Range Hood Suppression TOWN OF QUEENBURY
RANGE HOOD SUPPRESSION
(Z)w WORKSHEET
LOCATION:
DATE:
INSPECTOR: c
SYSTEM INFORMATION
w
MAKE: ANs_,i-
MODEL: ill cv-D-
SIZE: 3 d� 30 o
SYSTEM DATA TESTING DATA
PASS FAIL I PASS FAIL
All appliances properly covered Nozzle caps off
System monitored by fire alarm Fire alarm activation
Nozzle protection in plenum Central Station Monitored
Hood filters Gas valve off
"K' Extinguisher Exhaust hood On
Fusible Links All appliances shutdown
Nozzle Caps
Manual Actaution 10720'
Range Hood Operational Grease Duct Test MC506.3.2.5
UL 300
Appliance layout vs. drawings Type 1 hood interlock MC 507.2.11
16" deep fryer/open flame Makeup air interlock MC 508.1
MJKLER, LLB
July 5, 2019
Apex Capital
59 West Mountain Rd
Queensbury, NY 12804
RE: West Mountain Ski Resort
Kitchen Project
SRI Job#10019J
To Whom It May Concern:
This letter serves to confirm that SRI Fire Sprinkler, LLC has completed the sprinkler head
modification under the contract at the above referenced location and relocated Sprinkler Heads
to comply with NFPA 13 spacing requirements.
Respectfully,
/" 4"Z&
Justin Russell
Estimating/Service
SRI Fire Sprinkler, LLC
Corporate Office: 1060 Central Avenue, Albany, New York 12205
Truck Deliveries Warehouse: 1064 Central Avenue,Albany, New York 12205
Phone: 518.459.2776 Fax: 518.459.0068
ADiRONDACK P & M
PLUMBING & MECHANICAL
CONTRACTORS
Po Box 562, Glens Falls, NY z28oz-o562 AND SHEET METAL FABRICATORS
P(ovie No. (518) 793-3883, Fax No. (0)793-4114
8/9/19
West Mountain Ski Center
West Mountain Rd
Queensbury, NY 12804
Main Lodge Kitchen Renovation:
To Whom it may concern:
Adirondack P&M, Inc. has perform light test on the grease laden hood
ductwork as per IMC 506.3.2.5
Phil Tucker
Adirondack P&M, Inc.
i77
r
REORDER PART NO.IF100
Pre-Engineered Restaurant Fire Suppression Systems Report
,< '.•'.Cf. 'Nn?.i..r _-)AT DF V RVIC _,,
RNNU L EMI-AN UAt RECHARGE INST LA'ION RENOVATION
I E-W YORK FIRE & SECURITY
I :LOCATION OF SYSTEM CYLINDERS UL 300
4 Glens Falls Technical Park �y (� / }� }
G �y�+ q Q �/ Q(� Q Q �. i LJ�.�f���' _� �C�V7�" YES E�NO
l v I 1 s Falls, N{ 1 28 N 1-N U 02 MANUFACTURER -T MODEL NUMBER WE DRY CHEMICAL
(518) 798-9551
CYLINDER SIZE MASTER CYLINDER SIZE
i SLAVE i CYLINDER SIZE SLAgVE
L
-- - I FUSE L 360'F FUSE LINK `F ! FUSE LINKS SW F OTHER
e CUSTOMER
Name l l +* + t
FUELS F ELECTRIC G SIZE
Addressil
(/�t 7 -ic j '�
//r�� 'i SERIAL NUMBER I HYDRO TEST DATE _1
LAS RECHARGE DATE
Cityl f _State J.y ZIP.. '5 oo 31 1 �) _
"'�C, / MANUFACTURER'S MANUAL REFERENCE
l Telephone { Store No.
PAGE NUMBER: �^ DRAWING NUMBER DATE
Owner or Manager
COOKING APPLIANCE LOCATIONS: LEFT TO RIGHT
I
1. All appliances properly covered w/correct nozzles 20. Replaced fuse links
2. Duct and plenum covered w/correct nozzles 21. Check travel of cable nuts/S-hooks
3. Check positioning of all nozzles. 22. Piping&conduit securely bracketed
4. System installed in accordance w/MFG UL listing 23. Proper separation between fryers&flame
5. Hood/duct penetrations sealed w/weld or UL device 24. Proper clearance-flame to filters
6. Check if seals intact,evidence of tampering 25, Exhaust fan in operating order
7. If system has been discharged, report same 26. All filters in place
8. Pressure gauge in proper range(If gauged) 27. Fuel shut-off in on position
9. Check cartridge weight(If applicable) 28. Manual&remote set/seals in place
10. Hydrostatic test date 29. Replace systems Covers _
11. 6 year maintenance date Ivy 30. System operational&seals in place
12. Inspect cylinder and mount ---���-- 31. Slave system operational
13. Operate system from terminal link 32. Clean cylinder&mount
14. Test for proper operation from remote 33. Fan warning sign on hood
15. Check operation of micro switch _ 34. Personnel instructed in manual operation of system
16, Check operation of gas valve 35. Proper hand portable extinguishers �-
17. Clean nozzles 36. Portable extinguishers properly serviced
18. Proper nozzle covers in place 37. Service&Certification tag on system
19. Check fuse links and clean NOTE DISCREPANICES OR DEFICIENCIES BELOW
COMMENTS: Mil- Sc. �t�j 7 j'G J Ile-
On this date, this pre-engineered fire suppression system was inspected and operationally tested in accordance with the fire
suppression system requirements of NFPA17 or 17A, 96 and the manufacturer's manual with the results indicated above.
