engineer's letterWIN Cc HIP 36 Cougar Lane Phone:(518)494-2555 IENGINEERIN Gre PO Box 116 Fax:(518)494-2566 Chestertown,NY 12817 July 1,2019 Job No.:19-069 Page |of 1 Mailing Address:Patrick Seelye Remax Peak Performance 485 Glen Street Glens Falls,NY 12801 Job Address:26 Reardon Road Queensbury,NY 12803 Tax Map #289.7-1-31 Dear Mr.Seelye, This letter is intended to address the capacity of the existing wastewater absorption field at the above referenced location.Per the Town of Queensbury approved design,Permit Number 20010780,dated October 18,2001,the system and field were design for three bedrooms at 150 gallons per day per bedroom,or 450 gallons per day total design flow. The current use of the property is intended for four bedrooms.Renovation work is being conducted to modernize all water using fixtures;such fixtures reduce the required design flow to 110 gallons per day per bedroom.As such the required capacity of the system will be 440 gallons per day,less than the original design capacity. ‘The field as originally designed should be expected to function as intended. Ifyou have any questions or I can be of further assistance,please let me know. Very truly yours, bap nt veg Bret W.Winchip NYS PE #083076 Winchip Engineering,P.C.