Loading...
spray foam insulation info Johns Manville JM C O R B O N D JI A Berkshire Hathaway Company INSULATION CERTIFICATE This form MUST BE filled out and posted to comply with building code requirements. Meets IRC Sections rerequirements: 2009 IRC: N1101.2, N1101.4, N1101.8 2012 IRC: N1101.3, N1101.5, N1101.7, N1101.12 2015 IRC: N1101.3, N1101.4, N1101.7, N1101.10 The following spray applied polyurethane foam product(s) have been installed: ❑ JM Corbond oc SPF 0.5 lb/ft3 ICC ES ESR-3776 I CCRR-1079 ❑ JM Corbond ocx SPF 0.5 lb/ft3 UES ER-372 ✓❑ JM Corbond III 2.0 lb/ft3 UES ER-0146 In accordance with the 2015 International Building Code, Chapter 26, and the 2015 International Residential Code, R316, requirements for the foam plastics the insulation system(s) referenced above have been installed according to manufacturers' recommendations and to local building code requirements. For additional recommendations refer to ICC ES ESR-3776 or CCRR-1079 for JM Corbond oc SPF, IAPMO UES ER-372 for JM Corbond ocx SPF, and IAPMO UES ER-0146 for JM Corbond III. The following thermal resistance values have been installed: AREA INSULATED R-Value Thickness (inches) * Attic Area Sloped Ceilings R-38 5.5" Walls R-21 3.0" Floors Basement Walls Other Rim Joists_Basement R-24 3.25" Other * Nominal thicknesses are representative of field spray-applied foam material Job-site Address: 15 Warren St.Queensbury,NY Building Contractor: Do For You Construction Insulation Contractor: Advanced Spray Foam Inc Insulation Contractor Phone: 518.309.5141 Installed By: Date of Installation: 06i2020 DO NOT REMOVE THIS CERTIFICATE PLEASE POST NEAR ELECTRICAL PANEL For additional information: Q www.JM.com ❑ 800.654.3103 DID-328 12/18 2018 Johns Manville.All Rights Reserved.717 17th Street,Denver,CO 80282 tit* EVALUATION REPORT Number: 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 JOHNS MANVILLE 2.4 JM Corbond III® insulation shall be installed by 71717th Street contractors certified by SPFA or Johns Manville. Denver,Colorado 80202 2.5 When JM Corbond III®insulation is used in areas where 800-654-3103 the likelihood of termite infestation is"very heavy,"it shall www.soecim.com be installed in accordance with IBC Section 2603.9 (2009 IBC Section 2603.8)or IRC Section R318.4,as applicable. JM CORBOND ill®PERFORMANCE INSULATION SYSTEM® 2.5.1 When JM Corbond III® is used in conjunction with wood construction, in jurisdictions that have adopted NFPA CSI Section: 5000,and where termite infestation is known to be heavy,the 07 2100 Thermal Insulation foam plastic shall be installed in accordance with NFPA 5000 Section 45.6.9.5. 1.0 RECOGNITION 2.6 When used in exterior walls of buildings of Type I,II,III Johns Manville JM Corbond Ill® Performance Insulation or IV construction, application shall be as described in System®described in this report was evaluated for use as Section 3.5 of this report. foam plastic insulation. The surface burning characteristics, thermal performance, physical, air infiltration, vapor 3.0 PRODUCT USE permeance, fungal resistance,and thermal barrier properties of the Johns Manville JM Corbond III® were evaluated for JM Corbond III® is a non-structural, closed cell, spray compliance with the following codes: applied,polyurethane foam plastic insulation for use in wall cavities,floor assemblies,ceiling assemblies, and attics and • 2015,2012 and 2009 International Building Code® crawl spaces. The foam plastic insulation complies with (IBC) Section 2603 of the IBC, Section R316 of the IRC, and • 2015, 2012 and 2009 International Residential Sections C402 and R402 of the IECC(2009 IECC Sections Code®(IRC) 303 and 402)and Section 4804 ofNFPA 5000 for the specific uses described in this report. The insulation may be used in • 2015, 2012 and 2009 International Energy buildings of Types I, II, III, IV, and V construction per the Conservation Code®(IECC) IBC,residential structures constructed in accordance with the • 2015, 2012 and 2009 NFPA 5000 Building IRC,and buildings of Type I,II,III,N,and V construction Construction and Safety CodeTM per NFPA 5000. 