X-- LiL
��- � ----
SERVICE TECHNICIAN PER NO. DATE: TIME: AM PM C TOMER' AUTHORIZED AGENT
o�
W
<>
45 :1. ANSUL..
2K
450
4
tN
450
260 Z
ALML-
450
2W
if
NEATDETECTYIR
I
C�RIL�
if: 450
o
J.N
b BI.tRNER
3N
SRNDWICM a µ I
STATION \N 9 O
CHAP 230 'a
BROILER Y Z
Y
230 �
A Q
NOTbS:
Ay/y��yy rfRae ay��NaaRs?pA44du
�1FIR6 SK.pm5ss10N SYSTEM - ( ( ( r TAI
Al- sine N.T.s IL JI IL JI IL J SVI a�AI.lQN5 fi'pR.1TML1ANf,`a
AN514LANTOMAN L1Na
TMRaa f�AllONS fOR at�Ci ANa
T{.aN11IA
A101.
No.
SUBMITTAL
Job Title: West Mountain Kitchen
Engineer: Bruce Boswell
Contractor: Adirondack P&M
Elevation: (ft) 341
Date: 9/11/2018
Submitted By: Jeff Miller
BUCKLEY ASSOCIATES INC
120 RAILROAD AVENUE
ALBANY, NY 12205
US
Phone: (518)438-7423
Fax: (518)438-5527
Email Address: jmiller@buckleyonline.com
LdGREENHECK
Building Value in Air.
P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX(715) 355-2399 www.greenheck.com
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 1 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: Grease Hood
Model: GHEW-204.00-S
GHEW Type 1, Baffle Filter Single Wall-Exhaust Only Wall Canopy
m, Exhaust
Height
Hei
Hood Bottom 9 (in.) Exhaust SP Double
Model Length m. Width(in.) Width in. Volume in.w. Island
g ( ) ( ) Front Back (CFM) ( g)
GHEW 204 42 42 24 1 24 5100 0.519 No
Selected Options &Accessories:
Option or Accessory Description Material:430 SS Where Exposed
Mounting Height 80 in.off Finished Floor. UL Listing:UL 710 w/out Exhaust Fire Damper
Integral Air Space Factory Mounted on Back-3"wide Features:
Ceiling Enclosures 18 in.High on Left Front Right Performance Enhancing Lip(PEL)
Filter Type Stainless Steel Baffle Filters Standing Seam Construction for Superior Strength
Backsplash Panel 80 in High 216 in Long 0 in Wide Stainless Steel Finish for Higher Corrosion Resistance
Hood End Conditions:
Back Wall- Limited Combustible
Section Data:
Filter Qty
Section Length Volume SP 16" 20" Filter Ht. Cooking Light Light Type Foot Drain Weight
Num. (in.) (CFM) (in.wg) W W (in.) Load Qty Candles Location (Ibs)
1 102 2550 0.519 5 1 20 Heavy 3 Incandescent/CFL 41.85 Right 272
2 102 2550 0.519 5 1 20 Heavy 3 Incandescent/CFL 41.85 Right 272
Exhaust Collar Data:
Section Collar Collar Size(LxW)in. Pos.Off Pos Off Velocity Mounting Option
Num. Num. or Diameter(in.) Left(in.) Back(in.) (fpm)
1 1 24 x 10 1 51 7 1530 Factory Mounted Exhaust Collar(s)
2 1 24 x 10 51 7 1530 Factory Mounted Exhaust Collar(s)
Utility Cabinet Data:
Descripiton Length Width Height Weight
(in.) (in.) (in.) (Ibs)
Right Utility Cabinet 42 12 1 24 43
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 2 of 29
v 3.0
U)
? RgPR INTEGRAL AIR SPACE R iR INTEGRAL AIR SPACE
N 7.0
L_� 7.0
0 � 10.0 ��� 10.0 W
o' T 24.0 24.0 }U 42.0 m
34 IN.OC m
LEI Z)
Z
� m
� n
51.0 51.0 51.0 51.0 D
102.0 102.0 12.0 S
216.0
MARK:Grease Hood-SECTION 1 MARK:Grease Hood-SECTION 2
0 PLAN VIEW PLAN VIEW
cr
21
Cu
cn
6 0 n
CD
CD
C
m �
m
Er r
CD
(D c
Q N
D�
U)�.
