Fire Alarm System Inspection mt, lue$ r Town of Queensbury FIRE MARSHAL'S OFFICE FIRE ALARM SYSTEM INSPECTION DATE: 11 FA CONTRACTOR At) LOCATION: 4L() ( 41ft_ CENTRAL STATION TIE IN AND CONFIRMED COPY OF LICENSE FIRE ALARM PLANS AND CUT SHEETS PROVIDED RECORD OF COMPLETION PROVIDED NFPA 72 INSPECTION REPORT PROVIDED / FIRE DEVICES VISIBLE DO NOT RESET STICKER ON PANEL ZONE CHART PROVIDED STROBE FUNCTION ON SILENCE GA ;)DISABLED ALL REQUIED KEYS PROVIDED FUNCTION TEST: PULL STATION SMOKE DETECTOR HEAT DETECTOR \� HORN STROBE HVAC SHUTDOWN ANSUL TIE IN FUEL ISLAND TIE IN TAMPER y FLOW CO DETECTION ""'S SYSTEM RECORD OF COMPLETION LF This form is to be completed by the system installation contractor at the time of system acceptance and approval.` -" It shall be permitted to modem this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets,data,or calculations as necessary to provide a complete record. Form Completion Date: 10/17/2019 Supplemental Pages Attached: 1. PROPERTY INFORMATION Name of property: Aldi#18R Queensbury Address: 708 Upper Glen Street Queensbury NY 12804 Description of property: Retail store Name of property representative: Address: Phone: Fax: E-mail: 2. INSTALLATION,SERVICE,TESTING,AND MONITORING INFORMATION Installation contractor: CNC Microtech Address: 14 Jupiter Lane Ste 4 Albany NY 12205 Phone: 518-366-1941 Fax: E-mail: ctasse@cncmicrotech.com Service organization: Address: Phone: Fax: E-mail: Testing organization: Protectionl Address: 4221 W John Carpenter FWY Irving Tx.75063 Phone: 866-889-9459 Fax: E-mail: Effective date for test and inspection contract: Monitoring organization: Protectionl Address: 4221 W John Carpenter FWY Irving TX.75043 Phone: Fax: E-mail: Account number: Phone line 1: Phone line 2: Means of transmission: Cellular Entity to which alarms are retransmitted: Warren County Serriff Phone: 518-743-2501 3. DOCUMENTATION On-site location of the required record documents and site-specific software: Document Box near fire panel 4. DESCRIPTION OF SYSTEM OR SERVICE This is a: ®New system ❑Modification to existing system Permit number: NFPA 72 edition: 4.1 Control Unit Manufacturer: Firelite Model number: ES-20OX 4.2 Software and Firmware Firmware revision number: 4.3 Alarm Verification ®This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds Copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 120VAC Control panel amps: 20A Overcurrent protection: Type: Breaker Amps: 20A Branch circuit disconnecting means location: Electrical Panel Number: 5.1.2 Secondary Power Type of secondary power: Battery Location,if remote from the plant: Calculated capacity of secondary power to drive the system: In standby mode(hours): 24 hours In alarm mode(minutes): 5 minutes 5.2 Control Unit ® This system does not have power extender panels ❑ Power extender panels are listed on supplementary sheet A 6. CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line Y Device Power Initiating Device Y Notification Appliance Y Other(specify): 7. REMOTE ANNUNCIATORS Type Location LED Front Exit 8. INITIATING DEVICES Addressable or Type Quantity Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 1 Addressable Alarm Smoke Detectors 2 Addressable Alarm Duct Smoke Detectors 2 Addressable Supervisory Heat Detectors Gas Detectors Waterflow Switches 1 Addressable Alarm Tamper Switches 2 Addressable Supervisory Copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type Quantity Description Audible Visible 9 Strobe Combination Audible and Visible 13 Horn/strobe 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices HVAC Shutdown Fire/Smoke Dampers Door Unlocking Elevator Recall Elevator Shunt Trip 11. INTERCONNECTED SYSTEMS ® This system does not have interconnected systems. ❑ Interconnected systems are listed on supplementary sheet 12. CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system s ccrfied herein has been installed according to all NFPA standards cited herein. Signed: _W Printed name: Angela Antoniato Date: 10/17/19 Organization: Protectionl Title: NAI PM Phone: 516-743-2296 12.2 System Operational Test This system s ecified herein has tested according to all NFPA standards cited herein. Signed: �W Printed name: Angela Antoniato Date: 10/17/19 Organization: Protectionl Title: NAI PM Phone: 516-743-2296 12.3 Acceptance Test Date and time of acceptance test: 10/17/2019 Installing contractor representative: Ian Poultney Testing contractor representative: Ian Poultney Property representative: Brandon Vance Aldi Construction Manager AHJ representative: Copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. Fire Department & Project Submittal for Monitoring of the Facility Sprinkler System With Carbon Monoxide Detection Submitted per NFPA 72 & NFPA 13 At Aldi 18 176 Quaker Road Queensbury, NY 12804 Remote Station Monitoring: Via Sole Source Cellular ADT LLC DBA Protection 1 4221 W. John Carpenter Fwy Irving, TX 75063 UUFX-S2684-20 877-357-1808 ADT LLC DBA Protection 1 Protection PO Box 3 Lac,DBA Halfmoon, NY 12065 518-375-1201 ARCHWAY Joel Damminga S Y S T E M S Archway Systems 17020 E 40 Hwy, Suite 1 Independence, MO. 64055 (816) 709-3358 Intrusion Alarm Systems I D7412GV4 Control Panel D7412GV4 Control Panel www.boschsecurity.com BOSCH Invented for life ► Fully integrated intrusion, fire, and access control allows users to interface with one system instead of three '—� ► Conettix IP-based communication options provide 1±77 F high-speed, secure alarm transport and control through connection of wired and/or wireless cellular ��---�� network interfaces ► Up to 8 programmable areas each supporting both with perimeter and interior points with your choice of touch screen,ATM style, or LED keypads ► 75 points with flexible configuration options to meet multiple installation requirements P. OPTIONAL GV4 version 2.00 firmware upgrade available (NEW) GV4 panels are the premier commercial control panel Four alarm-output patterns line from Bosch. GV4 panels integrate intrusion, fire Programmable bell test and access control providing one simple user interface System Response for all systems. With the ability to adapt to large and High-performance micro-controller provides small applications,the D7412GV4 provides up to 75 industry-leading system response individually identified points that can be split into 8 High-speed device bus (NEW) areas. The control panel includes a communicator that 31 custom point indexes, including fire supervisory sends events to selected public switched telephone Selectable point response time network (PSTN), IP network, or cellular network Cross point capability destinations through four programmable route groups. Fire alarm verification With the D7412GV4 you can: Fire inspector's local test • Monitor alarm points for intruder or fire alarms while Watch mode operating keypads and other outputs Scheduled events (SKEDs) arm, disarm, bypass and • Program all system functions local or remote using unbypass points,control relays, control authority Remote Programming Software (RPS) or by using levels, and control door access basic programming through the keypad. User Interface • Add up to two doors of access control using the Supervision of up to 16 keypads (up to 32 optional D9210C Access Control Interface Module. unsupervised keypads can be used) Functions • Remote Programming Software (RPS) Lite allows end users to perform control panel management tasks- Programmable Outputs Add/Delete/Change user passcodes and authorities, • 2 A alarm power at 12 VDC view and print the panel history event log • 1.4 A auxiliary power at 12 VDC 2 D7412GV4 Control • Custom keypad text is fully programmable, including Programmable Passcode-controlled Menu List remote programming The system prompts users to enter a passcode prior to • Full function command menu including Custom viewing the keypad menu. The keypad display shows Functions the user the menu options allowed according to the • Authority by area and 16-character name for each user's authority level. Passcode-controlled menus user provide users only with the options and information • 14 custom authority levels control user's authority to pertinent to them, simplifying system operation. change,add,or delete passcodes or access control credentials; to disarm or bypass points; and to start Flexible Control system tests The system provides the flexibility to select added convenience or high security. For example, you can Area Configurations restrict passcode arming and disarming to a keypad's Area programming offers a wide selection of different immediate local area, even if the user has access to system configurations. Each area is assigned an other areas. This is particularly useful for high security account number to define annunciation, control, and areas, where a user may have access to the area, but reporting functions. Multiple areas can be linked to a would prefer to only disarm the area individually rather shared area which is automatically controlled (hallway than with the rest of the system. Another option is to or lobby). Area arming can be conditional on other program the system to disarm all areas the user can areas (master or associate). Any area can be access from any keypad. configured for perimeter and interior arming, not requiring a separate area for this function. Invisible Walk Test A menu item allows the user to test invisible 24-hour Custom Functions points within the scope of the keypad without sending For added convenience, Custom Functions can be a report to the central station. programmed to eliminate keystrokes for users allowing the installer to program an easy command for a System Users complicate function. For example, a custom function The system supports up to 399 users, each can have a can be written to bypass a group of points and arm passcode, an access token and a wireless keyfob. User the system, allowing the user to perform this function passcodes contain three to six digits. Passcodes can with one easy command.This can be used to control a be assigned to one of 14 customized authority levels in particular room, or even a single door allowing each area and can be restricted to operate only during customized access. In additions, Custom Functions certain times. can be activated with a token or card, or automatically Communication Formats as a scheduled event (SKED) providing further The D7412GV4 Control Panel prioritizes and sends flexibility and ease of use. reports in Contact ID or Modem Illaz communications Door-Activated Custom Function formats to four route groups. Each group has a A custom function activates when user credentials are programmable primary and backup destination. presented to a D9210C Access Control Interface The D7412GV4 provides flexible communications for Module door controller's reader. The custom function most central stations with reporting capabilities such behaves as though the user performed a function at as: the keypad associated with the door controller. Individual point numbers • Opening or closing reports by user and area number Passcode Security Remote programming attempts For high security applications, GV4 can be configured Diagnostic reports for several different passcode options. • Dual Authentication— requires a user to enter their IP Communication passcode and also use a token or card (NEW). The D7412GV4 uses the B420 Ethernet • Two-Man Rule-Requires two people with two unique Communication Module, DX4020, and/or the passcodes to be present at the time of opening. ITS-DX4020-G Cellular Communicator to communicate • Early Ambush-Allows users to verify that the facility with the Conettix D6600 and D6100i Communications is safe by requiring two passcode entries at different Receiver/Gateways. Using Conettix IP communication keypads within the same area, sending a duress event offers a secure path that includes anti-replay/anti- if the user does not enter the passcode a second time substitution features and provides enhanced security after inspecting the premises. with encryption. The B420, DX4020 and ITS-DX4020-G Easy Exit Control can all be used for remote programming. The D7412GV4 Control Panel changes from one armed GV4 is the first Security Control panel to support DNS state to another armed state without disarming. For (Domain Name System) for both remote programming