2.0 LIMITATIONS 3.1 General Use of the JM Corbond III® spray-applied foam plastic 3.2 Application insulation described in this report is subject to the following limitations: 3.2.1 JM Corbond III®shall be installed by spray application using a dual component, volumetric, positive displacement 2.1 The product shall be installed in accordance with the proportioner to combine A- and B-components in a one to manufacturer's published installation instructions, this one volumetric ratio, as specified in the manufacturer's evaluation report and the applicable code. In the event of a installation instructions. conflict the more restrictive shall govern. 3.2.2 JM Corbond III®shall not be applied to areas where the 2.2 JM Corbond III® insulation shall be protected by a 15- maximum service temperature is greater than 180°F(82°C). minute thermal barrier in accordance with Section 4.3 of this JM Corbond®III shall be applied to substrates that are clean, report except when installation complies with one or more of dry,and free from frost,ice,loose debris or contaminants that the following: will interfere with the adhesion of the spray foam insulation. JM Corbond III® shall not be applied in electrical outlets, (1)Exceptions specifically provided in the applicable code; junction boxes,to substrates over 120°F(49°C),or in direct (2)Section 3.3.3(Application without a Prescriptive Thermal contact with water and shall be protected from the weather Barrier)of this report; during application. (3)Section 3.4(Attics and Crawl Spaces)of this report. 3.2.3 JM Corbond III®may be applied in passes of uniform 2.3 Theinsulation components are produced by Johns thickness from a minimum of'A inch(13 mm)to a maximum Manville under a quality control program with inspections of 31/2 inches(89 rem)per pass.The total thickness shall be under the supervision of UES. as specified in Sections 3.3,3.4,and 3.5 of this report.(111E11)The product described in this Uniform Evaluation Service(UES)Report has been evaluated as an alternative material,design or method of construdion in order to satisfy and comply with the intent of the provision of the code,as noted in this report,and for at least equivalence to that prescribed in the code in quality,strength,effectiveness,fire resistance,durability and safely, as applicable,in accordance with IBC Section 104.11.This document shall only be reproduced in its entirety. Copyright®2018 by International Association of Plumbing and Mechanical Officials.All rights reserved.Printed in the United States. Ph:1-877-41ESRPT•Fax:909.472.4171 �SI w.web:wwuniform-es.org•4755 East Philadelphia Street,Ontario,California 91761-2816—USA �e®rt® 1f°1FC 17016 Page 1 of 9 Product Coronado,Body EVALUATION REPORT Number: 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 "Flash"passes or a thin pass of less than 1 inch(25 mm)on 3.4.3 Application without a Prescriptive Ignition Barrier: cold surfaces is to be avoided and may result in loss of The spray-applied foam plastic insulation may be installed adhesion of subsequent passes.Thicknesses over 31/2 inches without a prescriptive ignition barrier in accordance with (89 mm) require multiple passes in accordance with Section 3.4.2.1, 3.4.2.2 or 3.4.2.3 of this report,when all of manufacturers installation instructions. the following conditions apply,as applicable: 3.3 Thermal Barrier a) Entry to the attic or crawl space is only to service utilities,and no storage is permitted. 3.3.1 General: JM Corbond III® shall be covered with a b) Attic ventilation is provided when required by IBC thermal barrier except as specifically excluded by the Section 1203.2 or IRC Section R806, except when applicable code. an air-impermeable insulation is permitted in unvented attics in accordance with Section R806.4 3.3.2 Application with a Prescriptive Thermal Barrier: of the IRC.Under-floor(crawl space)ventilation is JM Corbond®III may be applied at any thickness in ceiling provided when required by 2015 IBC Section cavities and in wall cavities when separated from the interior 1203.4(2012 and 2009 IBC Section 1203.3)or IRC of the building by a prescriptive thermal barrier(minimum Section R408.1,as applicable. 