c- m
C
O a
cy In 0 z
� CCD
y
0
c m
� n
go
7
3 216.0 in.LENGTH
p BACKSPLASH PANEL
0 0 L
x x O
0 G) a M
v v O Grt
0 0 (D Q
M M '�"�
0
MARK:Grease Hood-SECTION 1 MARK:Grease Hood-SECTION 2 ='' C p
ELEVATION VIEW ELEVATION VIEW Cm G)=
8 v O
N cn
C)CDCD
�
w O=0 N
0 O 00 (D O
co NOTE:All dimensions are in units of in. (A n D 00
n Hanger Bracket Locations
D
can Sec Brkt Distance Off Distance
+' # # Left(in) Off Front 0^
iv (in) �1
V 1 1 3.50 2.50
A Cn 1 2 98.50 2.50 .�
0
1 3 3.50 38.00 �Qo
1 4 98.50 38.00 +z
2 1 3.50 2.50
2 2 98.50 2.50
18.0 4.0 2 3 3.50 38.00
2 4 98.50 38.00 ,n
Bracket Mounting Position
for a 4 Bracket Hood I'
24.0
� 3 �
o BACK
c
N FRONT
OID n 1 2
v r 122.0 UL LISTED LIGHT FIXTURE
CDC
Q �
D 80.0 UL LISTED
3. ABOVE STANDARD BAFFLE FILTERS
m` :R FINISHED
REMOVABLE GREASE CUP WI
N Q Z FLOOR CONCEALED GREASE TROUGH
0 y INTEGRAL AIRSPACE
CD N
N.O
3
7
C 9
7 n
50
7 3
n
0 MARK: Grease Hood (LAST HOOD IN ROW)
O
CL
CD is CL
2 0 v
ITI ..
v C)
O Cl)
n CD a
CD
O=0 N
° C)O CD �
rQ NOTE:All dimensions are in units of in. (!�CL Z3 00
Printed Date: 09/11/2018
LIYGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza over Hood
Model: GO - 84.00 - S
GO Type 2, Heat and Condensate Hood
Hood Exhaust Exhaust SP Condensate
Model Width(in.) Height(in.) Volume Gutter
Length(in.) (CFM) (in.w.g.) Baffle
GO 84 42 24 1400 0.035 No Baffle No
Selected Options&Accessories:
Option or Accessory Description Material:430 SS 100%Construction
Mounting Height 80 in.off Finished Floor (Hanger brackets-galvanized steel)
Ceiling Enclosures 18 in.High on Left Front Right
Backaplash Panel 80 in High 96 in Long 0 in Wide Features:
Stainless Steel Finish for Higher Corrosion Resistance
Section Data:
Section Length Volume Light Foot
Num. (in.) (CFM) 6P(ln.w.g.) Drain Qty Light Type Candles Weight(Ibs.)
1 84.00 1400.0 1 0.035 1 None 2 Incandescent/CFL 1 38.93 224.000
Exhaust Collar Data:
Section Collar Collar Size(LxW)in. Pos.Off Pos.Off Velocity Mounting Option
Num. Num. or Diameter(in.) Left(in.) Back(in.) (fpm)
1 1 34 x 11 42 21 539 Factory Mounted Exhaust Collar(s)
Utility Cabinet Data:
Descripiton Length Width Height Weight
(in.) (in.) (in.) (lb,)
Left Utility Cabinet 42 12 1 24 43
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 5 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza over Hood
Model: GO - 84.00 - S
0
N
o o U O
N
w W w
2 Z ,
o o C~7 d 0
.� Z = COOKING APPLIANCES Op
O 0 W 2
�
O7 w
> C J
a >
O O rn N>
m Y
o� N Uw rn U N p
Q Q
�Z �>
Q Q W
�d W
C
13NI13VO A-umn cli O
� to
7
C
cc
N
C
O
C
N
E
'O
Q
W
O
Z
NSf
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 6 of 29
D Hanger Bracket Locations
Sec Brkt Distance Off Distance Off
a # # Left(in) Front(in)
�4 1 1 3.50 2.50 ^
1 2 80.50 2.50
can 1 3 3.50 39.50
1 4 80.50 39.50 m
Bracket Mounting Position a „1
for a 4 Bracket Hood z
18.0 f40 3 4 E 171
BACK 9'
D
24.0 FRONT
2
0
0
o-
T1
CD
y
C
(D N
122.0 UL LISTED LIGHT FIXTURE
J 0)
CD N
o Q
x
_Cr Z 80.0
CCnn ABOVE
CD �D FINISHED
0 Q FLOOR
Ch n
C
CD CD
O
7
C N
7 n
60
3
CD MARK: Pizza over Hood
C—
O
tT �
O iv CDCn
N' rr
ON
� � O
�0 �'C.0
ca O CD �
CD o20 N
V O Zr CD
NOTE: All dimensions are in units of in. CL Z3 00
i
Printed Date: 09/11/2018
LIYGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Grease Fan
Model: CUBE-161-7
0 28.88
Model: CUBE-161 -7
Belt Drive Upblast Centrifugal Roof Exhaust
Fan 29.75
19.39
1.75
57.00
Dimensional (15.25)
Quantity 2
Weight w/o Acc's(lb) 72 (12.00)
Weight w/Ace's(lb) 114
Max T Motor Frame Size 145
Roof Opening(in.) 18.5 x 18.5 22.00 SQ
OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR.