example, if you change the state from Perimeter Arm and central station communication. DNS provides ease to Master Arm, the control panel complies and reports of use, eliminating the need to use static IP addresses the change. Easy Exit Control reduces the number of as your reporting destination,and accommodates a keystrokes, simplifying system operation. simple solution for central station disaster recovery. D7412GV4 Control IP Setup is available via the installer keypad menus than receiving several calls each day. When the event and the remote programming software, eliminating the log reaches a programmed threshold of stored events, need to use complicated internet programming tools it can send an optional report to a receiver. such as ARP and Telnet (NEW). Scheduled Events (SKEDs) Communication Paths The internal clock and calendar start individually D7412GV4 Control Panels accommodate up to four scheduled events (SKEDs). SKEDs perform functions separate destinations for primary, alternate, and such as arm or disarm, relay control, or point backup receivers for automatic test reports. bypassing. The D7412GV4 Control Panel offers: When resetting alarms or arming or disarming a 40 scheduled events with up to 25 different functions system, the user is identified by name and number. Eight opening windows and eight closing windows Eight user windows Firmware Updates (NEW) • Day-of-week,date-of-month, or holiday only schedules Remote firmware updates using the RPS Firmware Four holiday schedules of 366 days each (leap year) Update wizard through the IP connection (13420 Ethernet Communication Module) as well as an on-site Fire Test flash update key, provides for easy feature When a user activates Fire Test Mode, the control enhancements without replacing ROM chips. panel suppresses all reports to the central station. The keypad and annunciator show all testing data. An *For GV4 version 2.00 firmware update information, automatic sensor reset feature saves time; you do not refer to the, "GV4 version 2.00 firmware updates" need to reset the sensors manually. At the end of test, datasheet to learn more about key enhancements, and supported products. the keypad shows the number of untested points. A wide variety of input options Programming, Diagnostics and Controls Each point: Installers can program locally or remotely through RPS • Accommodates normally-open (NO) and as well as basic keypad programming. A programmable normally-closed (NC) devices with end-of-line (EOL) system passcode prevents unauthorized remote resistor supervision. programming. • Is programmable for fire,fire supervisory, or intrusion application. Two Data Buses • Can be hard-wired, addressable,or wireless. GV4 provides 2 data buses which support a wide array of components.The SDI bus supports keypads access Security and Fire Detection and communications modules and also allows The D7412GV4 Control Panel provides eight on-board connection of existing components in a retrofit points,and up to 67 additional off-board points. You application. The new SD12 bus supports input and can program individual points to monitor all types of output devices as well as a new interface module, and burglar alarms, fire alarms, and supervision devices. an Ethernet communicator. SD12 allows these devices Access Control to be mounted up to 1000 ft (305 m) from the control The D7412GV4 provides custom door strike, point panel, providing installation convenience and shunt and auto disarming response by area. There are flexibility. 14 panel-wide access levels with both manual and Commercial Fire Alarm Support scheduled control. Suitable for Commercial Fire (UL 864, 91h Edition) Store,view, or print access events such as: applications. • Access granted • No entry Certifications and approvals • Request-to-enter • Request-to-exit USA: Wireless Interface The B820 SD12 Inovonics Interface Module connects UL365 Police Station Connected Burglar Alarm an Inovonics EN4200 Serial Receiver to the control Units and Systems panel SD12 bus, allowing this UL Listed (NEW) UL609 Local Burglar Alarm Units and Systems wireless system to be programmed locally via the UL636 Holdup Alarm Units and Systems panel keypad, as well as remotely through RPS. UL 864 Control Units and Accessories for Fire Alarm Event Log The event log stores up to 1,000 local and transmitted Systems(Commercial events. The event log includes time, date, event, area, UL985 Household Fire Warning System Units point, user number, and transmission status (NEW). UL1023 Household Burglar Alarm System Units View the event log from a keypad or use RPS to remotely retrieve event information. RPS operators UL1076 Proprietary Burglar Alarm Units and can retrieve events periodically using one call, rather Systems UL 1610 Central Station Burglar Alarm Units Control ANSI/SIA CP-01:2010 False Alarm Reduction ZX794Z Long Range PIR Detector CSFM California Office of The State Fire Marshall ZX835 TriTech Microwave/PIR Detector 7165-1615:0242 Control Unit (Commercial) ZX935Z PIR Detector FM 3010 ZX938Z PIR Detector FCC Part 15 Class B, ZX970 PIR/Microwave Detector Part 68 Bosch conventional detectors,including Professional Series,Blue Line Gent,Blue Line,Classic Line,Commercial Line,and Ceiling Mount Region Certification motion detectors,as well as glass break,seismic,request-to-exit, USA UL 20130918-S1871,UL 864,ANSI/SIA photoelectric,heat,and smoke detectors. CP-01-2010,UL 1076,UL 1610,UL Enclosures 1635,UL 365,UL 609,UL 985,UL 1023,UL 636 D8103 Universal Enclosure CSFM see our website D8108AAttock-resistant Enclosure FDNY- #6174 UL 864 9th Edition CoA D8109 Fire Enclosure Canada ULC 20140407-S1871;ULC/ORD-C1076- Magnetic Contacts M1986,CAN/ULC-S304-06,CAN/ULC- S303-M91,CAN-ORD-C1023 Bosch magnetic contacts include recessed,terminal connection, Brazil ANATEL 1083-12-1855 miniature,overhead door,and surface mount. installation/configuration notes Modules Compatible Products Conettix B426 Ethernet Communication Module(NEW) Keypads B208 Octo-input Module D1265 Touch Screen Keypad B308 Octo-output Module D1255 Series Keypads B520 Auxiliary Power Supply Module(NEW) (D1255,D1255W,D1255B,D1255RB,D1265) B820 SDI2lnovonics Interface Module D1260 Series Keypads Conettix B420 Ethernet Communication Module (D1260,D1260W,D1260R,D1260BLK,D1260B) Conettix ITS-DX4020-G Cellular Integrated Communicator D1256RB Fire Keypad Conettix DX4020 Network Interface Module D1257RB Remote Fire Alarm Annunciator Conettix DX4010V2 USB/Serial Interface Module D720 Series Keypads (D720,D720W,D720R,D720B) Conettix C900V2 Dialer Capture Module D279A Independent Zone Control D 113 Battery Lead Supervision Module D125B Dual Class B Initiating Module Detectors D127 Reversing Relay Module D278S Four-wire Addressable Detector Base,12 VDC D285/TH Photoelectric Smoke Detector Heads D 129 Class A Initiating Module D298S Addressable Detector Base,24 VDC D130 Auxiliary Relay Module D7050 Series Addressable Photoelectric Smoke and Smoke Heat D185 Reverse Polarity Signaling Module Detector Heads D 192G Notification Appliance Circuit Module F220-B6PM/S 12/24 VDC Addressable Detector Bases with POPITs D928 Phone Line Switcher FCC-380 Carbon Monoxide Detector D5060 MUX Programmer MX775i Addressable PIR Detector D8125 POPEX Point Expander MX794i Long Range Multiplex PIR Detector D8128D OctoPOPIT Eight-point Expander MX934i Addressable PIR Detector D8125MUX Point Expander MX938i Addressable PIR Detector D8125INV Wireless Interface Module ZX776Z PIR Detector D8129 Octo-relay Module 5 D7412GV4 Control D8130 Door Release Module EN1235D Beltclip Pendant Transmitter(Double-button) D9127 Series POPIT Modules EN1235DF Fixed-location Transmitter(Double-button) D9131A Parallel Printer Interface Module EN1235S Beltclip Pendant Transmitter(Single-button) D9210C Access Control Interface Module EN1235SF Fixed-location Transmitter(Single-button) DS7432 Eight-input Remote Module EN1247 Glass-break Detector Transmitter DS7457i Series Single-zone Multiplex Input Modules EN1249 Bill Trap Transmitter DS7460i Two-input Module EN1242 Smoke Detector Transmitter DS7461i Single-input Multiplex Module EN1260 Wall Mount Motion Detector DS7465i Input and Output Module EN1261HT High Traffic Motion Detector ICP-SDI-9114 SDI Splitter EN1262 Motion Detector with Pet Immunity Transformers EM 1265 360°Ceiling Mount Motion Detector D1640 Transformer EN4200 Serial Receiver D1640-CA Transformer EN5040-T High Power Repeater with Transformer Programming includedParts RPS or RPS-LITE Remote Programming Software The D7412GV4 includes the following parts: Readers Quant Component ARD-1110 iCLASS Mullion Reader 1 D7412GV4 Board ARD-1140 iCLASS Switchplate Reader 1 Mounting Skirt ARD-RK40-09 iCLASS PIN Reader 1 Faceplate with D7412GV4 Label ARD-VSMART iCLASS Reader i Literature pack • Installation Instructions D8223 Prox Pro Reader Owners Manual • Release Notes D8224 Mullion Reader 1 Literature CD containing all product literature D8224-SP Switch Plate Reader D8225 Mini Mullion Reader The available kits come with the parts indicated in the following table: D8301W Low-profile Proximity Readers Kits Components A -B -C -D Wireless D7412GV4 Board 1 1 1 1 B820 SDI2 Inovonics Interface Module D 101 Lock and Key Set 1 1 1 SDI2 Inovonics Interface and Receiver Kit.Includes B820 and EN4200 (ENKIT-SDI2) D101F Lock and Key Set 1 EN1210 Universal Transmitter(Single-input) D122 Dual Battery Harness 1 EN1210EOL Universal Transmitter with EOL Resistor D161 Dual Modular Phone Cord 2 EN 1210W Door-Window Transmitter with Reed Switch D928 Dual Phone Line Switcher 1 EN 1215EOL Universal Transmitter with Wall Tamper,Reed Switch,and D1640 Transformer 1 1 1 EOL Resistor D6103 Enclosure 1 EN 1223D Water-resistant Pendant Transmitter(Double-button) D8103 Enclosure 1 EN1223S Water-resistant Pendant Transmitter(Single-button) D8108AAttack-resistant Enclosure 1 EN1224-ON Multiple-Condition Pendant Transmitter EN1233D Necklace Pendant Transmitter(Double-button) D8109 Fire Enclosure 1 EN1233S Necklace Pendant Transmitter(Single-button) Control Panel specificationsTechnical D7412GV4-B Fire/Burglar Package Communications Contains one PCB, one dual battery harness, two telephone cords, one telephone line switcher, one Telephone One telephone line transformer, and one fire enclosure. Connection: D928 Dual Phone Line Module required for Order number D7412GV4-B two telephone lines D7412GV4-C Standard Burglar Package Environmental Considerations Contains one PCB, one lock and key set, one Relative Humidity: 5%to93%at+30°C(+86°F), transformer, and one universal enclosure. non-condensing Order number D7412GV4-C Temperature(Operating): 0°C to+50°C(+32°F to+122°F) D7412GV4-D Burglar PAckage Contains one PCB, one lock and key set, one Number of... transformer, and one D6103 Enclosure. Order number D7412GV4-D Areas: 8 Accessories Card Readers(Doors): 2 SDI2 Inovonics Interface and Receiver Kit Credentials(Tokens): 399 Kit containing B820 and EN4200 for use on SD12 bus panels. Custom Functions: 4 Order number ENKIT-SDI2 Events: Up to 1000 D928 Dual Phone Line Switcher PasscodeUsers: 399,plus 1 service passcode Allows the control panel to operate over and supervise two separate phone lines. Only one D162 phone cord Parallel Printers: 1 is supplied. Two additional D161 or D162 phone cords Points: 75(8 on-board,up to 67 are required. off-board) Order number D928 Programmable Relay Outputs: 67 D101 Lock and Key Set RFPoints: 67 Short-body lock set with one key supplied. Uses the D102 (#1358) replacement key. SKEDs: 40 Order number D101 Power Requirements D122 Dual Battery Harness Harness with circuit breaker. Connects two batteries Current Draw(Maximum): 300mA to a compatible control panel. Output(Alarm): 2 A at 12 VDC Order number D122 Output(Auxiliary,Continuous 1.4 A at 12 VDC nominal D122L Dual Battery Harness with Long Leads Power,and Switched Auxiliary Color-coded harness with circuit breaker and leads combined): measuring 89 cm (35 in.). Connects 12 V batteries to Voltage(Operating): 12 VDC nominal compatible control panels. Order number D122L Voltage(AC): 16.5 VAC 40 VA plug-in transformer(D1640) D126 Standby Battery(12 V,7 Ah) A rechargeable sealed lead-acid power supply used as Trademarks a secondary power supply or in auxiliary or ancillary functions. Inovonics is a trademark