATION
4 SYSTEM EQUIPMENT MANUFACTURE Silent Knight SK 5820 XL
4 �' 4 k
R.O.R. 26
SYSTEM INSTALLER NYFS
�
Fixed Heat SYSTEM APPLICATION Ski Lodge
Photoelectric 31
Ion TYPE OF SYSTEM Fire Alarm
Duct MAINTENANCE PROGRAM BY NYFS
Flame
CALL LIST UP TO DATE
Manual 16 v ❑Yes �N-.;
Z
G" Cross Zone REMARKS
t= ACCT NUMBER OJ2838
Single Zone -- — ------ ---
Contacts
Motions
Photobeams
CONTROL PANEL AGENT TANK COMMUNICATIONS DEVICES
Water Flow 1
Low Air 1 A.C.Voltage 125.9 Weight A.C.Voltage
Sprinkler Tamper 1
D.C.with Load Last Hydro D.C.Voltage
Bed Shaker
Elev/Shunt Trip 1 D.C.without Load 26.6 Gauge Pressure D.C.without Load
Air Hand. 2
Batt A 12.59 serial#
Ansel 2
Door Release Duct Damper Batt B 12.60
Equipment Shutdown
CO Detector added and inspected Additional devices added for remodel
ij A.C.Voltage _ v
BZ4. D.C-Voltage
IBattery J
Z Detection Circuit0 Audible Circuit
---
Remote Activation
gi. Audible Devices 18
Visual Devices 24
Pre.Discharge
Signs As Needed
Selector Valves
Piping [0 The testing performed and noted on this inspection report is based on NFPA 72 guidelines
Nozzles
sW Tanks -
uf Gauges — INSPECTOR vy
"Z{ Piston Activator TD/BF
hereby acknowledge the satisfactory completion Q SYSTEM FUNCTIONAL
Solenoid of the above described work.
Manual Release
❑ SYSTEM NON-FUNCTIONAL
Time Delay --
Remote Station Trans.
� Digital Dialer � DISCREPANCIES
x.Ia NOTED ABOVE
pVoice Dialer Ayr 6-13-2019
Phone Line Signature(Title) Date