Performance 1.2 — — 0.8
Requested Volume(CFM) 2,550
Actual Volume(CFM) 2,550 ------ -
Total External SP(in.wg) 0.769 �'f�
Fan RPM 1183 0.9 \1`� 0.6
Operating Power(hp) 0.68
Elevation(ft) 341 a
C � v
Airstream Temp.(F) 70 20.6 is 0.4 `n
�Air Density(Ib/ft3) 0.074
Drive Loss(%) 7.2 0-
Tip Speed(ft/min) 5,148Q YR1
Static Eff.(°i°) 49 0.3 Q \`,,\ 0.2 Cal
Motor 0.0 0.0
Motor Mounted Yes 0 5 10 15 20 25 30 35
Size(hp) 3/4 Volume(CFM)x 100
Voltage/Cycle/Phase 460/60/3
Enclosure ODP Operating Bhp point
Motor RPM 1725 Operating point at Total External SP
Fan curve
Windings 1 System curve
NEC FLA*(Amps) 1.6 ------Brake horsepower curve
Notes:
All dimensions shown are in units of in. -
`NEC FLA-based on tables 430.248 or 430.250 of !Q .Q
Sound Polder by�Ct1V0 Band for
Electrical Code 2014.Actual motor FLA may vary,
O�Rrltt[Drp�/
for sizing thermal overload,consult factory. "Me"
Sound LwA-A weighted sound power level,based on ANSI S1.4 •/
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA SoneS dBA-A weighted sound pressure level,based on 11.5 dB
attenuation per Octave band at 5 it-dBA levels are not \\J/ AIR
Inlet 74 80 79 76 70 68 64 60 78 66 14.4 licensed by AMCA International MrerYOt'
Sones-calculated using AMCA 301 at 5 it
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 8 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Grease Fan
Model: CUBE-161-7
Model: CUBE-161-7
Belt Drive Upblast Centrifugal Roof Exhaust Fan
Standard Construction Features:
-Aluminum housing-Backward inclined aluminum wheel-Curb cap with
prepunched mounting holes-Motor and drives isolated on shock mounts-Drain
trough-Ball bearing motors-Adjustable motor pulley-Adjustable motor plate-
Fan shaft mounted in ball bearing pillow blocks-Bearings meet or exceed
temperature rating of fan-Static resistant belts-Corrosion resistant fasteners-
Internal lifting lugs
Selected Options &Accessories:
Motor VFD Rated without Shaft Grounding Protection
Standard curb cap size-22 in.square
UL/cUL 762 Listed-"Power Ventilators for Rest.Exh.Appliances"
Switch,NEMA-1,Toggle,Shipped with Unit
Junction Box Mounted&Wired
Roof Curb-Galv.,GPI-22-G12,Under Sized 1.5 in.Total, 1 in.Insulation
Curb Extension-Galv.,VCE-22-G15.25
High Temp Curb Seal Rated for Continuous Duty at 2000 F(Attached)
Grease Trap(PIN 475538)
Heat Baffle(Attached)
Unit Warranty:1 Yr(Standard)
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 9 of 29
i
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Grease Fan
Model: CUBE-161-7
Roof Curb
Model: GPI Material: Galvanized
Standard Construction Features:
- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure-Constructed of either 18 ga
galvanized steel or 0.064 in. aluminum-Straight Sided without a cant-2 in. mounting flange- 3 lb density insulation- Height-
Available from 12 in. to 42 in. as specified in 0.5 in. increments. Notes: -The maximum roof opening dimension should not be
greater than the"Actual'top outside dimension minus 2 in.. -The minimum roof opening dimension should be at least 2.5 in.
more than the damper dimension or recommended duct size. -The Roof Opening Dimension may or may not be the same as
the Structural Opening Dimension. -Damper Tray is optional and must be specified. Tray size is same as damper size.-
Security bars are optional and must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded to the frame and
the frame is welded to the curb.
20.5 20.5
12.0
24.5 24.5
Notes:All dimensions shown are in units of in.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 10 of 29
I
i
I
Printed Date: 09/11/2018
L2fGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Grease Fan
Model: CUBE-161-7
Vented Curb Extension
i
Model: VCE
Standard Construction Features:
-Curb Extension mounts between the fan and the roof curb-Constructed of either 18 ga galvanized or optional 0.064 in.
aluminum- Louvered vents are designed to vent heat in restaurant exhaust applications- Designed to provide required 18 in.
minimum discharge height above roof line when used with an 8 in. high roof curb and Greenheck model spun aluminum upblast
exhaust fan per NFPA 96. NOTE: Damper Trays are not available.