of Inovonics Wireless Corporation. Order number D126 Ordering information D1218 Battery(12 V, 18 Ah) A 12 V sealed lead-acid battery for standby and D7412GV4 75 Point Control Communicator auxiliary power with two bolt-fastened terminals. Order number D7412GV4 Includes hardware for attaching battery leads or spade D7412GV4-A Attack-resistant Package connectors Contains one PCB, one transformer, and one attack- Order number D1218 resistant enclosure. Order number D7412GV4-A Control D1224 Battery(12 V,26-28 Ah) D8109 Fire Enclosure A 12 V sealed lead-acid battery for standby and Red steel enclosure measuring 40.6 cm x 40.6 cm x 8.9 auxiliary power with two bolt-fastened terminals. cm (16 in. x 16 in. x 3.5 in). UL Listed. Includes a lock Includes hardware for attaching battery leads or spade and key set. connectors. Order number D8109 Order number D1224 Software Options D1238 Battery(12 V,38 Ah) RPS Kit(USB) A 12 V sealed lead-acid battery for standby and Account management and control panel programming auxiliary power with two bolt-fastened terminals. software with USB security key (dongle). Includes hardware for attaching battery leads or spade Order number D5500C-USB connectors. Order number D1238 D137 Mounting Bracket Used to mount accessory modules in D8103, D8108A, and D8109 enclosures. Order number D137 D138 Mounting Bracket,Right Angle Used to mount accessory modules in D8103, D8108A, and D8109 enclosures. Order number D138 D1640 Transformer System transformer rated at 16.5 VAC,40 VA. Order number D1640 D8004 Transformer Enclosure For applications such as fire alarm that might require a transformer enclosure. Order number D8004 D9002-5 Mounting Skirt Mounts inside D8103, D8108A, and D8109 enclosures. Can accept up to six standard 7.62 cm x 12.7 cm (3 in. x 5 in.) cards. Order number D9002.5 D110 Tamper Switch Screw-on tamper switch that fits all enclosures. Shipped in packages of two. Order number Dii0 ICP-EZTS Dual Tamper Switch Combination tamper switch with a wire loop for additional tamper outputs. Order number ICP•EZTS D8108A Attack Resistant Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). UL Listed. Includes lock and key set. B520, B4512, and B5512 require the B12 mounting plate. Order number D8108A D8103 Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). Order number D8103 Control Represented by: Americas: Europe,Middle East,Africa: Asia•Pacific: China: America Latina. Bosch Security Systems,Inc. Bosch Security Systems B.V. Robert Bosch(SEA)Pte Ltd,Security Bosch(Shanghai)Security Systems Ltd. Robert Bosch Ltda Security Systems Division 130 Perinton Parkway P.O.Box 80002 Systems 201 Building,No.333 Fuquan Road Via Anhanguera,Km 98 Fairport.New York,14450,USA 5617 BA Eindhoven,The Netherlands 11 Bishan Street 21 North ISP CEP 13065900 Phone:+1 800 2890096 Phone:+3140 2577 284 Singapore 573943 Changning District,Shanghai Campinas,Sao Paulo,Brazil Fax:+1 585 223 9180 Fax:+31 40 2577 330 Phone:+65 6571 2808 200335 China Phone:+55 19 2103 2860 security.saleseus.bosch.com emea.securitysystemsebosch.com Fax:+65 6571 2699 Phone+86 21 22181111 Fax:+55 19 2103 2862 www.boschsecurity.us www.boschsecurity.com apr.securitysystemsebosch.com 1ax:+862122182398 latam.boschsecurityebosch.com www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com ®Bosch Security Systems 2015)Data subject to change without notice 2495670155)en,V13,26.Jan 2015 ® AL802ULADA MAltronIX NAC Power Extenders Rev.AL802ULADA_11072012 Overview AL802ULADA are extremely cost effective voltage regulated remote NAC Power Extenders. They may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC)expansion(supports ADA requirements)and providing auxiliary power to support system accessories. AL802ULADA Specifications Agency Listings: Supervision: • UL Listed Control Units for Fire Protective • AC fail supervision(form"C"contact,I amp/28VDC). Signaling Systems(UL 864). Factory set for 30 seconds with optional 2.5 to 3 hour • MEA-NYC Department of Buildings Approved. delay setting(field selectable). • CSFM-California State Fire Marshal Approved. • Instant local AC trouble reporting relay • FM-Factory Mutual Approved. (form"C"contact, 1 amp/28VDC). • NFPA 72 Compliant. • Battery presence and low battery supervision Input: (form"C" contact, 1 amp/28VDC). • Power input 120VAC 60 Hz, 5 amp. Visual Indicators: • Two(2)Class A, Style Z or two(2)Class B, • Input and output status LED indicators. Style W,X,Y FACP inputs. Special Features: • Two (2)NC dry contact trigger inputs. • 2-wire horn/strobe Sync mode allows audible Output. notification appliances (horns)to be silenced • Class 2 Rated power limited outputs. while visual notification appliances (strobes) • 24VDC @ 8 amp max total alarm current. continue to operate. • 2.5 amp max current per output. • Temporal Code 3, Steady Mode, Input to Output • Separate 1.0 amp auxiliary output. Follower Mode(maintains synchronization of • Two (2)outputs may be paralleled for more power on notification appliances circuit). an indicating circuit (see Application Guide). • Compatible with 12VDC or 24VDC fire panels. • Programmable supervised indicating circuit outputs: • Output loop supervision steered to input 1 or input 2. Four(4)Class B, Style W,X,Y or Two (2)Class A, • Signal circuit trouble memory(helps identify Style Z or One (1)Class A, Style Z and Two (2) intermittent loop problems). Class B, Style W,X, Y (see Application Guide). • Common trouble input and output. • Thermal and short circuit protection with auto reset. • Ground fault detection. Battery Backup: Added Features: • Built-in charger for sealed lead acid or gel type batteries. • Unit includes power supply,red enclosure, cam lock, • Automatic switchover to stand-by battery when and battery leads. AC Fails. Mechanical: • Zero voltage drop when switching over to • Enclosure Dimensions(H x W x D approx.): battery backup. 15.5"(393.7mm)x 12"(304.8mm)x 4.5"(114.3mm) • Product weight(approx.): 121bs. (5.44 kg). • Shipping weight(approx.): 13.3 lbs. (6.03 kg). Agency Approvals UL Listed Control Units and Accessories California State Fire Marshal Approved. U` for Fire Alarm Systems (UL 864)Ninth Edition FM Factory Mutual Approved. MPEA NYC Department of Buildings Approved. APPROVED Enclosure Dimensions (H x W x D)(approximate 15.5" (393.7mm)x 12"(304.8mm)x 4.5" (114.3mm) I.5' 4.615" 4.615" I5" 138.1mm) (117.22nm) (117.22mm1 138.Imm1 I I.75" (44.45mm) 01.375" (34.925mm) 01.125" (28.575mm) 4.5" 12.V'. a.>" 131 7 5mm) 1114.3mm) I 11; 1310.64mm1 _ 127.94mm1 I.I" 1114.3mm1 1.25 R7.94mm1 ( 131]Smml 0.91" 0114 � 1.5" (23.114mm1 � (23.114mm) I t (38.Imm1 138.Imm1 0 0 0 0 0 O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O O O O O O O O O O 0 0 0 0 0 0 00 00 00 2.0" o 0 0 0 0 (50.8mm) 157 0 0 0 0 0 (393.mm) 00000 0 0 0 0 O O O O O O O O O O O O O O O O O O O O 0 0 0 0 0 2.0" O O O O O (50.8mm) O O O O O 5.0.. (1)7.Omm) (127.Omm) O 0.79" (20.06mm) 131.75mm) R7.94mm) 13l 75mm) 1 (44.4545mm) 7.22. 4.,22. (36.Imm) 1117.22mm1 (117.22mm) (38.Imm) StationsFire Alarm Systems I FMM-462 POPIT Addressable Manual Stations FMMm462 POPIT Addressable Manual www.boschsecurity.com BOSCH Invented for life FIRE, 0 FIRE FIRE 'I FIR[ ► Single-gang mounting PUSH P. Latching alarm lever and key-locked reset PULL PULL P. Rugged die-cast housing with 14 gauge (1.9 mm) plated steel back and corrosion-resistant construction ► Optional scored acrylic breakrod BOSCH BOSCH The FMM-462 Addressable Manual Stations allow Functions people evacuating a building to initiate an alarm and alert others still inside. Addressable Operation The included POPIT module is addressed using on- The POPIT connects to a two-wire data expansion board slide switches. It is then connected to the circuit from the control panel. Device address is set control panel's data expansion loop. The POPIT is through slide switches on the POPIT Module, allowing polled by the control panel and sends reports on any programmable device identification by the control opens, shorts, or ground faults on the manual station's panel. wiring. The addressable feature allows the agencies Certifications and approvals- responding to alarm or trouble conditions to go to the point that initiated the alarm or trouble report. ADA Complies with Americans with These low-profile manual stations are die cast with Disabilities Act ADA4.28.3 rounded edges to fit most design applications. All metallic components are painted or plated to inhibit NFPA Complies with National Fire Protection Association NFPA72 corrosion. These manual stations conform to the Americans with Disabilities Act (ADA) standards. Region Certification USA UL UNIU:Boxes,Non-Coded(UL38) CSFM see our website notesMechanical Compatibility Information Activation Force: 5lb(2.3 kg) The following table lists control panels compatible Alarm Response Time: 1 sec(approximately) with the FMM-462 and FMM-462-D manual stations: Control Panels Dimensions(HxWxD): 4.75 in.x 3.2 in.x 0.875 in. (12.1 cm x 8.1 cm x 2.2 cm) Active products` Material: Painted die-cast metal,plated steel back D9412GV4,D7412GV4,D7212GV4—,D9412GV3,D7412GV3,and and painted steel front D7212GV3'" Orderin information Inactive products': - FMM-462 Single-Action Manual Station D9412GV2,D7412GV2,and D7212GV2""' The single-action manual station is UL Listed and Legacy products": meets Americans with Disabilities Act (ADA) requirements. It has a latching alarm lever with a D9412G,D7412G,D7212G—,D9412,D7412,and D7212— key-locked reset, a rugged die-cast housing, and D9124 corrosion-resistant construction. Order number FMMA62 D9112,D8112,and D7112 FMM-462-D Double-Action Manual Station 'Inactive products are no longer available for general sale The double-action manual station is UL Listed and "Legacy products were investigated to comply only toUL8648t1 meets Americans with Disabilities Act (ADA) edition requirements. It has a latching alarm lever with a key-locked reset, a rugged die-cast housing, and a Indicates products which are not UL listed for commercial fire corrosion-resistant construction. applications Order number FMM-462-D Mounting Considerations Accessories The manual stations are for indoor use only. D102 Replacement Key The manual station and the wiring from the control Replacement key (#1358) for LOCK-1358 and the panel data expansion loop fit into a single-gang back D101 lock. box for flush mounting. Use the larger FMM-100BB-R Order number D102 Back Box for surface mounting and to provide additional room for system wiring and the module. FMM-100BB-R Surface-mount Back Box(red) Parts included Red cast-metal back box Order number FMM-100BB-R Quant Component FMM-100GR Scored Acrylic Break Rods 1 Manual station Scored acrylic rods (12 per package) Order number FMM-100GR 1 D9127U POPIT module 1 FMM-100GR scored acrylic breakrod 1 D102 Key(1358) 1 Literature pack Technical specifications Electrical Current(alarm): 0.8 mA Current(normal): 0.5 mA Voltage(operating): 7 VDC to 15 VDC supplied by the control panel Environmental Temperature +14°F to+120°F(-10°C to+49°C) (operating): Represented by, Americas: Europe,Middle East,Africa: AsiaAacitic: China: America Latina: Bosch Security Systems,Inc. Bosch Security Systems B.V. Robert Bosch(SEA)Pte Ltd.Security Bosch(Shanghai)Security Systems Ltd. Robert Bosch Ltda Security Systems Division 130 Perinton Parkway P.O.Box 80002 Systems 201 Building,No.333 Fuquan Road Via Anhanguera,Km 98 Fairport.New York,14450,USA 5617 BA Eindhoven,The Netherlands it Bishan Street 21 North IBP CEP 1306"00 Phone:+1 800 289 0096 Phone:+3140 2577 284 Singapore 573943 Changning District,Shanghai Campinas,Sao Paulo,Brazil Fax:+1 585 223 9180 Fax:+31 40 2577 330 Phone:+65 6571 2808 200335 China Phone:+55 19 2103 2860 security.sales®us.bosch.com emea.securitysystems®bosch.com Fax:+65 6571 2699 Phone+86 21 22181111 Fax:+55 19 2103 2862 www.boschsecurity.us www.boschsecurity.com apr.securitysystemsebosch.com Fax:+86 21 22182398 latam.boschsecurity®bosch.com www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com O Bosch Security Systems 2014 1 Data subject to change without notice 27084439151 an,V4,11.Aug 2014 is RIM - •1 BOSCH Invented for life D278S Four-wire Addressable Detector Base ( 12 VDC) ► Low-profile modular design ► Addressable application ► Data In and Data Out terminals i Easy head