Signed Inspection Report (02-18-2020) (3).pdfINSPECTION WORKSHEET (FRM-000957-2020)
Town of Queensbury - Building and Codes - Fire Marshal
742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal
Case Number:AST-0593-2019 Case Module:Permit
Inspection Date:Tue Feb 18, 2020 Inspection Status:Partial Pass
Inspector:John O'Brien Inspection Type:Building Framing
Job Address:Parcel Number:133 Jenkinsville RD
Queensbury, NY, 12804
279.-1-21
Contact Type Company Name Name
Architect Rucinski-Hall Architecture
Granted Permission TOWN OF QUEENSBURY REC
DEPT
Primary Owner TOWN OF QUEENSBURY REC
DEPT
Concrete Contractor A.J. Catalfamo Construction Co., Inc.
Checklist Item Status
Building Inspector Notes Failed
2/3/20 Framing Not Approved
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
- Framing needs to be inspected behind fire retardant plywood. Remove one sheet of fire retardant plywood from
each wall so we may verify the framing.
- Workshop has not been framed in accordance with the approved walls. Please let us know if this has been
deleted from project.
2/18/20 Framing Partial Approval
- Non-bearing interior partitions approved.
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
Feb 18, 2020 Page (1)
INSPECTION WORKSHEET (FRM-000957-2020)
Checklist Item Status
Framing Failed
2/3/20 Framing Not Approved
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
- Framing needs to be inspected behind fire retardant plywood. Remove one sheet of fire retardant plywood from
each wall so we may verify the framing.
- Workshop has not been framed in accordance with the approved walls. Please let us know if this has been
deleted from project.
2/18/20 Framing Partial Approval
- Non-bearing interior partitions approved.
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
Air Seal all Plates and Sills Failed
Air Sealing all Joints Before Insulation Failed
Jack Posts Main Beams Failed
Anchor Bolts 6 ft. or less on center Failed
Design Professional Sign-off, if required Failed
2/3/20 Framing Not Approved
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
- Framing needs to be inspected behind fire retardant plywood. Remove one sheet of fire retardant plywood from
each wall so we may verify the framing.
- Workshop has not been framed in accordance with the approved walls. Please let us know if this has been
deleted from project.
2/18/20 Framing Partial Approval
- Non-bearing interior partitions approved.
Remaining Items:
- Structural steel needs to be inspected by a third party engineer.
Feb 18, 2020 Page (2)
O'Brien, John