I
21 .0 21 .0
I 0
0 � D
15.3 2.5
22.0 22.0
ISOMETRIC VIEW
Notes:All dimensions shown are in units of in.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 11 of 29
[3GREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza Oven Fan
Model: CUBE-121-3
02
4.88
Model: CUBE-121 -3
Belt Drive Upblast Centrifugal Roof Exhaust
Fan 28.25
17.38
3.44
55.50
o :1— E
Dimensional (15.25)
Quantity 1
Weight w/o Acc's(lb) 58 (12.00)
Weight w/Acc's(lb) 99
Max T Motor Frame Size 56
Roof Opening(in.) 14.5 x 14.5
19.00 SQ
OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR.
Performance 1.2 0.6
Requested Volume(CFM) 1,400 141
Actual Volume(CFM) 1,400 1 0 4 FF?PA4 0.5
Total External SP(in.wg) 0.5
Fan RPM 1414
Operating Power(hp) 0.28 A 0.8 0.4
Elevation(ft) 341 3 p^
c t
Airstream Terri 70
Air Density(lb/ft3) 0.074 0.6 � 0.3
Drive Loss(%} 11.5 `
Tip Speed(ft/min) 4,834 - 0.4 °r 0.2
a
Static Eff.(%) 44 m
0.2 0.1
.--"po� stem. - • .
Motor 0.0 - �'' 0.0
Motor Mounted Yes 0 2 4 6 8 10 12 14 16 18
Size(hp) 1/3 Volume(CFM)x 100
Voltage/Cycle/Phase 115/60/1
Enclosure ODP Operating Bhp point
Motor RPM 1725 Operating point at Total External SP
Fan curve
Windings 1 - - - System curve
NEC FLA*(Amps) 7.2 ------Brake horsepower curve
Notes:
All dimensions shown are in units of in. 7
"NEC FLA-based on tables 430.248 or 430.250 of iQQ
Sound Power by Octave Band National Electrical Code 2014.Actual motor FLA may vary,
for sizing thermal overload,consult factory.
rmaGt
Sound LwA-A weighted sound power level,based on ANSI S1.4
Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA-A weighted sound pressure level,based on 11.5 d6 IjJOUM
attenuation per Octave band at 5 ft-dBA levels are not
Inlet 76 77 82 68 63 64 56 49 75 64 12.7 licensed by AMCA International �rewia
bones-calculated using AMCA 301 at 5 ft
Generated by:jmiiler@buckleyonline.com
CAPS 4,27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 12 of 29
Printed Date: 09/11/2018
LMGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza Oven Fan
Model: CUBE-121-3
Model: CUBE-121 -3
Belt Drive Upblast Centrifugal Roof Exhaust Fan
Standard Construction Features:
-Aluminum housing-Backward inclined aluminum wheel-Curb cap with
prepunched mounting holes-Motor and drives isolated on shock mounts-Drain
trough-Ball bearing motors-Adjustable motor pulley-Adjustable motor plate-
Fan shaft mounted in ball bearing pillow blocks-Bearings meet or exceed
temperature rating of fan-Static resistant belts-Corrosion resistant fasteners-
Internal lifting lugs
Selected Options &Accessories:
UL/cUL 762 Listed-"Power Ventilators for Rest.Exh.Appliances"
Switch,NEMA-1,Toggle,Shipped with Unit
Junction Box Mounted&Wired
Roof Curb-Galv.,GPI-19-G12,Under Sized 1.5 in.Total, 1 in.Insulation
Curb Extension-Galv.,VCE-19-G15.25
Hinged Base(Attached)
High Temp Curb Seal Rated for Continuous Duty at 2000 F(Attached)
Heat Baffle(Attached)
Unit Warranty:1 Yr(Standard)
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 13 of 29
Printed Date: 09/11/2018
L2fGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza Oven Fan
Model: CUBE-121-3
Roof Curb
Model: GPI Material: Galvanized
Standard Construction Features:
- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure-Constructed of either 18 ga
galvanized steel or 0.064 in. aluminum-Straight Sided without a cant-2 in. mounting flange-3 lb density insulation - Height-
Available from 12 in. to 42 in. as specified in 0.5 in. increments. Notes: -The maximum roof opening dimension should not be
greater than the"Actual"top outside dimension minus 2 in..-The minimum roof opening dimension should be at least 2.5 in.
more than the damper dimension or recommended duct size. -The Roof Opening Dimension may or may not be the same as
the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. -
Security bars are optional and must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded to the frame and
the frame is welded to the curb.
