HVAC98 Richmond Hill Drive HVAC Load Calculations for Hodorowski Builders Queensbury.N.Y 308.7-1-75,RC-0014-2020 Hodorowski Homes 98 Richmond Hills Dr,Lot 28 SFD w/gas FP 2115 s.f.,Gar.365 sf. Rhvac is an ACCA approved Manual J,D and S computer program.Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. Prepared By: Greg Watson Appolo Heating &Cooling 868 Burdeck St Schenectady.N,Y ‘Thursday,January 2,2020 (Project Report Project Title 98 Richmond Hill Drive Designed By:Hodorowski Builders Project Date:Thursday,January 2,2020 | Client Name:Hodorowski Builders Client City:‘Queensbury,N.Y ‘Company Name:Appolo Heating &Cooling Company Representative:Greg Watson ‘Company Address:868 Burdeck St ‘Company City Schenectady,N.Y Reference City:‘Schenectady,New York Building Orientation:Front door faces North Daily Temperature Range:Medium Latitude:42 Degrees Elevation:378 Altitude Factor:0.986 Outdoor Outdoor Outdoor-—Indoor Indoor Grains DryBulb WetBulb RelHum Rel.Hum Dry Bulb Difference Winter:1 0.31 nla nla 70 nla Summer,87 72 49%50%75 30 Total Building Supply CFM 1,090 CFM Per Square ft 0.347 Square ft.of Room Area:3,145 Square ft.Per Ton 1,388 Volume (ft):27.913aReqmom——Air 52,389 Btuh 52.389 MBH " I 23,656 Btuh 87 % 3,526 Btuh 13% Total Cooling Required Including Ventilation Air:27,182.Btuh 2.27 Tons (Based On Sensible +Latent) Rhvac is an ACCA approved Manual J,D and S computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at | your design conditions. C:\Usersigregw\Desktop\RHVAC 9198 Richmond Hill drive.rhS Thursday,January 2,2020,9:58 AM ‘Miscellaneous Report Winter:1 0.31 80%nla 70 nla Summer.87 72 49%50%75 29.96 Runouts Calculate:Yes Use Schedule:Yes Roughness Factor:0.00300 0.01000 Pressure Drop:0.1000 in.wg./100 ft.0.1000 in.wg./100 ft Minimum Velocity:0 feJmin Maximum Velocity:900 ft/min Minimum Height:0 in. Maximum Height:0 in. | Winter immer Infitration Specified:0.370 AC/hr 0.190 AC/hr 172 CFM 88 CFM Infitration Actual:0.370 ACIhr 0.190 ACIhr Above Grade Volume.x 13 Cutt X_27.913 Cust, 10,328 Cu.ft/hr 5,303 Cu.ft/hr X 0.0167 X 0.0167 Total Building Infiltration:172 CFM 88 CFM Total Building Ventilation:0 CFM 0 CFM System 1— Infitration &Ventilation Sensible Gain Multiplier:13.02=(1.10 X 0.986 X 12.00 Summer Temp.Difference) Infitration &Ventilation Latent Gain Multiplier:20.09=(0.68 X 0.986 X 29.96 Grains Difference) Infiltration &Ventilation Sensible Loss Multiplier:74.87=(1.10 X 0.986 X 69.00 Winter Temp.Difference) Winter Infiltration Specified:0.370 AC/hr (172 CFM),Construction:Average ‘Summer Infiltration Specified:0.190 AC/hr (88 CFM),Construction:Average = C:\Users\gregw\Desktop\RHVAC 9198 Richmond Hill drive.rh9 Thursday,January 2,2020,9:58 AM _Load Preview Report nal ‘sa seo)8]8]8]caelsore$5)|so]Sl S|ie al Al el ang aa iam aie es wo 800 10801000Sptarime380%seam emo 100 tnZeeais288eoee‘Bossman 188 2374 tom 12 me 112xtchenmatatgSok1413tame‘Fenian asian oD oor wTSars1mmeanest0hnaReamwo14808)tse ame wwTakFoammrtmzeewtroamoenom8wmtlFoe510mosteo{ase Bocan as tome ots sew tltiain12totomsawattjaan640{Sad oan em 0 mM 5 mM om td{eons i tans a381 3 wottbadeom4im197wi2aa0tat‘ebeoan2 fm 208 032A 2m‘sana ome 8 iw oe ot‘hey wow 0 ot ww CAUsers\gregw\Desktop!RHVAC 9198 Richmond Hill drive.rhg Thursday,January 2,2020,9:58 AM [Duct Size Preview are|Snes er erSeen! Som Rouaat ean mot af ans 4isBasomtola)ms izaooarcacrc“i Feaiaon oa star ras us “ae en i rotons ei ee oleroRoaneasoeateortftectoscoIfatalaaratafocicoyteersa‘tector oa ihe essetcct teint asowoanclccoFeFaeroeea¢oo a a op oeaseaCeeeof0cttn°75 an!2402 oem ad{StareyReon eee 0 mom atts ee‘4 Becoom3 Buitn °70 oot at 452 «Ml oo 14eae:ae ec a ae16-Bedroom 2 Buittin 0 750 O01 Ot 4806 35 i 8 6aeseceoizaoe18Haaybait°70 an)3386 cM 