removal for cleaning and servicing Use the D278S Four-wire Addressable Detector Base Installation/Configuration Notes with smoke and heat detector heads to provide early warning fire detection for life safety and property Compatible Products protection systems.The D278S is a 12 VDC base for use The following products are compatible with the D278S in systems controlled by a D7412G or D9412G 12 VDC Four-wire Addressable Detector Base: Control Panels with a D8125 POPEX Module.The D278S has a built-in POPIT to provide individual addresses on Category Product ID Product Description the FACP data expansion circuit. Control Panels D7412G Addressable control panel The D278S accepts the D285/D285TH Photoelectric D9412G Addressable control panel Smoke Detector Heads, the D286 Ionization Smoke Detector Heads D285 Photoelectric smoke detector head Detector Head, and the D603, D604, and D605 Heat D285TH Photoelectric smoke detector head with Detector Heads. When used with the D285 Series fixed-temperature(+135°F[+57°C]) detector heads, the D278S indicates Chamber Check® heatsensor trouble to the control panel through the POPIT bus. The D286 Ionization smoke detector Chamber Check trouble indication appears on the D603 Rate-of-Rise heat detector keypads as a fire trouble. D604 Fixed-temperature(+135°F[+57°C]) heat detector Certifications and Approvals D605 Fixed-temperature(+190°F[+88°C]) heat detector Listings and UL UROX:Smoke—Automatic Fire Detectors(UL268) Mounting Approvals: ULUROX7:Automatic Fire Detectors certified for Canada The D278S base mounts on a single-gang switch box or (ULC529) on standard three-inch and four-inch square or c-UL-us octagonal back boxes.An adapter plate is packaged with CSFM 7300-1615:109 the base. NYC/MEA(12-92-E,Vol.X) www.boschsecurity.com 2 1 D278S Four-wire Addressable Detector Base'(12 VDC) Wiring Technical Specifications The D278S accepts any wire from 12 AWG (2.0 mm) to 24 AWG (0.3 mm). The minimum wire size depends on Environmental Considerations the number of bases used and the distance from the Temperature(operating): +32°Fto+100°F(0°Cto+38°C) FACP to the furthermost base. Refer to the D278S/ D298S Installation Instructions (P/N: 33353) for specific Mechanical Properties wiring requirements. Color: Bone white Dimensions(diameterx D): 6.375 in.x 0.9 in.(16.2 cm x 2.3 cm) Parts Included Power Requirements (Auxiliary Supply) Quant. Component Current(alarm): 40 mA 1 D278S detector base Current(standby): 2.5 mA 1 Adapter plate(P/N:18851) Voltage(operating): 9.6 VDC to 13.9 VDC 1 Hardware pack Trademarks 1 Literature pack Chamber Checko is a registered trademark of Bosch Security Systems in the United States. Ordering Information D278S Four-wire Addressable Detector Base(12 D278S VDC) Americas: Europe,Middle East,Africa: Asia-Pacific: Represented by Bosch Security Systems Bosch Security Systems B.V. Bosch Security Systems Pie Ltd 130 Peri nton Parkway P.O.Box 80002 38C Jalan Pemimpin Fairport,New York,14450,USA 5600 JB Eindhoven,The Netherlands Singapore 577180 Phone:+1 585 223 4060 Phone:+31 40 27 83955 Phone:+65 6319 3450 Fax:+1 800 289 0096 Fax:+31 40 27 86668 Fax:+65 6319 3499 security.sales@us.bosch.com emea.securitysystems@bosch.com apr.securitysystems@bosch.com www.boschsecurity.us www.boschsecurity.com www.boschsecurity.com ®Bosch Security Systems 20061 Data subject to change without notice F1431625739I Cur:en-US,V2,25 Jan 2006 Fire Alarm Systems I D285 Photoelectric Smoke Detector Heads (12/24 VDC) • Photoelectric Smoke Detector f (12/24 VDC) 1 www.boschsecurity.com BOSCH Invented for life " ► Commercial or residential applications ► Two-wire or four-wire application, depending on base ► Chamber Check rapid-flash LED sends contaminated chamber reports ► Flashing LED power indicator ► Steady-On LED alarm indicator The D285 and D285TH detector heads detect the large D293E Power Supervision Detector Base (6 in. smoke particles which typically result from wood, [15.2 cm] diameter) with Auxiliary Form A Relay paper, and fabric combustion. The D285TH smoke D293S Four-wire Detector Base (6 in. [15.2 cm] detector also has a+1350F (+57°C) fixed temperature diameter) with Sounder heat sensor. Use in areas where the ambient D298M 24 V Four-wire Addressable (POPIT) Master temperature does not exceed +100°F (+380C). These Detector Base (6 in. [15.2 cm] diameter) detectors are compatible with two-wire or four-wire, D298S 24 V Four-wire Addressable (POPIT) Slave 12 VDC or 24 VDC circuits. Also available are Detector Base (6 in. [15.2 cm] diameter) addressable bases for use on the POPEX bus. Functions These detectors have two components: the detector base and the detector head.The base is permanently Detection chamber operation attached and wired to a back box. The interchangeable These smoke detectors use an infrared (IR) LED light heads quickly detach for replacement and cleaning source and a silicon photodiode to measure light in a without affecting circuit wiring. The D285 and D285TH chamber. In normal conditions the light is absorbed in detector heads attach to the following detector bases: the chamber. The presence of a significant number of • D278S 12 V Four-wire Addressable (POPIT) Detector particulates allows the light to reflect to the Base (6 in. [15.2 cm] diameter) photodiode. After three consecutive measurements • D287 Two-wire Detector Base (5.5 in. [14 cm] exceeding the threshold level, the unit signals an alarm diameter) condition. The detector can be reset from the control • D288 Two-wire Detector Base ([6 in. [15.2 cm] panel, after an alarm condition is cleared, by diameter) interrupting power. • D292 Four-wire Detector Base (6 in. [15.2 cm] The detection chamber, designed for reliable smoke diameter) entry characteristics, is protected by a micro-fine • D293A Four-wire Detector Base (6 in. [15.2 cm] insect screen to reduce dust accumulation and insect diameter) with Form C Relay penetration and minimize nuisance alarms. 2 1 D285 Photoelectric Smoke Detector Heads (12/24 VDC) Chamber Check Feature Wiring To further reduce nuisance alarms, the detector heads The terminal block accepts up to 12 AWG (ISO 2.5 check their calibration. This Chamber Check feature is mmz) wire. automatic. If the head is out of calibration for a period exceeding 24 hours, the Trouble-Alarm LED flashes Parts included once per second, three times the normal rate. Quanti Component Testing ty Internal diagnostic test 1 Detector head with dust cover These heads have moisture-proof reed switches that react to an external magnet for testing.The magnet 1 Lit pack-Installation Manual,Technical Service Note on test simulates a 4%to 6%smoke obscuration that installation places the detector in an alarm condition. This test results in specific LED and alarm circuit responses to Technical specifications indicate: Electrical • Detector within calibration standards • Detector settings outside sensitivity standards Current Two-wire:depends on control panel that must limit the • Detector not operational (alarm): alarm current to 100 mA maximum This test is especially useful in environmentally Four-wire:depends on detector base;refer to unstable or unclean areas. pertinent base specifications Sensitivity voltage test Current Two-wire:0.08 mA at 12 VDC;0.09 mA at 24 VDC These detector heads have a socket that accepts the (standby): Four-wire(D293E):4 mA at 12 VDC or 24 VDC D1005 Test Cable.The D1005 connects to the detector head and allows a voltmeter to read the RMS Ripple 25%of DC input sensitivity of the device. (maximum): LEDs Voltage Two-wire:8.5 VDC to 33 VDC The detectors have a built-in LED that flashes to (input): Four-wire:10 VDC to30VDC indicate the device is powered. The LED latches on Environmental steady in an alarm condition. Radio Frequency No alarm or setup on critical frequencies in Certifications and approvals i Interference the range from 26 MHz to 950 MHz at field (RFI)Immunity: strengths less than 50 V/m Region Certification Relative Humidity: Up to 93%,non-condensing USA UL UROX:Smoke-Automatic Fire Detectors (UL268 and A) Temperature +32°F to+100'F(0°C to+38°C) CSFM see our website (operating): NYC- 274-93-E,Vol.VII Mechanical MEA Color: Bone white MSFM permit#2186 Dimensions(diameter x D): 4 in.x 1.25 in.(10.2 cm x 3.2 cm) Hong Kong HKFSD J-005/C/019 Ordering Instal lation/configuration notes D285 Photoelectric Smoke Head Notice Photoelectric smoke detector head; requires base. — Smoke detectors are intended for detection Order number D285 circuits that protect people. Heat detectors are D285TH Photoelectric Smoke Head with Fixed-Tempera- appropriate for circuits that protect property. ture(1350F [570C]) Heat Sensor Photoelectric smoke detector head with heat sensor; Mounting requires base. The D285 smoke detector head and D285TH smoke Order number D285TH and heat detector head are parts of a compound Accessories device. The detector base installs over a back box and contains all the wiring.The detector head attaches to 131005 Test Cable the base by aligning the head with the base and Connects a digital voltmeter to the detector's turning it clockwise. No tools are required for calibration pin for verifying that the detector is within installation other than the hex key used to tighten the its calibration range optional tamper screw. Order number D1005 3 D285 Photoelectric Smoke Detector Heads (12/24 VDC) DT-2 Detector Removal Tool Use the DT-2 to remove, replace, or test the detector head Order number DT-2 D275 Power Supervision Module Line supervision device for four-wire fire detection circuits Order number D275 Represented by: Americas: Europe,Middle East,Africa: Asi.Paciflo: China: America Latina: Bosch Security Systems,Inc. Bosch Security Systems B.V. Robert Bosch(SEA)Pte Ltd,Security Bosch(Shanghai)Security Systems Ltd. Robert Bosch Ltda Security Systems Division 130 Perinton Parkway P.O.Box 80002 Systems 201 Building,No.333 Fuquan Road Via Anhanguera,Km 98 Fairport,Now York,14450,USA 5617 BA Eindhoven,The Netherlands 11 Bishan Street 21 North IBP CEP 13065-900 Phone:+1 800 289 0096 Phone:+3140 2577 284 Singapore 573943 Changning District,Shanghai Campinas,Sao Paulo,Brazil Fax:+1 585 223 9180 Fax:+31 40 2577 330 Phone:+65 6571 2808 200335 China Phone:+55 19 2103 2860 security.salesous.bosch.com emea.securitysystems®bosch.com Fax:+65 6571 2699 Phone+86 21 22181111 Fax:+55 19 2103 2862 www.boschsecurity.us www.boschsecurity.com apr.securitysystems®bosch.com Fax:+86 21 22182398 latam.boschsecurity®bosch.com www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com ®Bosch Security Systems 20141 Data subject to change without notice 27010563951 an,V2,04.Aug 2014 SYSTEM �.� SENSOR' C01224T and C01224TR Carbon Monoxide Detectors ,,, , with RealTest°Technology The System Sensor CO 1224T and CO1224TR(round) Carbon Monoxide(CO)Detectors use a highly accurate and reliable electrochemical sensing cell to provide early warning of dangerous CO levels. Features With RealTest®technology,the CO gas sensing cell used in • RealTest®enables a functional test using canned CO the C01224T and C01224TR CO detectors can be tested using a CO gas agent,fully meeting the requirements of NFPA 720:2009. • Full compliance with UL 2075 Simply put the detector into RealTest mode,spray a small amount • A code-required trouble relay of CO into the detector per the installation instructions,and within • Wiring supervision with SEMS terminals seconds the detector will alarm,indicating successful gas entry.(See the reverse page or the user manual for complete instructions.) • A six-year end-of-life timer • 12/24 VDC When dangerous amounts of CO are detected,the C01224T and A low current draw of 20 mA in standby and 40 mA in alarm C01224TR detectors alert residents by sounding and flashing a temp 4 signal alarm.With 24/7 central station monitoring,residents • Versatile mounting for wall and ceiling are guaranteed protection whether they are away from home, • Accurate and reliable electrochemical sensing technology sleeping,or already suffering from the effects of CO. • Optional CO-PLATE CO Detector Replacement Plate to upgrade The C01224T and C01224TR are designed for system operation. previously installed competitor detectors to the CO1224T These detectors are fully listed to UL 2075 and offer acode- required trouble relay to send a sensor failure or end-of-life signal to the control panel and the central station.The CO1224T and C01224TR also use SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-required wiring supervision.With a low current draw,these detectors enable more devices to be connected to the panel,limiting the need to purchase extra power supplies or more expensive panels.As 12/24 VDC detectors,the C01224T and C01224TR will operate on most industry security and fire alarm control panels. Agency Listings uL ...