17.5 17.5
12.0
21 .5 21 .5
Notes:All dimensions shown are in units of in.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 14 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: Pizza Oven Fan
Model: CUBE-121-3
Vented Curb Extension
Model: VCE
Standard Construction Features:
-Curb Extension mounts between the fan and the roof curb-Constructed of either 18 ga galvanized or optional 0.064 in.
aluminum-Louvered vents are designed to vent heat in restaurant exhaust applications- Designed to provide required 18 in.
minimum discharge height above roof line when used with an 8 in. high roof curb and Greenheck model spun aluminum upblast
exhaust fan per NFPA 96. NOTE: Damper Trays are not available.
18.0 18.0
D 0
15.3 2.5
19.0 19.0
ISOMETRIC VIEW
Notes:All dimensions shown are in units of in.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 15 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
DG-112-H2O
Unit Performance
Design Conditions
Elevation(ft) DB(`Summer W13('F) Winter('F) Supply(CFM) Outdoor Air(CFM)
341 1 88.3 74.2 -8.3 1 5,200 5,200
Unit Specifications
Weight(lb) I Cooling Type Heating Type Unit Installation Unit ETL Listing
714(+/-5%) None Direct Gas-Fired Outdoor/Indoor ANSI Z83.4/CSA 3.7
Configuration
Unit Orientation I Unit Configuration I Outdoor Air Intake Return Air Intake Supply Air Discharge
Horizontal Constant VOollume 100% End - Bottom
Heating Specifications
Gas Pressure Capacity(MBH) Temerature Performance
Type Gas Type Min Max p o 0
(in.wg) (psi) Input Output Rise( F) EAT( F) FLAT( F)
Direct Gas LP 3 0.5 478.0 1 439.7 78.3 -8.3 70.0
Air Performance
Total External SP Total SP Operating Fan
Type Volume RPM
(CFM) (m.wg) (in.wg) Power(hp) Qty Type Size(in.) Drive-Type
Supply 5,200 0.5 1.614 1238 4.2 1 Forward Curve 12 Belt-Drive
Motor
Motor I Qty I Size(hp) Enclosure Efficiency I RPM
Supply Fan Motor 1 1 1 5 ODP NEMA Premium 1725
Electrical Specifications
Power Supply Rating(V/C/P) MCA(A) MOP(A)
Unit 208/60/3 22.8 35
�NTearfR
C
isTETOUS
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 16 of 29
Printed Date: 09/11/2018
[MGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
CONSTRUCTION FEATURES AND ACCESSORIES
Accessories
Installation-Indoor or Outdoor Std I Factory Installed, Lockable, NEMA 3R Disconnect Std
Unit Construction-Single Wall X Weatherhood
Wall Insulation- 1 in.fiberglass-Heat source on X Supply Air Filters-2"MERV 8 X
Base Insulation- 1 in.fiberglass-entire unit base pan Std Outdoor Air Inlet Damper X
Corrosion Resistant Fasteners Std Supply Air Outlet Damper
Access and Connections-Right side when facing intake X Diffuser
Service Access-Removable lift off panels X Roof Curb-GPI X
Unit Finish-G90 Galvanized X Combination Curb
Finish Color Spare Belts
Supply Fan-Belt-drive,forward-curved X Spare Filters
Supply Fan and Motor Vibration isolation-Neoprene X j Motor with Shaft Grounding
Service Outlet Gas Heating Accessories
Unit Controls-Terminals rip with remote panel X
Remote Panel-Kitchen X Pilot Ignition Std
Temperature Control-Discharge control X Flame Sensing-Flame rod X
Supply Fan VFD Flame Safeguard Display
Supply Fan Control Agency Approval-ETL and IRI Std
Melink/Vari-Flow wiring package FM Approved
Recirculation Control Minnesota Code Requirements
Unoccupied Mode(Night Setback) High Gas Pressure Switch
Control Accessories Low Gas Pressure Switch
Heating Inlet Air Sensor 77 Visual Indication Valves
Cooling Inlet Air Sensor External Gas Pressure Regulator(Ships loose)
Dirty Filter Switch Warranty Options
Fire Stat Type III (Ships loose) Unit Warranty-1 Year X
120V/24V Smoke Detector(Ships loose) 5 Year Burner Warranty
Inlet Damper End Switch 10 Year Burner Warranty
External Cooling Lockout Relay
Freeze Protection (Supply Air Low Limit)
Auxiliary Supply Starter Contacts Standard Option Std
Auxiliary Exhaust Starter Contacts Not Included
Airflow Proving Monitoring Contact Included X
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 17 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
Fan Charts And Performance
Supply
Total Volume External SP Total SP RPM Operating M I Size Fan
(CFM) (in.wg) (in.wg) Power(hp) Qty (hp) Qty Type Drive-Type
5,200 0.5 1.614 1238 4.2 1 1 5 1 Forward Curve Belt
Pressure Drop
Weatherhood Filter Damper Cooling Heating I External I Total
0.094 1 0.22 - 0.8 0.5 1 1.614
AccordanceSound Performance in
Sound Power by Octave Band Lwa dBA Sones
62.5 125 250 500 1000 2000 1 4000 8000
99 92 1 85 1 84 84 82 1 81 1 75 1 89 78 33
Supply Fan
2.8 �-- , 7
r� FRPM 8