1]eine renert Supply Main Tank Buln o 000009 at errs 600 (NAHB 1000 sax Sanna|System 1 HesingFow 080 Conny Fove 1080 C:\Users\gregw\DesktopiRHVAC 9\98 Richmond Hill drive.rh9 Thursday,January 2,2020,9:58 AM CAUsersigregw\Desktop\RHVAC 9198 Richmond Hill drive.rho {Total Building Summary Loads PlyGem Pro:Glazing-PlyGem Pro,U-value 0.33,SHGC. 0.28 New Material:Door-slider generic door,U-value 0.28 ‘Therma90:Door-ThermaTru 90 Fire Door,U-value 0.14 Front Door:Doot-TMG Front Door,U-value 0.19 12E-Obw:Wall-Frame,R-19 insulation in 2 x 6 stud cavity,no board insulation,brick finish,wood studs, U-value 0.068 12F-Obw:Wall-Frame,R-21 insulation in 2 x 6 stud cavity,no board insulation,brick finish,wood studs, Unvalue 0.065 R-49:RoofiCeiling-Under Attic with Insulation on Attic Floor (also use for Knee Walls and Partition Ceilings),Custom,R-49 Batt Insulation,U-value 0.02 21A-32-c:Floor-Basement,Concrete slab,any thickness,2ormorefeetbelowgrade,no insulation below floor, carpet covering,shortest side of floor slab is 32° wide,U-value 0.02 19A-cp:Floor-Over enclosed crawl space,No insulation on exposed walls,sealed or vented space,passive, 1o floor insulation,carpet or hardwood,U-value 0.295 19A-Otp:Floor-Over enclosed crawl space,No insulation ‘on exposed walls,sealed or vented space,passive, ‘no floor insulation,tle or vinyl,U-value 0.368 _Subtotals for structure People Equipment: Lighting’ Ductwork: Infiltration:Winter CFM:172,Summer CFM:88 Ventilation:Winter CFM:0,Summer CFM:0 AED Excursion:_ Total Building Load Totals: 1402 1156 4601 388 9,041 4,522 1,595 12,243 3,205 39,500 0 12,889 aa52,389 CFM Per Square ft. Square ft.Per Ton: Total Building Supply CFM 1,090 Square ft.of Room Area:3,145 Volume (ft):27,913 Total Heating Required Including Ventilation Air:52,389 Btuh Total Sensible Gain:23,856 Btuh Total Latent Gain:3,526 Btuh Total Cooling Required Including Ventilation Air:27,182 Btuh Rhvac is an ACCA approved Manual J,D and S computer program.Calculations are performed per ACCA Manual J 8th Edi All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. 0 3,342 0 263 0 61 0 a9 0 620 0 998 0 4,037 0 0 0 2,129 0 558 0 9.095 1,750 2,250 0 0 10,912 0 0 1,776 1,149 0 0 0 250 52.389 MBH 87 13 2.27 Tons (Based On Sensible +Latent) % % |.Version 2,and ACCA Manual D. 3,342 263 61 89 620 | 996 4,037 2,129 558 9,095 4.000 0 10,912 2,925 0 250 27,182 0.347 1,388 Thursday,January 2,2020,9:58 AM {System 1 Room Load Summary —Zone 1— 1 Basement 1,156 10,789 142 17 409 -2,874 564 108 1092Kitchen1683,336 44 15 396 1,170 421 54 54 3.Nook 144 2,596 m4 15 412 1:218 56 56 564FamilyRoom2855,037 66 16 380 1,621 149 75 755Stairs982.668 35 15-365 1,079 106 50 506DiningRoom1603,145 4 16 349 1,489 89 69 697MudRoom1302.879 38 15 314930 107 43 43 8 Powder Room 30819 8 14 225 425 23 20 209Foyer561,998 26 15 342 1,013 70 47 4710MasterBedroom2245,199 68 28 361 3,078=840.142 142 11 Master Bath 112 2,363 3t 15 341 1,010 65 47 4712wic4843361424045502424 13.Laundry Room 6 a7 5 14 432 0 20 2014Bedroom31543,515 46 16 1,897 454 87 a7 15.Bedroom 4 120 3,011 40 16 1,97718Bedroom21202,626 35 16 2,04817Bath2801,340 18 15 79818Hallway541-4 641 ___System total 3,145 ‘System 1 Main Trunk Size: Velocity: Loss per 100 ft: 227 87%/13%23,656 3,526 27,1822.60 75%|25%22,500 7,500 30,000 Healing System Cooling System Natural Gas Furnace ‘Standard Air Conditioner ML195UHO70XP36B-43ACXNO30-230-* Indoor Model C35-36B+TDR+TXV Brand:MERIT 90 MERIT 13ACX SERIES Description:Natural Gas or Propane Fumace Efficiency:95 AFUE 45 SEER Sound:0 0 Capacity:64,000 Btuh 30,000 Btuh Sensible Capacity:nia 22,500 BtuhLatentCapacity:nia 7,500 Btuh AHRI Reference No.nla 8267079 C:\Usersigregw\DesktoptRHVAC 9198 Richmond Hill drive.rh9 Thursday,January 2,2020,9:58 AM