BINS-000360-2019 01232019
INSPECTION WORKSHEET (BINS-000360-2019)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
CC-000365-2016Permit
Case Number:Case Module:
Wed Jan 23, 2019Partial Pass
Inspection Date:Inspection Status:
John O'BrienBuilding Framing
Inspector:Inspection Type:
44, 46, 50, 52, 56, 58, 62, 64 Wedgewood302.9-1-28.1
Job Address:Parcel Number:
DR Bldg. 4
Queensbury, NY 12804
Contact TypeCompany NameName
ContractorSchermerhorn R.E. HoldingsVANDERWARKER, DARREN
Primary OwnerSCHERMERHORN WEDGEWOOD
LLC
Granted PermissionSchermerhorn R.E. HoldingsVANDERWARKER, DARREN
ArchitectRucinski-Hall Architecture
ApplicantSchermerhorn R.E. HoldingsVANDERWARKER, DARREN
Checklist ItemPassedComments
Building Inspector NotesNO6/29/18 Ice & Water Shield Approved
1/23/19 Framing Partial Approval - Preliminary Framing
- Anchor bolts are missing in some garage and rear bump out
exterior walls. Some bolts are to close to the edge of the
bottom plates and further than 6' oc.
- Check stair landings missing toe nails in hangers.
- Bridging missing at outside box area and at stair opening.
Check after trades have completed their work.
- Truss Bracing was better on this building but blocking
missing at the following location. I believe the T01 Truss
should be tied into the T01SGE need your input.
- Garage Truss north of step has cracked bottom chord need
repair.
- Truss clip missing nails on one side on garage truss.
- Spoke with Ethan earlier still waiting for accurate layout of
shear anchors.
Jan 23, 2019Page (1)
INSPECTION WORKSHEET (BINS-000360-2019)
Checklist ItemPassedComments
FramingNO1/23/19 Framing Partial Approval - Preliminary Framing
- Anchor bolts are missing in some garage and rear bump out
exterior walls. Some bolts are to close to the edge of the
bottom plates and further than 6' oc.
- Check stair landings missing toe nails in hangers.
- Bridging missing at outside box area and at stair opening.
Check after trades have completed their work.
- Truss Bracing was better on this building but blocking
missing at the following location. I believe the T01 Truss
should be tied into the T01SGE need your input.
- Garage Truss north of step has cracked bottom chord need
repair.
- Truss clip missing nails on one side on garage truss.
- Spoke with Ethan earlier still waiting for accurate layout of
shear anchors.
Attic Access 22 x 30 minimumNO
Jack Studs HeadersNO
Continuous Header for Garage Doors withNO
Straping
Truss Specification ProvidedNO
Bracing BridgingNO
Hurricane Clips/Uplift Screws/Nail Holes FilledNO
Air Seal all Plates and SillsNO
Air Seal All Registers at FloorNO
Air Sealing all Joints Before InsulationNO
Joist hangersNO
Jan 23, 2019Page (2)
INSPECTION WORKSHEET (BINS-000360-2019)
Checklist ItemPassedComments
Jack Posts Main BeamsNO
Exterior sheeting nailed properlyNO
12 O.C.NO
Headroom 6 ft. 8 in.NO
Notches Holes Bearing WallsNO
Metal Strapping for Notches Top PlateNO
Draft stopping 1,000 sq. ft. floor trussesNO
Anchor Bolts 6 ft. or less on centerNO
Ice and water shield 24 inches from wallYES6/29/18 Ice & Water Shield Approved
Soffits-Insulation BaffelNO
Windows Habitable Space BedroomsNO
24 in. (H)NO
20 in. (W)NO
5.7 sf above below gradeNO
5.0 sf gradeNO
Design Professional Sign-off, if requiredNO
O'Brien, John (Inspector)
Jan 23, 2019Page (3)