2.4
2.0 5
1.6 4
1.2 3
cc 0.8 s 2 m
0.4
0.0
0
0 1 2 3 4 5 6 7 8
Volume(CFM)x 1,000
Operating Bhp point
Operating point at Total External TP
Fan curve
System curve
Brake horsepower curve
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 18 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-1-120
Heating Specifications
Heating Performance
Gas Pressure Capacity(M13H) Performance
Temperature
Type Gas Type Min Max Input Output Rise(°F) EAT(°F) LAT(°F)
(in.wg) (Psi)
Direct Gas LP 3 0.5 478.0 439.7 78.3 -8.3 70.0
Gas Train Details
Redundant Electronic Visual Proof of
Internal Hydraulic Gas Pressure External
Main Modulating Pilot Valve Indication Closure
Valves Valve Regulator Valve Valve Main Valve(s) Switch(es) Regulator
Std Std Std Std - - - - -
Additional Heating Information
Agency Approvals Flame
Temperature Ignition
ETL and IRI FM Approved Minnesota Control Flame Sensing Control CO2 Sensor Safeguard
Code Display
Std - - Discharge Flame Rod Pilot - -
Unit Details
92 o thermal efficiency 10 second pre-purge sequence
Cast aluminum burner manifold with stainless steel mixing plates Low fire start
Electronic modulation burner control
Gas Connections
ELECTRICAL
CONNECTION
47.500
8.000
O 0
1" NPT GAS 47.500
CONNECTION
8.000
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 19 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
30.244 86.192
oC� 33.676
0 0
ELEVATION VIEW
'Standard configuration for unit access is on the right-hand side,when looking into the unit intake in the direction of airflow.
'Note:Order of unit sections is from intake of unit to discharge of unit.
'Sections included on this unit: Filter Section,Heating Section
Insulation:Duct Liner,from Burner Section through end of unit.
V-BANK FILTER BURNER
30.244 86.192
Eff
SUPPLY 18.000 36.474
DUCT
9.237
ACCESS SIDE ACCESS SIDE-
CONTROL CENTER
7.346
16.000
PLAN VIEW
Standard configuration for unit access is on the right-hand side,when looking into the unit intake in the direction of airflow.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 20 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
36.474
END VIEW
1.096
32.154
34.674
1.424
1.446 1.446
33.581
36.473
INTAKE VIEW
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 21 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
NOTE: Roof Opening Requirements:
Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in.on all sides.
For example: If the duct size is 14 x 14 in.square,the minimum roof opening size is 14.5 x 14.5 in.square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in.between the roof opening and the roof curb.
For example: If the roof curb is 75 x 30 in.square,the maximum roof opening is 71.5 x 26.5 in.inches square.
82.500
CURB LENGTH ACTUAL
16.000
..................................
---------- ----------- --- -
i
7.25
i
i
32.500
SouctY 18.000 CURB WIDTH
i
ACTUAL
7.25
L---------------------------------------
__
5.85
NOTE: The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design,to prevent
water infiltration.MUA Unit supports are shipped loose with unit.
FOOTPRINT VIEW
UNIT BASE
1.00
I�-1.63 INSULATION �1.15
0.82
CURB
INSIDE OF RAILS 34.15
CURB VIEW
Notes: All dimensions shown are in in.'s.
Curb Dimenision: Length = 82.5 in. Width = 32.5 in. Height = 12 in.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 22 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
Recommended Minimum Combustible Clearances
Floor Top Sides Ends
Insulated/Units 0 in. 0 in. 0 in. 0 in.
Non-Insulated/Units 0 in. 6 in. 6 in. 6 in.
Clearance to combustibles is defined as the minimum distance required between the heating source and the
adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the
ambient temperature.
Recommended Minimum Service Clearances
Housing 32 and less 42 in.on the controls side of the unit
Housing 35 and higher 48 in. on the controls side of the unit
To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances
should be 6 in. wider than the width of the module itself.
Generated by:jmiller@buckleyontine.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 23 of 29
Printed Date: 09/11/2018
L2fGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
L,b D3T1 ST,OL
MAIN—
To µ Building Value in Air.GREENHECK
c�_ LS MOTOR
GD21N402A010N10CM19
CAUTION
UNR SWML SEEOFF EDNAGCpiONiLEsVnll N.E.C.
ER MUST BE OFF WILE SERVICING.
NOTES
MI3 L FO CONOULTORS
ORR TE TERMI NALS RATEDIEB LE55 THAN 1 W AMPS.
FU] TS°C FOR TERMINALS RATED 1 W AMPS OR MORE.
FIELD CONTROL W WNO RESISTANCE SHOULD
NOT EXCEED 0.750HM.