��..: UIC LISTED L E307195 E304075 5276.1653:0194 C01224T and C01224TR Carbon Monoxide Detector Specifications Carbon monoxide(CO)detector shall be a system-connected System Sensor model number C01224T or C01224TR listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual-color LED indication that blinks to indicate normal standby,alarm,or end-of-life.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.The detector shall perform in the detection of CO up to 12,000 feet above sea level and alarm within the time specified by ANSI/UL 2034 for CO concentrations of 70,150 and 400 parts per million(ppm),as verified by a Nationally Recognized Test Laboratory. Electrical Specifications Operating Voltage 12/24 VDC Audible Signal 85 dB in alarm Standby Current 20 mA Alarm Current 40 mA(75 mA test) Alarm Contact Ratings 0.5 A @ 30 VDC Trouble Contact Ratings 0.5 A @ 30 VDC Physical Specifications C01224T Length:5.1 in,Width: 3.3 in,Height:1.3 in C01224TR Diameter:6 in,Height: 1.3 in Approximate Weight CO1224T 7 oz;C01224TR: 11 oz Operating Temperature Range 32°F to 104°F(0°C to 40°C) Operating Humidity Range 22 to 90%RH Input Terminals 14 to 22 AWG Mounting Single-gang back box;surface mount to wall or ceiling Operation Modes Operation Mode Green LED Red LED Sounder Normal(standby) Blink 1 per minute — — Alarm — Blink in temp 4 pattern Sound in temp 4 pattern RealTest®Feature: The System Sensor C01224T and C01224TR Carbon Monoxide Detectors with RealTest enable evaluation of the functionality of the CO sensing cell using a canned CO test agent. Push and hold the Test/Hush button for Spray canned CO agent into Verify CO sensing at the two seconds to enter RealTest mode.The the detector. control panel.The detector will green LED will flash once every second automatically exit RealTest alarm to indicate RealTest mode has started. mode after about 20-60 seconds. NOTE:Check with local codes and the AHJ to determine if a functional gas test is desired for an installation. Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes(except in RealTest mode). Trouble Feature: When the detector is in a trouble condition,it will send a trouble signal to the panel. �^ End-of-Life Timer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to the panel to indicate it is time to replace the detector.An electrochemical CO detector lifespan is about six years.The detector must be replaced by the date marked on the inside of the product. CO-PLATE: System Sensor also offers the CO-PLATE CO Detector Replacement Plate to cover the footprint(when necessary)of previously installed competitive carbon monoxide detectors that require replacement. Ordering Information CO-PLATE Part No. Description CO1224T 12/24 volt,4-wire system-monitored carbon monoxide detector with RealTesto Technology C01224TR 12/24 volt,4-wire system-monitored round carbon monoxide detector with RealTesto Technology CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary SYSTEM 3825 Ohio Avenue•St.Charles,IL 60174 02012 System Sensor. Phone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to change without notice.Visit systemsensor.com for current product information,including the latest version of this data sheet. SENSOR" www.systemsensor.com scoSG01soo,00•anz SYSTEM SENSOR® D4120 Duct Smoke Detector The InnovairFlex""Series are the only duct smoke detectors flexible enough to fit configurations from square to rectangular and everything in between. By Mechanical Contractor InnO% i=vf e&'X' v ` Features The InnovairFlex D4120 4-wire photoelectric duct smoke • 4-Wire Photoelectric,integrated low-flow technology detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. • Air velocity rating from 100 ft/min to 4,000 ft/min This unit senses smoke in the most challenging conditions,operating (0.5 m/s to 20.32 m/sec) in airflow speeds of 100 to 4,000 feet per minute,temperatures • Versatile mounting options:square or rectangular configuration of—40F to 158°F,and a humidity range of 0 to 95 percent(non- • Plug-in sensor offers superb false alarm immunity and the latest condensing).A plug-in sensor head offers improved false alarm sensor technology immunity and simple installation,testing,and maintenance.An improved cover design isolates the sensor head from the low-flow • Broad ranges for operating temperature(-4°F to 158°F)and feature for simple maintenance. humidity(0%to 95%non-condensing) • Patented sampling tube installs from front or back of the detector The InnovairFlex housing provides ample wiring space,a 3/4-inch with no tools required conduit knockout,and built-in short circuit protection to prevent damage to sensitive components during installation.High contrast • Increased wiring space with a newly added 3/4-inch conduit terminal designations make wiring easy.With its 2:1 sensor-to-power knockout capability,the power board of the D4120 may be used to monitor a • One easy-access Test/Reset button and improved LED status second sensor,D4S,simultaneously(i.e.,supply and return side). • Patented interconnect feature for multi-fan shutdown As many as 50 InnovairFlex detectors can be interconnected.When one unit senses smoke,all interconnected detectors will switch • New high contrast terminal designations their relays;only the detector sensing smoke will go into alarm,thus • Built-in short circuit protection from operator wiring errors pinpointing the fire source. • Field selectable settings for configuring the detector An easy-access Test/Reset button makes it possible to test the unit • Two DPDT Form-C relay contacts with the cover on.Three DIP switches can be used to configure • 24 VAC/DC or 120 VAC field selectable settings:cover tamper delay,number of sensors to be controlled,and shut down on trouble option.Each power board • Backward compatibility with existing Innovair products,including has two LEDs that can be used to indicate the status of connected remote accessories sensors,and a quick reference imprinted on the cover explains the LED status indications(Standby,Maintenance,Trouble,and Alarm). The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring.The new InnovairFlex product line is compatible with all previous Innovair Agency Listings models,including remote test accessories. A WARNING:Duct smoke detectors are NOT a substitute for open UL F M area smoke detectors;NOT a substitute for early warning detection; LISTED APPROVED NOT a replacement for a building's regular fire detection system. s_,, 3033744 7272-1653:0203 Refer to NFPA 72 and 90A for additional information. InnovairFlex'" Duct Smoke Detector Specifications Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlex'"D4120 Photoelectric Duct Smoke Detector.The detector housing shall be UL listed per UL 268A specifically for use in air handling systems.The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular.The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute(0.5 to 20.32 meters/second). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors.The detector shall be capable of providing a trouble signal in the event that the front cover is removed.It shall be capable of local testing via magnetic switch,test button on the cover,or remote testing using the RTS2-AOS Multi-Signaling Accessory or the RTS151 KEY Remote Test Station.Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size:(Rectangular Dimensions) 14.38 in(37 cm)Length;5 in(12.74 cm)Width;2.5 in(6.36 cm)Depth (Square Dimensions) 7.75 in(19.7 cm)Length;9 in(22.9 cm)Width;2.5 in(6.35 cm)Depth Weight: 2.5 Ibs(1.14 kg) Operating Temperature Range: D4120&D4S:-4'to 158'F(-20'to 7O'C); D4P120:-40'to 158'F(-40'to 7O'C) Storage Temperature Range: D4120&D4S:-221 to 158OF(-30°to 70oC); D4P120:-40°to 158'F(-40°to 70'C) Operating Humidity Range: 0%to 95%relative humidity non-condensing Air Duct Velocity: 100 to 4000 ft/min 0.5 to 20.32 m/sec Electrical Ratings Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz Input capacitance: 270 FrF max. 270 uF max. N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. Reset time:(with RTS151) .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time:(by power down) 0.6 sec.max. 0.6 sec.max. 0.6 sec.max. Power up time: 35 sec.max. 35 sec.max. 35 sec.max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements:(Using No Accessories) Max.standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz Max.alarm current: 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz Contact Ratings Alarm initiation contacts: 2.OA @ 30 VDC(resistive) (SPST) Alarm auxiliary contacts: 10A @ 30 VDC(resistive); 10A @ 250 VAC(resistive);'/2 HP @ 240 VAC;Y4 HP @ 120 VAC (DPDT) Note:Alarm auxiliary contacts shall not be connected to initiating circuits of control panels.Use the alarm initiation contact for this purpose. Supervisory contacts:(SPDT) 2.OA @ 30 VDC(resistive);2.OA @ 125 VAC(resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm APA151 12.5 mA n/a 30 mA Max. MHR/MHW 0 mA n/a 29 mA Max. RA100Z 0 mA n/a 12 mA Max. RTS151/RTS151 KEY 0 mA/12 mA n/a 12 mA Max. RTS2/RTS2-AOS 3.OmA max 16 mA Max. with strobe:55 mA max;without strobe 30 mA max Note:Any combination of accessories may be used such that the given accessory loads are:110 mA or less at the Aux output,and 50 mA or less at the Alarm output Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector.The tube locks securely into place and can be removed b releasing the front or rear locking tab(front locking tab shown below right). P, r c a `Y, 4 xavfi� � a HVDS00500 Wiring for 4-wire Duct Smoke Detector and Accessories ------------ ------------ PO WER INPUTS(NOTE 1) I I POWER INPUTS(NOTE 1) I z4VAC,DC, -12 ' F4V-1 rVAC� VAO 9 10 I I 9 10 I OR I I OR I AUXILIARY CONTACTS I I AUXILIARY CONTACTS FOR FAN SHUTDOWN,ETC.(NOTE 2) I I FOR FAN SHUTDOWN,ETC.(NOTE 2) , AUX A AUX B I I AUX A AUX B N N N N N N C N I I I I EOL I I I I SPECIFIED BOY SUPERVISORY CONTACTS I I SUPERVISORY CONTACTS I PANEL MANUFACTURER (NOTE 3) I I (NOTE 3) , — SU SUP .O. I I SU SUP O. UUFM LISTED i 3 14 I 3 14 4-WIRE CONTROLPANEL + ALARM 4 ALARM C. ALARM 4 ALARM C. ALARM INITIATION INITIATION I INITIATION CONTACTS CONTACTS LOOP \ (NOTE 4) (NOTE 4) \\\ 6 ALARM N.C. 5 ALARM N.O. I ——— -----------� I--' FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP NOTE 1:24V Power Inputs accept a non-polarized 24VDC or 24VAC NOTE 3:Supervisory contacts shown in standby position.Open 50-60Hz. 120VAC Power Inputs accept only 120VAC contacts indicate a trouble condition to the panel.See 50-60Hz.Connect power source to appropriate terminals specifications for contact ratings. of each detector.See specifications for additional power NOTE 4:Alarm Initiation contacts shown in standby position.Closed supply information. contacts indicate an alarm condition to the panel.See NOTE 2:Auxiliary contacts shown in standby position.Contacts specifications for contact ratings. switch during alarm as indicated by arrows.Auxiliary contacts are not to be used for connection to the control panel.See specifications for contact ratings. `Please refer to the corresponding installation manual for accessory wiring diagrams. Important Notes on 2:1 Sensor-to-Power Capability •2:1 sensor-to-power capability is not available for all InnovairFlex models. The feature is only available on the D4120 4-wire conventional models. •2:1 sensor-to-power capability can be enabled using one D4120 and one D4S,or two D4S and one D4P120. Important Interconnect Notes •When using the interconnect feature,all interconnected units must be powered using the same independent supply. •Polarity must be maintained throughout the interconnect wiring.Connect the INT+terminal on unit 1 to the INT+terminal on unit 2 and so on.Similarly,connect the INT/AUX—terminal on unit 1 to the INT/AUX-terminal on unit 2 and so on. •Up to 50 D4120 units,50 D4P120 units,or 50 units of combination