1/2-inch[12.7 mm]thick gypsum board).The gypsum board shall be installed in accordance with the applicable provisions c) The foam plastic insulation is limited to the in Section 2508 of the IBC, Section R702.3 of the IRC or maximum thickness and density stated in this report. Section 47.2 of NFPA 5000 in such a manner that the foam d) Combustion air is provided in accordance with plastic is not exposed. Sections 701 and 703 (2006 IMC)and Section 701 (2009 IMC). 3.3.3 Application without a Prescriptive Thermal e) The installed coverage rate or thickness of coatings, Barrier: JM Corbond III® may be installed without a if part of the insulation system,shall be equal to or prescriptive thermal barrier when it has been installed in greater than that which was tested. accordance with one of the assemblies in Table 2 of this f) Attic and crawl spaces do not have interconnected report. areas. g) Air in the attic or crawl space is not circulated to 3.4 Attics and Crawl Spaces other parts of the building. 3.4.1 General: When installing JM Corbond III® in attics 3.4.3.1 Attic and Crawl Space Overhead and Vertical and/or crawl spaces and a thermal barrier is omitted in Surfaces Covered with an Alternative Ignition Barrier: accordance with IBC Section 2603.4.1.6, IRC Sections JM Corbond III®spray foam insulation may be spray-applied R316.5.3 or R316.5.4 or Section 48.3.3.4 of NFPA 5000, without a prescriptive ignition barrier to overhead surfaces installation shall comply with either Sections 3.4.1 or 3.4.2 and/or vertical surfaces when covered with an alternative of this report. ignition barrier as described in Sections 3.4.2.1.1,or 3.4.2.1.2 (and as summarized in Table 5)of this report. JM Corbond® III spray-foam insulation qualifies as an air- impermeable insulation and, when installed in accordance 3.4.3.1.1 JM IC Ignition Barrier: Surfaces to be coated with Sections 3.4.2 or 3.4.3 of this report, may be used to shall be dry, clean, and free of dirt, loose particles and any insulate unvented attics and/or unvented cathedral ceilings in other substances that could interfere with adhesion of the accordance with 2015 IRC Section R806.5 (2012 and 2009 coating. Back-rolling of sprayed material may be necessary IRC Section R806.4). to fill pinholes in substrates.The JM IC Ignition Barrier shall be applied with a medium-size nap roller, soft brush or 3.4.2 Application with a Prescriptive Ignition Barrier: conventional airless spray equipment to a minimum dry film When JM Corbond III® insulation is installed within attics thickness of 3 mils(0.08 nun)(requiring an application rate and crawl spaces where entry is made only service of utilities, of approximately 4 wet mils[0.10 mm]or 345 ft2/gal[8.3 m2 the insulation shall be protected by an ignition barrier in /L]).The coating shall be applied in accordance with the JM accordance with IBC Section 2603.4.1.6, IRC Sections IB Product Data Sheet and this report. The maximum R316.5.3 and R316.5.4 or Section 48.3.3.4 of NFPA 5000,as thickness of JM Corbond® III is limited to 5'/2 inches (140 applicable. The ignition barrier shall be consistent with the mm)on overhead surfaces and 31/2 inches(89 mm)on vertical construction type of the building.The ignition barrier shall be surfaces. installed in accordance with the provisions applicable to the material referenced in the IBC,IRC or NFPA 5000 in such a 3.4.3.1.2 JM Spider® with adhesive: JM Spider® with manner that the foam plastic is not exposed. The maximum adhesive shall be installed by insulation contractors who have thickness of JM Corbond®III is limited to 11'/z inches(292 been trained and certified by Johns Manville.Installers shall mm) on overhead surfaces and floors and 9'/. inches (235 use only the JM Spider® Insulation Delivery System mm)on vertical surfaces. equipment engineered and specified by Johns Manville. JM Spider®with adhesive shall be applied in accordance with Page 2 of 9 ttltzt EVALUATION REPORT Number: 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 Johns Manville installation specifications. If the installation 4.0 PRODUCT DESCRIPTION temperatures are below 50°F (10°C) the