FIELD WIRED
FACTORY SIIPPLJED AND WIRED
0v WIRE COLOR CODE
81( BIACN BL SLUE SR
LT BROWN
GY OMY BL LIGHT SL O
PEO E
%NN PUNPLE� R
wNITE
75 VA LEGEND
2av C ALET DI`RAM
Ot I INLET DAMPER
OS, MAN GSLONNECTBYATCH
FSC FIRE SVSTE CONTALT
FSC FL GUARD
SAFE GIIPAD
W FUSE
INLET DAMPER HIGH UM CONTROL MM
MOTOR
MOD MOT RATING VALVE
STt 52 SC L IXA MOTORS.
OVERLOAD
iF- G p5 SS AZ A, PRVFAN RELAv W AIR PROVING SWITCX
RF SUPPLY FAN RELAY
XEAT RELAY
32 FANSYATCN
. NEZSG SPA;ANO COOL SWITCX
K GENERATOR
STIR MOTOR STARTER
T.TRANSFORMER
T.NBCNAROE AIR SENSOR
—INLET AIR SENSOR-MEAT
PILOT VALVE
VY MAN VKVE
Tt SUPPLYFAN
11 16
�� R e A2 At POST NEAT
(I,s V) ® s FSG L3 a(„SV)
ORECT—CONTROL
ENSp S
NLCt SG
----------------
10
O3 B
Pffi Pffi
C NO NC C
M ,D SEC 2— VA
e e X PE STAT. TEMP E
s 8 S
z WirYq Twngw:M13 Doc NUMBER:— REV—
Manufacturer reserves the right to change, modify, or improve this product at anytime
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 24 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
Roof Curb - GPI
CONSTRUCTION FEATURES
•Welded aluminum(0.064 in.)or galvanized steel(18 ga.)
Straight sided•2 in.mounting flange•1 in.,3 lb.density
insulation•Wood nailer
Dimension Description Value (in.)
A Length 82.5
C B Width 32.5
C Height 12
*All dimensions are actual
GPI Curb Weight: 47 lb
ADDITIONAL NOTES
•The Roof Opening Dimension may NOT match the
Structural Roof Support Dimension.
•Curbs with length> 143.5 will ship knocked-down
•Curbs with length> 119.5 may ship knocked-down,
dependent on manufacturing location
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 25 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
Corner Weights
149 lb 187 lb
Unit
167 lb 211 lb
Note: Estimated corner weights are shown looking down
on unit and airflow from left to right. Weights are applied
at the base of the unit. Images not drawn to scale.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 26 of 29
Printed Date: 09/11/2018
LNGREENHECK Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
KSCP
REMOTE CONTROL PANEL
STANDARD CONSTRUCTION FEATURES
•Toggle switches and stainless face plate for wall mounting.
•Junction box included.
3.78
C)
4.50
3.81
2.50
FP
4.56
" Location of switches, lights and controls may vary.
NOTES:All dimensions shown are in units of inches
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jeffjobs\West Mountain Kitchen.gfcj Page 27 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
SEQUENCE OF OPERATIONS
Unit Controls
The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
• Supply fan motor starter(contactor and overload)
• Factory mounted and wired outdoor air inlet damper with actuator
• Remote Control Panel
Kitchen Remote Control Panel
A kitchen remote control panel shall be shipped loose with following switches for controlling the operation of the
unit:
• Supply Switch
• Heat Switch
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Outdoor air inlet damper actuator is energized
• Supply Fan Is Enabled
Supply Fan Sequence
The supply fan is configured for constant volume operation. The fan speed is set to the design fan RPM at the
factory through the use of belts and sheaves.Adjustment or replacement of belts/sheaves is necessary to balance
the supply airflow. The supply fan speed is not to be modulated.
Heating Control
A heating enable signal must be present and the supply fan must enabled before the unit will enable heating.
Heating Inlet Air Sensor(Heating Lockout)
The heating will be locked out when the outside air temperature is above the heating inlet air sensor set point
(typical 65 F, adj.)
Direct Gas Fired Heating (Discharge Control)
The gas control amplifier located in the unit shall modulate the heating to maintain a supply temperature set
point(55 F-90 F, adj.).
• The set point is adjusted in the unit control center.
Generated by:jmiller@buckleyonline.com
CAPS 4.27.1405 R:\Job Files\Greenheck CAPS\Jefrjjobs\West Mountain Kitchen.gfcj Page 28 of 29
LNGREENHECK Printed Date: 09/11/2018
Job: West Mountain Kitchen
Building Value in Air. Mark: MAU
Model: DG-112-H20
Warranty Information
Limited Warranty - Unit
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1
year(s)from the purchase date.Any component which proves defective during the warranty period will be
repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid.
The warranty does not include labor costs associated with troubleshooting, removal, or installation.
Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use,
repair, or operation of any Greenheck product.
This warranty is exclusive, and is in lieu of all other warranties,whether written, oral or implied, including
the warranty of merchantability and the warranty of fitness for a particular purpose.