may be interconnected. •Up to 10 DH100ACDC units may be interconnected.Please note that each of the 9 DH100ACDC units interconnected may be replaced by three D4P120 units.Therefore,when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 27 D4120 units. NOTE:Alarm can be reset only at the initiating device and not at the devices interconnected. HVDS00500 Accessories System Sensor provides system flexibility with a variety of accessories,including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors,all duct smoke detector accessories are UL listed. SMOKE s*a RTS151 UL S4011 RTS151 KEY UL S2522 APA151 UL S4011 RTS2-AOS UL S2522 RA100Z UL S2522 MHW UL S4011 MHR UL S4011 AOS Ordering Information D4120 4-wire photoelectric low-flow duct smoke detector Accessories D4S 4-wire photoelectric sensor component only ETX Metal exhaust tube duct width 1ft(0.3m) D4P120 4-wire photoelectric power board component M02-04-00 Test magnet only,24 VAC/DC,120 VAC 2D51 4-wire conventional photoelectric sensor head MHR Mini Horn,Red DST1 Metal sampling tube duct width up to 1ft(0.3m) MHW Mini Horn,White DST1.5 Metal sampling tube duct widths 1 ft to 2 ft P48-21-00 End cap for metal sampling tubes (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 ft to 4 ft RA10OZ Remote annunciator alarm LED (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to 8 ft RTS151 Remote test station (1.2to2.4m) DST10 Metal sampling tube duct widths 8 ft to 12 ft RTS151 KEY Remote test station with key lock (2.4to3.7m) APA151 Remote annunciator with piezo alarm RTS2-AOS Multi-signaling accessory with add on strobe DH4000E-1 Weatherproof enclosure SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 02012 System Sensor. Product specifications subject to Change withoutnotice.Visitsystemsensor.com Phone:800-SENSOR2•Fax:630-377-6495 or current product information,including the latest version of this data sheet. SENSOR' www.systemsensor.com rivosoosoo•1n2 SYSTEM F SMOKE SENSOR® Duct Smoke ¢F Detector Accessories Expand the versatility of the InnovairFlex'line of duct smoke detectors with System Sensor notification and test accessories. Available Accessories Duct smoke detector accessories add functionality to the duct APA151 Piezo Annunciator smoke detection system by allowing quick,convenient inspections at eye level and effective audible and visible notification options.All MHR Mini-Horn,Red System Sensor duct smoke detectors and accessories are UL listed. MHW Mini-Horn,White The APA1S1 piezo annunciator,which replaces the APA451 with RA100Z/RA100ZA Remote Annunciator a new,improved look,provides an audible alarm signal,a red LED RTS151 Remote Test Station to indicate alarm status,and a green LED to indicate power status. RTS151 KEY Remote Test Station with Key It is intended for use with System Sensor 4-wire conventional duct smoke detector applications without a system control panel,to RTS2 Multi-Signaling Accessory comply with NFPA 90A. AOS Add-On Strobe The MHR and MHW SpectrAlert Advance mini-horns feature RTS2-AOS Multi-Signaling Accessory temporal or continuous tones at high and low volume settings. Their small footprint allows mounting to single-gang back boxes for applications where a small device is desired. The RA100Z and RA10OZA remote annunciators are designed for both conventional and intelligent applications.Their red LED provides visual indication of an alarm condition. The RTS151 and RTS151KEY remote test stations are automatic fire detector accessories designed to test duct smoke detectors from a convenient location.For 4-wire detectors,the RTS151 KEY test station features a multi-colored LED that alternates between steady green and red.For 2-wire detectors,the LED illuminates red for alarm. The RTS2 and RTS2-AOS multi-signaling accessories are designed to work with InnovairFlex 4-wire conventional duct smoke detectors. These accessories include a key switch that can be used to select one of two connected sensors to be tested,reset,or both by a push button switch.They also enable sensitivity measurements using Agency Listings the SENS-RDR sensitivity reader(sold separately).The AOS(Add-On Strobe)is an optional accessory included with the RTS2-AOS model. UL FM `U 0: LISTED APPHWEO Specifications,Duct Smoke Detector Accessories RTS151 Remote Test Station Voltage Regulated 24VDC Power Requirements Alarm LED:2.8 to 32 VDC,12 mA max. Operating Voltage 16 to 33 VDC Total Current:105 mA max. Maximum Alarm Current 30 mA Test Switch 10 VA @ 32 VDC Temperature Range 0°C to 49°C(32°F to 120°F) Reset Switch 10 VA @ 32 VDC Relative Humidity 10 to 93%non-condensing Alarm Response Time 40 seconds max. Wire Gauge 12 to 18 AWG Temperature Range —10°C to 60°C 04°F to 140°F) Dimensions 4.6"H x 2.9"W x.45-D Relative Humidity 95%non-condensing MHR/MHWSpectrAlert Advance Mini-Horns Wire Gauge 14 to 18 AWG Voltage Regulated 12 DC or FWR(Full Wave Rectified) Dimensions 4.8"H x 2.90"W x I A-D or Regulated 24 VDC or FWR RTS 151 KEY Remote Test Station with Key Operating Voltage 8 to 33 VDC Power Requirements Power LED(Green):14 to 35 VDC,12 mA max. (9 to 33 VDC with Sync-Circuit"Module) Alarm LED(Red):2.8 to 32 VDC,12 mA max. Sounder Current Draw 22 mA RMS max.at 8 to 17.5 Volts DC Total Current:105 mA max. 17 mA RMS max.at 8 to 17.5 Volts FWR Alarm Response Time 40 seconds max. 29 mA RMS max.at 16 to 33 Volts DC Temperature Range —10°C to 60°C(14°F to 140°F) 25 mA RMS max.at 16 to 33 Volts FWR Relative Humidity 95%non-condensing Temperature Range 0°C to 49°C(32°F to 120°F) Wire Gauge 14 to 18 AWG Humidity Range 10 to 93%non-condensing Dimensions 4.6"H x 2.75"W x 1.8-D Nominal Sounder Frequency 3 kHz Wire Gauge 12 to 18 AWG Voltage Multi-signaling20 to 29 VDC Dimensions 4.6"H x 2.9"W x 0.45"D Power Requirements Standby:3.0 mA max. OOZA Remote AnnunciatorTrouble:16.0 mA max. Voltage Range Conventional System:3.1 to 32 VDC Alarm without strobe:30 mA max. Intelligent System:18 to 32 VDC Alarm with strobe:55 mA max. Maximum Alarm Current 12 mA Sounder 85 dBA at ten feet Dimensions 4.6"H x 2.8"W x 1.3"D Temperature Range —101C to 60°C(14°F to 140°F) Relative Humidity 95%non-condensing Wire Gauge 14 to 22 AWG Dimensions 4.8"W x 5.3"H x 1.6"D For the very latest product specifications and listing information,please visit the System Sensor Web site at www.systemsensor.com. SMOKE-,I F <w .....� 3 I V r� RTS151 UL S4011 RTS151 KEY UL S2522 APA151 UL S4011 RTS2-AOS UL S2522 RAl00Z UL S2522 MHW UL S4011 MHR UL S4011 AOS f� SYSTEM 02010 System Sen— �� SENSOR 3825 Ohio Avenue•St.Charles,IL 60174 Roductspecimductinw cttod angewitheltestceV�sitsystesdatascmm o Phone:800-SENSOR2-Fax:630-377-6495 ent p odua inhumation,23-001-duding the latest 09 on of this data sheet A05-0423-001.2/10•k2309 Intrusion Alarm Systems I D9127 Series POPIT Modules D9127 Series POPIT Modules www.boschsecurity.com ,/ BOSCH Invented for life ► Provides point identification of initiating devices ► Supervises wiring to devices for circuit integrity ► Expands the number of points in the system ► Compact size ► Terminal connections for reliability The D9127 Series POPIT Modules includes the D9127T Region Certification (with magnetic tamper switch) and the D9127U (without tamper). They are used with a D8125 USA UL AMCX:Central Station Alarm Units Addressable Expansion Module when there is a need (U Station rmUnit),AMCX7:Central Station Alarm Units Certified for Canada to expand a compatible control panel beyond its (cULus),AOTX:Local Alarm Units standard number of onboard initiating zones or (UL464,UL609),AOTX7:Local Alarm points. Future system expansion is very economical as Units Certified for Canada(cULus), APAW:Police Station Alarm Units D9127 Series POPITs can be added anywhere along (UL365,UL464),APAW7:Police Sta- the two-wire data expansion loop from the D8125 tion Alarm Units Certified for Canada module. (cULus),APOU:Proprietary Alarm Units rm Both modules include proven technology that Units Certified nada(cULusroprietary , P gY Units Certified for Canada(cULus), combines zone and point supervision with individual NBSX:Household Burglar Alarm System device addressing on one pair of wires. Screw Units(UL1023),NBSX7:Household Burglar Alarm System Units Certified for terminals provide reliable connections for the data Canada(cULus),UOJZ:Control Units, expansion loop and supervised sensor loop wiring. System(UL864,9th edition),UTOU: Install a 33 kO end-of-line resistor at the farthest point Control Units and Accessories-House- hold System Type(UL985),UTOU7: on the loop for proper supervision.The units are small Control Units and Accessories-House- and easily installed in standard outlet boxes, above hold System Type Certified for Canada false ceilings, closets, or other accessible locations. (cULus) FM Certifications and approvals NYC- 12-92-E,Vol.1212-92-E,Vol.12 Australia C-Tick MEA NYC- 12-92-E,Vol.15 12-92-E,Vol.15 MEA D9127 Series POPIT Modules Region Certification POPIT to Sensor Loops The number of detection devices each sensor loop can FDNY- 6059 supervise is limited only by the resistance on the loop. CoA Resistance on each sensor loop must be less than CSFM 7167-1615:0100 CONTROL UNIT 100 Q not including the end-of-line (EOL) resistor. (HOUSEHOLD) Certain UL and National Fire Protection Association CSFM 7165-1615:0113 FIRE ALARM CON- (NFPA) applications can limit the number of detection TROL UNIT(COMMERCIAL) devices. Consult the appropriate UL or NFPA standards. CSFM 7167-1615:0243 Terminate each POPIT sensor loop with the 33 kO EOL CSFM 7165-1615:0119 resistor included with each POPIT. Use a twisted-pair wire (six twists per foot) in all notes POPIT installations for both the data expansion loop wiring and the POPIT sensor loops. Run wires away Compatibility Information from AC sources to prevent AC induction. Control Panels All G Series control panels,D9412,D7412, Parts • . D7212,D7212B1,D9112,D9112B1, D8112G1,D8112G2,and D9124 Quantit Component Module D8125 y The D8125 Multiplex Zone Expander is required. The 1 POPIT module D9127 modules are wired in parallel on the D8125 1 33 kf1 EOL resistor data loop. Number of POPIT Modules per Control Panel 1 Magnet(D9127T only) D7212G,D7212GV2,D7212GV3 32 D9127 POPITs 1 Hardware pack D7212B1 40 D9127 POPITs 1 Literature pack D7212,D7412,D7412G,D7412GV2, 67 D9127 POPITs • ' ons D7412GV3 Environmental Considerations D9124 119 D9127 POPITs Relative Humidity: Up to 93%non-condensing D911261 126 D9127 POPITs D9112,D9412,D9412G,D9412GV2, 238 D9127 POPITs Temperature(operating): 0°C to+50°C(+32°F to+122°F) D9412GV3 Properties Wiring Considerations Color: Off white Wire Size Maximum Length of all Data Dimensions: 8.1 cm x 3.8 cm x 2.4 cm Expansion Loops Combined (3.2 in.x 1.5 in.x 0.9 in.) 0.8 mm(22 AWG) 549 m(1800 ft) Material: UL Listed fire-resistant 1.0 mm(20 AWG) 881 m(2890 ft) Power Requirements 1.2 mm(18 AWG) 1402 m(4600 ft) Current Draw 0.8 mA maximum 1.5 mm(16 AWG) 2231 m(7320 ft) Resistance: Maximum increase in resistance on the POPIT 1.8 mm(14 AWG) 3551 m(11650 ft) loop is 1000 Q.Maximum resistance between the D8125 module and each POPIT is 90 n. D8125 to POPIT Loops Use one two-wire data expansion loop, or distribute Voltage(operating): 12VDCnominal the POPITs on up to three loops. The maximum lengths shown in the following table are for all data Sensor Loop expansion loops combined connected to the same Resistance: Maximum resistance on the sensor loop is1000. D8125 module. Setting DIP switches on the POPIT modules assigns them to point numbers. The switch Response Time: 1 sec approximately setting on each POPIT assigns it a point number, regardless of its physical location. D9127 Series POPIT Modules Ordering Accessories D9127T POPIT Module Includes a magnetic tamper switch. Order number D9127T D9127U POPIT Module No tamper switch. Order number D9127U Represented by: Americas: Europe,Middle East,Africa: Asis,Pacifle: Chino America Latina: Bosch Security Systems,Inc. Bosch Security Systems B.V. Robert Bosch(SEA)Pte Ltd,Security Bosch(Shanghai)Security Systems Ltd. Robert Bosch Ltda Security Systems Division 130 Perinton Parkway P.O.Box 80002 Systems 201 Building,No.333 Fuquan Road Via Anhanguera,Km 98 Fairport,New York,1.111,USA 5617 BA Eindhoven,The Netherlands 11 Bishan Street 21 North IBP CEP 13065-900 Phone:+1 800 289 01196 Phone:+3140 2577 284 Singapore 573943 Changning District,Shanghai Campinas,Sao Paulo,Brazil Fax:+1 585 2239180 Fax:+31 40 2577 330 Phone:+65 6571 2808 200335 China Phone:+55 19 2103 2860 security.saleseus.bosch.com emea.securitysystemsebosch.com Fax:+65 6571 2699 Phone+86 21 22181111 Fax:+55 19 2103 2862 www.boschsecurity.us www.boschsecurity.com apr.securitysystemsebosch.com Fax:+86 21 22182398 al.securitysystemsebosch.com www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com ®Bosch Security Systems 20131 Data subject to change without notice 25381784431 an,V3,02.Jan 2013 SYSTEM SENSOR' F F R Indoor Selectable- E Output Horns, Strobes, and V Horn Strobes for11 - ; Wall Applications SpectrAlert@ Advance audible visible notification products SPECTRMed are rich with features guaranteed to cut installation times a o v a IIV c E and maximize profits. Features The SpectrAlert Advance series offers the most versatile and • Plug-in design with minimal intrusion into the back box easy-to-use line of horns.strobes,and horn strobes in the industry. With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance • Automatic selection of 12-or 24-volt operation at can meet virtually any application requirement. 