adhesive shall be heated and applied per Johns Manville specifications. JM 4.1 General Spider® with adhesive spray-on insulation shall be installed at a minimum 2'A inches(63.5 mm)thickness and a nominal 4.1.1 JM Corbond III® is a two-component, spray-applied, density of 1.8 pcf(28.8 kg/m3). The maximum thickness of medium-density, closed-cell polyurethane foam plastic JM Corbond® III is limited to 10 inches (254 mm) on insulation system having a nominal core density of 2.0 pcf overhead surfaces and 8 inches (203 mm) on vertical (32 kg/m3).The foam plastic is generated by combining the surfaces. isocyanate (A-component) and a polymeric resin (B- component)through a dual component proportioner,on site, 3.4.3.2 Attic Floors: JM Corbond III® insulation may be by SPFA certified or Johns Manville certified applicators. installed exposed(no coating),without an ignition barrier up All materials shall be stored in their original containers, to a maximum thickness of 11%2 inches (292 mm) between which shall be kept out of direct sunlight and away from heat and over the joist in attic floors. The insulation shall be and moisture. When stored unopened and indoors at a separated from the interior of the building by a minimum ''A- temperature between 50°F(10°C)and 80°F(27°C),the shelf inch (12.7 mm) thick gypsum board or an approved life for A-component isocyanate is 12 months, and B- equivalent thermal barrier, which shall be installed in component polymeric resin is 6 months. Prior to use, both accordance with the provisions set forth in the IBC,IRC,or components(A and B)shall be conditioned in a manner that evaluation report. The ignition barrier required by IBC results in drum temperatures between 60°F(16°C)and 75°F Section 2603.4 and IRC Section R316.5.3 may be omitted in (24°C). this case. 4.1.2 A-component isocyanate and B-component polymeric 3.4.3.3 Attic and Crawl Space Overhead and Vertical resin properly mixed and applied yields a Lavender®finished Surfaces Without an Ignition Barrier: The JM Corbond foam insulation product. The Lavender® color is a Federal III®can be installed exposed(no coating),without an ignition Registered Trademark color of Johns Manville. barrier when installed as required in this section.JM Corbond III®insulation may be spray-applied in attics to the underside 4.2 Surface Burning Characteristics of roof sheathing, roof rafters and vertical surfaces, and in crawl spaces to the underside of floors and vertical surfaces. 4.2.1 JM Corbond III®, when tested in accordance with When applied to the underside of the top of the space, the ASTM E84,at a maximum thickness of 4 inches(102 mm), thickness of the JM Corbond III®insulation shall not exceed and a nominal core density of 2.0 pcf(32 kg/m3),has a flame 71/2 inches(191 mm)and when applied to vertical surfaces, spread index of less than 25 and a smoke developed index of the maximum thickness shall not exceed 5'/2 inches (140 not more than 450. mm). 4.2.2 Thicknesses are not limited for ceiling cavities and wall 3.5 Exterior Walls of Types I,II,III and IV Construction cavities when covered by a prescriptive thermal barrier (IBC) (minimum 'A-inch [12.7 mm] thick gypsum board) in accordance with Section 3.3.1 of this report.Thicknesses of 3.5.1 When used on exterior walls of Type I, II,III and IV up to 11'/:inches(292 mm)for ceiling or floor cavities and construction,JM Corbond III®spray-applied foam insulation 7%z inches (191 mm) for wall cavities are recognized based shall comply with Section 2603.5 of the IBC or Section on testing in accordance with NFPA 286,when installed in 48.4.1 of NFPA 500,as applicable and Section 3.5.2 of this accordance with Section 3.3.2 of this report. report,and shall be installed at a maximum thickness of 3'/2 inches(88.9 mm).The potential heat of the JM Corbond III® 4.3 Thermal Resistance:The R-value of JM Corbond III®is is 1991 BTU/ft2 (22.4 MJ/m2) per inch of thickness when 7.0 per inch regardless of thickness. Table 1 of this report tested in accordance with NFPA 259. provides additional information on the values of thermal resistance(R-Value)for specific thicknesses. 