blower door results
Vestal Office
Wappingers Falls Office
Main Office
414 Commerce Road
95 Airport Drive – Suite 1
868 Burdeck Street
P.O Box 66
Wappingers Falls, NY 12590
Schenectady, NY 12306
Vestal, NY 13851
Tel. (845) 452-5400
Tel. (518) 355-0433
Tel. (607) 729-5847
Fax. (845) 452-1606
Fax. (518) 355-3174
Fax. (607) 797-7520
www.appoloheating.com
Property Address 59 Richmond Hills Dr, Queensbury Ny
Builder Hodorowski
Date of test 2/12/20
Model of Home
Ceiling
Level Square Feet Height Air Volume (Cu. Ft.)
Basement 935 8 7480
1 st Floor 714 9 6426
2nd Floor 927 8 7416
Family Room 221 17 3757
Total 2797 25079
Blower Door Test
TEC Minneapolis Blower Door with TEC DG-1000
Equipment Used Manometer
Fan Configuration A Ring
Measured CFM50 1242
Calculated ACH50 3.0
Testing done in accordance with ASTM E 1827-11
I hereby certify and attest to the accuracy of the testing results
Test performed by:
Nick Abrunza
Energy Auditor/
BPI Certification Number: 5059019
APPOLOHEAT1
Degrees Above The Rest,S/WCEaCertificateofCompletionP.c-0494-ZO
Duct Sealing Performed For:200
Hodorowski,Appolo Heating
59 Richmond Hills Dr
Queensbury,NY 12804 250
=200 \
Overall Sealing Results ie \When we arrived,z 0 Y
YOUR DUCTS HAD:Z \281.3 CFM of Leakage,equivalent to a ion Ni
53.1 Square Inch Hole NO
This equals 168.8 refrigerators full of air loss every 50 —hour.MN
After we finished,0.
YOUR DUCTS HAVE:cn aw Oo DO Re
28.2 CFM of Leakage,equivalent to a ‘Sealing Time in Minutes
5.3 Square Inch Hole
This corresponds to a 90.0%Reduction in
Duct Leakage.
Aeroseal Technician Nick
Aeroseal Case ID 5068
Date of Seal 1/30/2020
System Description Upflow Basement
Note:Duct Leakage results are calculated in SE ae em
Cubic Feet per Minute (CFM)measured at a Seal Description Basement Return
standard OPERATING PRESSURE of 25 Pa.(ey Dor
AEROSEAL.Duc Seating Performed By:
rearDuctSeatingFromThe.Appolo Heating,Inc
“4 868 Burdeck St |
‘Schenectady,NY 12306 |
Phone:(518)355-0433 (|FEB 13 20
~APPOLOHEAT1
Degrees Above The Rest,aaie
Certificate of Completion .._,eerie aaDuctSealingPerformedFor:
Hodorowski,Appolo Heating
59 Richmond Hills Dr
Queensbury,NY 12804
Overall Sealing Results
When we arrived,
YOUR DUCTS HAD:
291.8 CFM of Leakage,equivalent to a
55.1 Square Inch Hole
This equals 175.1 refrigerators full of air loss every
‘hour.
After we finished,
YOUR DUCTS HAVE:
33.1 CFM of Leakage,equivalent to a
6.3 Square Inch Hole
This corresponds to a 88.7%Reduction in
Duct Leakage.
Note:Duct Leakage results are calculated in
Cubic Feet per Minute (CFM)measured at astandardOPERATINGPRESSUREof25Pa.
300.
wl
\7Fw N
2||)
S 100.aL
0.
0 0 20 3 4 50 6
‘Sealing Time in Minutes.
7
AEROSEAL.Duct Sealing From The Inside
‘Aeroseal Technician Nick
‘Aeroseal Case ID 5068
Date of Seal 1/30/2020
System Description Upfow Basement
Seal Description Basement supply
Hardware HomeSeal Connect
Duct Sealing Performed By:
‘Appolo Heating,nc.
£868 Burdeck St
Schenectady,NY 12306 |
Phone:(518)355-0433,|