15 and 15/75 candela • Field-selectable candela settings on wall units: 15, 15/75, Like the entire SpectrAlert Advance product line,wall-mount horns, 30,75.95, 110, 115, 135, 150, 177,and 185 strobes,and horn strobes include a variety of features that increase their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating • Universal mounting plate for wall units costly and time-consuming ground faults. • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage,SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring • Compatible with MDL3 sync module continuity before the device is installed. • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings SIGNALING � & F M> MEA LISTED APPROVED approved 7125-1653186(indoor strobes) 7125-1653 188(horn strobes, S4011(chimes.horn s:roces.horns) 3023572 M-A452-05-E chime strobes) S5512(shobes) 7135-1653189(horns.chimes) SpectrAlert Advance Specifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17B-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit-Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110.115, 135,150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21B-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Range 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6-L x 4.7-W x 2.5-D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6-L x 4.7-W x 1.3-D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS) 5.7-L x 4.8"W x 0.35-D(145 mm L x 122 mm W x 9 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) i UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15175 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 86 96 96 3 Temporal Low 71 71 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 73 74 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 74 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobes. SpectrAlert Advance Dimensions 4.7" 2.5" 5.6" Wall-mount horn strobes SpectrAlert Advance Ordering Information Model Description Model Description Wall Horn Strobes Wall Strobes(cont.) P2R 2-Wire Horn Strobe,Standard cd,Red SRH Strobe,High cd,Red P2R-P 2-Wire Horn Strobe,Standard cd,Red,Plain SRH-P Strobe,High cd,Red,Plain P2R-SP 2-Wire Horn Strobe,Standard cd,Red,"FUEGO" SRH-SP Strobe,High cd,Red,"FUEGO" P2RH 2-Wire Horn Strobe,High cd,Red SW Strobe,Standard cd,White P2RH-P 2-Wire Horn Strobe,High cd,Red,Plain SW-P Strobe,Standard cd,White,Plain P2W 2-Wire Horn Strobe,Standard cd,White SWH Strobe,High cd,White P2W-P 2-Wire Horn Strobe,Standard cd.White,Plain SWH-P Strobe,High cd,White,Plain P2WH 2-Wire Horn Strobe,High cd,White Horns P2WH-P 2-Wire Horn Strobe,High cd,White,Plain HR Horn,Red P4R 4-Wire Horn Strobe,Standard cd,Red HW Horn,White P4R-P 4-Wire Horn Strobe,Standard cd,Red,Plain Accessories P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red P4W 4-Wire Horn Strobe,Standard cd,White SBBR Indoor Surface Mount Back Box,Red Wall Strobes SBBW Indoor Surface Mount Back Box,White SR Strobe,Standard cd,Red SR-P Strobe,Standard cd,Red,Plain SR-SP Strobe,Standard cd,Red,"FUEGO" Notes: All-P models have a plain housing(no"FIRE'marking on cover) All-SP models have"FUEGO"marking on cover "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135,150,177,and 185 candela settings. SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 @2014 Sysenn Sensor. Product specifications subject change without notice.Visit systemsensor.com Phone:BOO-SENSOR2•Fax:630 377-6495 SENSOR www.systemsensor.com for current productinformation, the latest version of this data sheet. www.s nvDS10os,o201 o,•,n4 SYSTEM �4 SENSOR Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SPECTRAlert SpectrAlert'Advance outdoor audible visible products �0► o v �► 1V c E are rich with features that cut installation times and maximize profits. Features SpectrAlert Advance offers the broadest line of outdoor horns, • Weatherproof per NEMA 4X, IP56 strobes,and horn strobes in the industry.With white or red plastic housings,wall or ceiling mounting options,and plain or FIRE-printed • Listed to UL 1638(strobe)and UL 464(horn) devices,SpectrAlert Advance can meet virtually any application • Compatible with System Sensor synchronization protocol and requirement,including indoor,outdoor,wet,and dry applications in legacy SpectrAlert products temperatures from—40°F to 151°F. • Field-selectable candela settings: 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185 Like the entire SpectrAlert Advance line,outdoor horns.strobes, and horn strobes for wall applications include a variety of features • Automatic selection of 12-or 24-volt operation at 15 and that increase application flexibility and simplify installation.First, 15/75 candela field-selectable settings,including candela,automatic selection of • Rotary switch for horn tone and three volume selections 12-or 24-volt operation,horn tones,and three volume options enable • Horn rated at 88+dBA at 16 volts installers to easily adapt devices to meet requirements. • Rated from—40°F to 151°F Next,SpectrAlert Advance devices use a universal mounting plate • Universal mounting plate with an onboard shorting spring that for both wall and ceiling applications.This mounting plate includes tests wiring continuity before devices are installed an onboard shorting spring that ensures wiring continuity before • Plug-in design with minimal intrusion into the back box devices are installed,so installers can verify proper wiring without mounting the devices and exposing them to potential construction • Tamper-resistant construction damage.Once the plates are mounted,all SpectrAlert Advance • Listed for ceiling or wall mounting devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes(metal back boxes are available separately)that accommodate in-and- Agency Listings out wiring for daisy chaining devices.Plastic back boxes feature ot removable side flanges and improved resistance to saltwater SIGNALING corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting.Plastic and metal weatherproof back U` boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch F M MEA 300-'653 187(outcoor Strobes) LISTED approved 72s-'5531aa(horn strobes, knock-outs at the back.A screw-in NPT plug with an 0-ring gasket S4011(chimes,horn strobes,Morns) APPROVED Pp chime strobes) S3593(outdoor and alert strobes) 3023572 MEA452-05-E 7135-185189(horns,ch mes) for a watertight seal is included with each back box. SpectrAlert Advance Outdoor Horn,Strobe, and Horn Strobe Specifications General SpectrAlert Advance outdoor horns,strobes,and horn strobes shall mount to a weatherproof back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.Outdoor SpectrAlert Advance products shall operate between—40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15,15/75,30,75,95, 110, 115.135, 150,177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL.The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch. On four-wire products,the strobe shall be powered independently of the sounder.The horn or horn strobe models shall operate on a coded or non-coded power supply.The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature —40°F to 151°F(-40°C to 66°C) Strove Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6-L x 4.7-W x 2.5-D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6-L x 4.7-W x 1.3-D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Weatherproof Back Box Dimensions(SA-WBB) 5.7"L x 5.1-W x 2.0-D(145 mm L x 130 mm W x 51 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVOS01201 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-Temporal High 57 56 69 75 95 NA NA 181 176 Non-Temporal Medium 42 50 60 69 110 NA NA 202 195 Non-Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 -221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures,listed Horn and Horn Strobe Output candela ratings must be reduced in accordance with ,8-17.5 16-33 24-Volt Nominal this table. Switch Sound Volts Volts Reverberant Anechoic Strobe Output(cd) Position Pattern dB DC FWR DC FWR DC FWR DC FWR Listed Candela Candela rating at-40°F 1 Temporal High 78 78 84 84 88 88 99 98 15 2 Temporal Medium 74 74 80 80 86 86 96 96 15/75 Do not use below 32°F 3 Temporal Low 71 73 76 76 83 80 94 89 30 4 Non- High 75 44 Temporal 82 82 88 88 93 92 100 100 95 70 5 Non- Medium 110 110 Temporal 78 78 85 85 90 90 98 98 115 115 6 Non- Low 75 75 81 81 88 84 96 92 135 135 Temporal 150 150 71 Coded High 82 82 88 88 93 92 101 101 177 1177 8t Coded Medium 78 78 85 85 90 90 97 98 185 1185 91 Coded Low 75 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobe. AVDS01201 SpectrAlert Advance Diagrams �4.7"� 2.5" 5.6" O 0 Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Up 0 •.s Wall-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Model Description Horn Strobes P2RK*I 2-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P2RHK*t 2-Wire Horn Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) P2WK*t 2-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2WHK*t 2-Wire Horn Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe,High cd,Red,Outdoor, 120 V(includes plastic weatherproof back box) Wall Strobes SRK*t Strobe,Standard cd,Red,Outdoor(includes plastic weatherproof back box) SRHK*t Strobe,High cd,Red,Outdoor(includes plastic weatherproof back box) SWK*- Strobe,Standard cd,White,Outdoor(includes plastic weatherproof back box) SWHK*t Strobe,High cd,White,Outdoor(includes plastic weatherproof back box) Horns HRKt Horn,Red,Outdoor(includes plastic weatherproof back box) Accessories SA-WBB Red,Metal Weatherproof Back Box SA-WBBW White,Metal Weatherproof Back Box Notes: *Add%P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2RK-P. t Add%R"to model number for weatherproof replacement device(no back box included),only for use with weatherproof outdoor flush mounting plate,WTP and WTPW. "Standard cd"refers to strobes that include 15,15/75,30.75,95,110,and 115 candela settings."High cd"refers to strobes that include 135.150,177,and 185 candela settings.When replacing standard outdoor units both the device and back box must be replaced. SYSTEM ®2012 System Sensor. 3825 Ohio Avenue•St.Charles,IL 60174 Adduct specificationssubjecnochange thoutn wiotice.�isrtsystemsensor.com SENS AVDS01S01201•3/12 OR Phone:800-SENSOR2•Fax:630-377-6495 to current infomation,r2 helatestversonofthsdatasheet. 