3.5.2 Specific Wall Assemblies: Wall assemblies shall be constructed as described in Tables 3 and 4 of this report. 4.4 Water Vapor Resistance:JM Corbond III®,when tested in accordance with Procedure A of ASTM E96,has a vapor 3.6 Installation permeance of less than 1 perm(57 ng/Pa-s-m2)at a minimum thickness of 1.5 inches(38 mm), and qualifies as a Class II 3.6.1 Installation General: JM Corbond III® shall be vapor retarder as defined in IBC Section 202, IRC Section R202 and 2015 NFPA 5000 Section 3.3.662.1 (2012 and installed in accordance with the manufacturer's installation 2009 NFPA 5000 Section 3.3.644.1). instructions, the applicable code and this report. Where conflicts occur the more restrictive shall govern. The 4.5 Air Permeability: JM Corbond III®, when tested in installation instructions and this report shall be made accordance with ASTM E283 at a minimum thickness of 1.0 available upon request. inches(25.4 mm) exhibits a maximum total air leakage rate of 0.02 L/s-m2(0.004 ft3/min-ft2)when tested at a 75 Pa Page 3 of 9 • kilt, EVALUATION REPORT Number: 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 pressure differential and qualifies as an air-impermeable 5.0 IDENTIFICATION insulation for use in attics in accordance with the applicable code. Jobsite labeling and certification of the insulation shall comply with IRC Sections N1101.10 and 1101.10.1 (2012 4.6 Fungal Resistance: JM Corbond III®, when tested in IRC Sections 1101.12 and 1101.12.1 and 2009 IRC Sections accordance with ASTM C1338 exhibits no fungal growth. N1101.4 and N1101.4.1) and IECC Sections C303.1.1 and C303.1.2, R303.1.1 and R303.1.2 as applicable. Each 4.7 Fire Protective Coatings component for the JM Corbond III® is identified with the following: 4.7.1 JM IC (aka TPR2 Fireshell® IB4): JM IC ignition barrier coating is manufactured by Thermal Products • Manufacturer's name (Johns Manville), address and Research (TPR2).The coating is water-based and available telephone number, in both 5-gallon (18.9 L) and 55 gallon (208 L) containers • Product trade name(JM Corbond III®), and has a shelf life of 12 months when stored in factory- • Product density, sealed containers above 45°C(7°C). • Flame-spread and smoke-development indices and the name of the inspection agency (IAPMO R & T 4.7.2 JM TC (aka Fireshell® F10/E/TB): JM TC thermal Laboratory), barrier coating is manufactured by Thermal Products • Evaluation report number(ER146),and the name of the Research(TPR2). The coating is water-based and available inspection agency(IAPMO ES). in both 5-gallon (18.9 L) and 55 gallon (208 L) containers and has a shelf life of 12 months when stored in factory- Either Mark of Conformity may be used as shown below: sealed containers above 45°C(7°C). 4.7.3 DC315 Fireproof Paint: DC315 Fireproof Paint, recognized in ER-499, is a water-based latex intumescent I A p M U E coating manufactured by International Fireproof Technology, Q S Inc. and is supplied in 5-gallon (19 L) pails and 55-gallon E S (208 L) drums. When stored in factory-sealed containers at temperatures between 50°F (10°C) and 80°F (27°C), the TM or coating has a shelf life of 12 months. I %I'MO UES ER-146 4.7.4 No-Burn® Plus ThB Coating: No-Burn Plus ThB coating,recognized in ER-305, is a water-based latex liquid 6.0 SUBSTANTIATING DATA manufactured by No-Burn,Inc.,which exhibits intumescent properties when exposed to elevated temperatures and flame. 6.1 Data in accordance with ICC-ES Acceptance Criteria for The product is packaged in 5-gallon pails and 55-gallon Spray-Applied Foam Plastic Insulation (AC377) Approved drums and has a shelf life of eighteen months when stored in April 2016. unopened containers between 40°F and 90°F. 6.2 Reports on air leakage tests in accordance with ASTM 4.8 JM Spider®Ignition Barrier E283. 4.8.1 JM Spider® ignition barrier is supplied by Johns 6.3 Reports on water vapor transmission tests in accordance Manville Corporation. The JM Spider®loose-fill glass fiber with ASTM E96. material is mixed with an adhesive during the spraying process and adheres to the foam plastic. The JM Spider®is 6.4 Reports on Fungal Resistance tests in accordance with available in 30 lb(13.6 kg)bags.The ignition barrier shall be ASTM C1338. kept clean and dry at all times. The spray-applied fiberglass product may be installed at variable thickness levels,and may 6.5 Reports on flame spread and heat release in accordance be used for both wall and ceiling applications. with NFPA 286. 