0t ti. TG - 7FS Vr T E LG UA R D P/LTELV01 d COMMERCIAL FIRE PRODUCT FEATURES �. Certified for use on Verizon's LTE network for long, sunset- free installation. I Meets UL 864 requirements for sole, primary or backup path communications. F Minimizes false alarms by providing dual paths for self-tests. The Telguard TG-7FS LTE-V is the ideal cellular alarm communications solution for commercial fire systems. The TG-7FS LTE-V transmits alarm signals from the fire panel over the digital cellular network to the designated monitoring station. Compliant with the 2016 Edition of NFPA 72, the TG-7FS LTE-V can serve as the sole communications path for the fire alarm system. It replaces all of the landlines currently dedicated to the master control unit. On average, cellular monitoring costs the end user significantly less than a dedicated landline. For each landline replaced with a TG-7FS LTE-V, the monthly communications bill decreases. By being able to signal failures to the central station within sixty minutes of an outage, the TG-7FS LTE-V can be installed as the sole path for commercial fire installations. For existing installations, all landlines can be swapped for a single TG-7FS LTE-V because of the new sixty minute supervision mode. The TG-7FS LTE-V can also be installed as a backup path and upgraded to sole path at a later date. . -. � . Reliability TeIguard makes adopting cellular TeIguard Cellular Service provides Features the ability to utilize easy with a secure Internet portal. Verizon . .verage multiple cellular technologies . availabilityThe straightforward web interface for all TeIguard units. Teiguard's increase -. allows security dealers and central Communication Center is UL false alarms, stations o quickly and efficiently compliant and . . Automatic self-tests with central access . .. -. betweenstation notification ensure the This advanced .. user authorization d provides products Supporttotal account management of TeIguard Technical provides controlthe alarm panel pointUL Listed TeIguard cellular alarm a single . .. trouble condition occurs. communicators, cellular service • TeIguard product TELGUARD TG - 7FS TeIguard technology allows full data reporting for unlimited point-to-point signal details and maximum transmitting power Transmit Power: ® � „,,, r• I�I Power Consumption: �� z , ,,,, 60mA(Standby) ' 250mA (Transmission), • Transformer: 12VAC,800mA UL listed plug-in. Radio Transceiver for superior in-building penetration. • LTE Bands:4&13. • Antenna: 9" dipole with 2dBi gainTeIguard products are easy t• install, economical, and UL Listed. 12 ft of cable and universal Accessories mounting bracket. • FCC part 15,27 and 68 compliant. ACD 12, • D 35, ACD SO, ACID 100: 12/35/50/100 feet of low loss, high performance cable. Physical Details • : High gain directional antenna. • TG-7FS LTE-V: 7.5"H x 11.5"W x 3.5"D. • Shipping Weight: 81bs. • Operating Environment: 0°C to +50°C; up to 95% humidity (non-condensing). Standard FeaturesUL Listings Commercial Fire 864 Commercial Burglary Residential • Fuli data reporting. Household accessories for connected warning systems fire alarm systems burglar alarm• Automatic self-test(6Q min.&daily). • • • burglar • Power supply with battery harness. units and systems alarm systems • Locking, red metal enclosure. 1610 Central station burglar alarm units; Line security servcies • Two pr©grammable supervisory For the most current product specifications and UL Listings visit www.Teiguard.com. TeIguard,a Division of Telular Corporation-3225 Cumberland Blvd SE-Suite 300-Atlanta,GA 30339- USA trip outputs.. • Supports virtually all alarm formats (Contact ID, SIA2,and others) using dial capture for universal secuRlTv panel compatibility. SIGNALING s he \ ����G III ELECTRONIC • Telephone line monitor built-in, O � / SECURITY VerlZn with Standard Line Security. � .fw % ASSOCIATION'" NFPA ��I11 NETWORK LISTED INTERNATIONAL C E RT I F I E D 110 . option 5-www.Telguard.com •• • •17 Telular Corporation-All Rights Reserved Standby Battery Calculations Bosch D7412 Aldi,18 176 Quaker Road Queensbury,NY 12804 Standby Current Alarm Current Part Number Description Quantity Per Device All Devices Per Device All Devices D7412 Control Panel 1 0.200000 0.200000 0.500000 0.500000 D8125 POPEX Point Expander 1 0.050000 0.050000 0.050000 0.050000 D928 Dual Phone Line Switcher 1 0.018000 0.018000 0.100000 0.100000 D125B Dual Class B Initiating Module 1 0.022000 0.022000 0.150000 0.150000 D8128D OctoPOPIT Eight Point Expander 1 0.025000 0.025000 0.050000 0.050000 D9127 Series POPIT Modules 8 0.000800 0.006400 0.000800 0.006400 D278S Four Wre Addressable Detector Base 2 0.003000 0.006000 0.040000 0.080000 D285 Smoke Detector Photoelectric 2 0.008000 0.016000 0.010000 0.020000 FMM-462 Single Action Manual Pull Station/w popit 1 0.000500 0.000500 0.000800 0.000800 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 Total Aux currrent Max 3 Amps 0.344 Alarm 0.957 Signal Circuits Alarm Current Circuit Device Quantity Per Device All Devices Circuit 1 P2R(15/75CD) 3 0.097 0.291 0.000 0.000 0.000 0.000 0.000 Total 1 Maximum 1.0 Amps 0.291 Circuit 2 HRK 1 0.075 0.075 0.000 0.000 0.000 0.O00 0.O00 Total 2 Maximum 1.0 Amps 0.075 Totals Maximum 2.OAmps 0.366 Circuit 1 Circuit 2 Max Wire Run Distance For AWG 14 2154 8359 Actual Wire run Distance 220 200 Voltage Drop for 14 AWG wire 0.408 0.096 Voltage Drop=2*Wire Run Distance'3.19 Ohms Per 1000 ft 14 AWG*Total Current for Circuit/1000 Standby Hours 24 Standby Battery Draw 0.344 Standby Amp Hrs 8.254 Alarm Current 1.323 Alarm Current 5 Min 0.110 Battery Size Required with 5 Min.Alarm Time and 20%Reserve 10.036 Battery Size Supplied Voltage drop Calculations & Current Draws for NACP #1 AL802ULADA Circuit#1 Circuit#2 Circuit#3 Circuit#4 Device Current Draw Quantity Total Current Quantity Total Current Quantity Total Current Quantity Total Current 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Current for Circuit 0 0 0 0 Wire Length Ft for Circuit Max Wire Run Distance For AWG Actual Voltage Drop For Circuit MAX Volt Drop for Circuit 4.400 4.400 4.400 4.400 Device Standby Device Alarm Total Stanby Total Alarm Device Current Current Quantity Draw Draw Wire Size AL802ULADA 0.09 0.175 1 0.09 0.175 14 C01224TR 0.02 0.04 6 0.12 0.24 0 0 0 0 0 1 0 Standby Hours 24 Alarm Current: 0.415 Power Supply Min Voltage 20.400 Total Battery Calculation Standby: 5.040 Battery size Reqired: 6.089 Device Min Operating Voltage 16.000 1 Alarm Current 5 Min: 0.034 Battery Supplied: 7 AH Current Draws for Fire Communicator TG-7FS Device Standby Device Alarm Total Stanby Total Alarm Device Current Current Quantity Draw Draw Wire Size TG-71FS 0.06 0.25 1 0.06 0.25 18 0 0 0 0 0 0 0 1 0 1 Standby Hours 24 Alarm Current: 0.250 Total Battery Calculation Standby: 1.440 Battery size 1.753 Alarm Current 5 Min: 0.021 Battery Supplied: 7 AH U Applicant ID No: 370746-011 L Service Center No:22 Expires: 31-MAR-2019 CERTIFICATE OF COMPLIANCE THIS IS TO CERTIFY that the Alarm Service Companv indicated below is included by Underwriters Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service. This Certificate does not apply in any way to the communication channel between the protected property and any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm Transport Company is specified on the Certificate. Listed Service From: IRVING, TX Alarm Service Company: (370746-011) Service Center: (370746-011) ADT LLC DBA PROTECTION 1 ADT LLC DBA PROTECTION 1 4221 W JOHN CARPENTER FWY 4221 W JOHN CARPENTER FWY IRVING TX 75063-2924 IRVING TX 75063-2924 The Alarm Service Company is Listed in the following Certificate Service Categories: File - Vol No. CCN Listing Category BP1790-3 CPVX [Burglar Alarm Systems] Central Station BP10566-1 CRZM Monitoring Stations, National Industrial Security S2684-20 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling Services) Central Station ***THIS CERTIFICATE EXPIRES ON 31-MAR-2019*** "LOOK FOR THE UL ALARM SYSTEM CERTIFICATE" Fire Alarm Device Legend ® h• ND ND © . AY••w•w M M���•.•r•M. PLAN TYPE. OFFICE BREAK MENS ROOM R.R. IX IX .,, o.•,.<I.,AX7 IARR —, No � 1— —-— — -_ „_ _..,_ ...—., ,.—..��•`,� I BACKROOM .a. u±a=L•anw. � L1d'' J I Pa VpMENS 71.'r ND I e ® a <°'°.,uN..me.< r. s sw.• i sxn..s.•e A•12A 'F R.R y= WALK IN It N 3 II .olaxw wnss w•w.<s.•m r FREEZER FREEZER I I NO 1 - °i< .— I s _ _ _ M E"tMI rY a.em.•ww " d�.r••Wrlr �fr_ yrM�eau ear b I I I I I I „ 9N.M d .r. �`• s"w Ya ewe_•w•b• �F �, � f.wb b era9 bola �" I• I I II II i I L ... Fire Alarm Wire Leoend W. LI II II 14 XM b to Mo II _ iI � II Iv I N,DD2 III B� .._..._..._,._.._...— I.I—.._.._.._,__.._..—..._,_..._.._,_—._.._...—...—..._ _. — CI-ASS NOTES wLrw•.<,...•...,...x. o�' F Nsrsa = II N o IHCR IXj jIX rl{E�; SALES i ;[�I UVVx ° @rbD PROJECT INFORMATION WALK IN PRD.A=.cTINFae 0N. COOLER NAME OT PRgxcT: ALDI V18 p••�•y.Nr 12w N I PROPosn DBE:METICAN,XE % FlRE ALARM INSTALLER: ADT LLC DBA PROTECRON, BUILgNG SOFT:13.]NM m Z`A r D,-,, _ J �,rxxr,xoi 'OGcuPANCY LOAD'.NO C x ��;p65 accuPANCY cuss:M E N 1 NO 4M:wIN L••a aa..a m 2ms eC Ivmwa FlRE ALARM MO MTEC(VENDOR AOT LLC N CARPENTER I = 4221 W JONX CMPENIER fWY IB77_CSJX 1750 3 UfX/52B61-20 FlRE ALAMADESN.NER II EXIT ENTRY i� i'T rrr Bib r)09-3.110 58 I SCOPE OF WORK FIRE ALARM SYSTEM FLOOR PLAN ® INSTALL TON OF CARBON MONOXIDE DETECTORS ON AN EXISTING SYSTEM V .CHANCE MONITORING VENDOR TO ADT/PROTECTION I v m CEILINGS ARE DROP TILE AT 10'-0"A.F.F. } INDEX OF DRAWINGS ;z .fA-, FIR ALARM FLOOR PLAN LAYOUT Z •fA-2 E ALARM RISER DIAGRAM A SYSTEM CALCULARONS Q U, A, DEVICE INSTALLATION LEGEND CODE SUMMARY ° ND-NEWDEVILE •2015 IBPIIAI •2013 NFPA 72 EX-EUSTINGTOREMAIN •NYS UNIFORM FlRE PREVENRON CODE XO-EXISTINGTO BE REMOVED Prepared By Daniel HebblethVvaite,ET Fire Alarm Systems Level III 107102 Fire Protection Engineering Technology Expires February 1,2021 Of FA-2 Fire Alorm Device Legend Addressable Sya(em Riser srw+a vela+ �wi.� ° TO MONITORING STATION ® "v°' w sr Yr°"wasiitlgi TG7 SlaMby 6a11ery CalcWlall as Boacn ® u Mw Iwuw w wawa PUN TYPE: QDr�12 M yy+ - I w.nas ' ��n�iu r a°� Swlw.swv w Ir .`..ww..waw.uaws.. wl sM w TO 1 SLC-1 D JED DEOK:ATEO. LIWJr a» se+ow omaro 0 LOCKED ea4y eaEnKEa FACP L1N01! YY To GROUO L,Yon s� c es -OFsww w4.r ww�ww.srw w.+ LI4MD YY Yw w,+ s.a+�sww a.j°,.I r w.wawy awuw QLINM' MI Y ve.arnwwa.r let's Fire Alarm ire Legend o NACP MMIS 2 _ MY — — — — - J_ LIAe18 YM LI4M6PfMEfl SUPEftN510N e — — — - r...� C 24VDC au.wc vc.. CLASS NOs..w....®.�.s.. +...,: ff.. a GENERAL NOTES: A FIRE CONTROL PANEL/TG7 ARE INHERENTLY POWER LIMITED AND SIGNALING AND INITIATING CIRCUITS DO NOT REQUIRE OVER CURRENT PROTECTION. THE TG7 WILL BE EQUIPPED AS SOLE PATH AS DEFINED IN NFPA 72. ITS ABILITY TO PRIVIDE LOCAL AND REMOTE NOTIFICATION OF A LINK FAILURE WITHIN 60 ® MINUTES OF DETECTION,AS WELL AS ITS ABILITY TO MEET THE BATTERY N REQUIREMENTS UNDER THE ADDITIONAL STRESS OF SIXTY MINUTE SUPERVISION. p THE TG7 WILL BE PROGRAMMED TO INITIATE AND COMPLETE A TEST SIGNAL > C.—M DINM M Fl.CMIaaaaMNyr Vohs"hay Cakuls""&Cu—i Dr.—lar MACF H I TRANSMISSION EVERY 60 MINUTES. � mZ T6TFy aLNXILaaA _ _ CONSULT WITH OWNER AND/OR GENERAL CONTRACTOR FOR EXACT LOCATION OF a O C -- THE FIRE CONTROL PANEL/TRANSPONDER PRIOR TO INSTALLATION. 2`h a E.N INSTALLER SHALL COORDINATE ALL WORK Vv1TH THE OWNER&GENERAL CONTRACTOR AND ALL OTHER TRADES. ® _ INSTALLATION: THE ELECTRICAL CONTRACTOR WILL PROVIDE A 120 V.A.C.20 AMPS DEDICATED -- CIRCUIT TO LOCATION OF FIRE CONTROL PANEL/TRANSPONDER WITH LOCK-ON TYP. arr•waew cwwwaw w.l.ynan.a C. POWER LIMITED WIRING SHALL BE SEPARATED FROM NON-POWER LIMITED ELECTRIC LIGHT.AND CUSS 1 CIRCUITS.A MINIMUM OF 21NCMES. m '� ALL CIRCUITS WILL BE IDENTIFIED AT JUNCTIONS AND AT TERMINATION BY MEANS OF F-1 A DURABLE AND VISIBLE LABEL. V ALL WIRING AND CABLING METHODS WILL COMPLY WITH N.F.P.A.70'760-25 p am om on r STANDARDS.BY WAY OF PROTECTING ALL WIRING WITHIN 7 FEET FROM THE y FINISHED FLOOR IN CONDUIT STUB-UP AND BY CONCEALING ALL WIRING IN WALLS. CEILING AND PROTECTIVE BUILDING ELEMENTS. _� O NO'T"TAPPING OF FIELD WIRING IS PERMISSIBLE IN SUPERVISED CIRCUITS,DATA Y ,y,,,,,,,,, y CIRCUITS ARE EXCLUDED. NFPA 72 AND ADA DEVICE MOUNTING OF ALL DEVICES TO _ v Z INSTALLATION REQUIREMENTS COMPLY WITH NFPA 72. Q w Z REFER TO MANUFACTURER'S CUT SHEETS FOR MORE INFORMATION ON THE J 8. DEVICES. IF THE TRANSMITTER IS NOT LOCATED IN THE SAME ROOM AS THE TELCO EQUIPMENT BACKBOARD FIRE WIRE IS TO BE USED BETWEEN THE-D'MARK AND THE FIRE ALARM _ CONTROL PANEL EXCEPTION,IF CONDUIT IS PROVIDED FROM TELCO BACK BOARD TO Q ? TRANSMITTER LOCATION STANDARD I/O WIRE MAYBE USED. J P THE FIRE ALARM INSTALLER IN RESPONSIBLE CHARGE OF THE EACH SPECIFIC PRO- FIRE ALARM pYF )) J pB y JECT SHALL BE CERTIFIED BY THE DIVISION OF APPRENTICESHIP STANDARDS AS A ® O MATRIX M a y t' 6 FIRE/LIFE SAFETY TECHNICIAN",AND MUST FURNISH PROOF OF SUCH CERTIFICATION UPON REQUEST. WITH OCCUPANT F CONTROL PANEL FOR FIRE ALARM ONLY. wa.. NOTIFICATION Q*gf '� 01 1 Prepared By ��lllLe111� Daniel Hebblethwaite,ET Fire Alarm Systems Level III 107102 Fire Protection Engineering Technology Expires February 1,2021 lrbi Of FA-2