4.8.2 The JM Spider®adhesive comes in totes and 55-gallon 6.6 Reports on Exterior Fire Propagation tests in accordance (208 L) drums. The adhesive shall be stored in a cool, dry with NFPA 285. area in original packaging and at temperatures above 40°F (4.4°C). 6.7 Reports on Potential Heat tests in accordance with NFPA 259. 6.8 Reports on Heat Release and Flame Propagation in accordance with AC377 Appendix X. Page 4 of 9 %!tt EVALUATION REPORT Number: 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 7.0 STATEMENT OF RECOGNITION This evaluation report describes the results of research carried out by IAPMO Uniform Evaluation Service on Johns Manville JM Corbond III® to assess their conformance to the codes shown in Section 1.0 of this report and serves as documentation of the product's certification. Products are manufactured under a quality control program with periodic inspections under the supervision of IAPMO UES. Brian Gerber,P.E.,S.E. Vice President,Technical Operations Uniform Evaluation Service i/e10,401/ Richard Beck,PE,CBO,MCP Vice President,Uniform Evaluation Service GP Russ Chan y CEO,The IAPMO Group For additional information about this evaluation report please visit www.uniform-es.org or email us at infouniform-es.org Page 5 of 9 • • • kilt* EVALUATION REPORT Number: T" Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 TABLE 1-THERMAL RESISTANCE (R-Value)1 Thickness(Inch) R-Value(°F.ft2.h/Btu) 1.0 7.0 2.0 14 3.0 21 3.5 24.5 4.0 28 5.0 35 5.5 38.5 6.0 42 7.0 49 8.0 56 9.0 63 10.0 70 11.0 77 12.0 84 For SI: 1 inch=25.4 mm; 1 °F•ft2•hr/Btu=0.176110°K•m2•hr/W. 1R-values are calculated based on tested k-factors at 1-and 4-inch thicknesses TABLE 2: ALTERNATE ASSEMBLIES WITHOUT A PRESCRIPTIVE THERMAL BARRIER''2 Coating Max.Insulation Max.Insulation Dry Film Wet Film Application Rate' Thickness Thickness Thickness Thickness (theoretical) Overhead Vertical Surfaces (nominal) Surfaces JM TC (aka 11.5 in. 7.5 in. 12 mils 18 mils 86 ft2/gal FIRESHELL® 292 mm 191 mm 0.30 mm 0.46 mm 2.11 m2/L F10E) DC315 11.5 inches 7.5 inches 9 mils 14 mils 115 ft2/gal 292 mm 191 mm 0.23 mm 0.36 mm 2.82 m2/L Plus ThB 8 inches 6 inches 9 mils 14 mils 115 ft2/gal 203 mm 152 mm 0.23 mm 0.36 mm 2.82 m2/gal Notes: 'Theoretical coating application rates are based strictly on minimum wet film thickness requirements and shall be increased for site-specific conditions such as foam plastic surface texture, overspray loss, container and other residues, application technique and environmental conditions. 2 The coatings shall be applied in accordance with the Product Data Sheet and this report in such a manner that the foam plastic is not exposed. Page 6 of 9 • krItt EVALUATION REPORT Number: : 46 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 TABLE 3: NFPA 285 COMPLYING WALL ASSEMBLIES WITH JM CORBOND III IN WALL CAVITY WALL COMPONENTS MATERIALS Base Wall System' 1. Concrete wall (Use either 1, 2 or 3) 2. Concrete masonry wall 3. 1 layer of 5/8-inch thick Type X gypsum wallboard installed on the interior side of minimum 35/s-inch deep,minimum 25-gauge equivalent thick steel studs spaced a maximum of 24 inches on center. Lateral bracing installed minimum every 4 feet vertically or as required. Wall stud cavities shall be filled at each floor line with minimum 4 lb/ft3 mineral wool(e.g. JM MinWool®Safing)friction fit between steel wall studs. Perimeter Fire Barrier System Perimeter fire barrier system complying with Section 715.4 of the 2015 IBC shall be installed, as applicable, to fill the void between the edge of the concrete floor slab and the interior surface of the exterior wall assembly(see note 1). Interior Insulation 1. None (Use either 1,2, 3,4, 5 or 6 2. Maximum 35/8-inch thickness of Corbond III CC SPF applied to interior surface of Base Wall System 1 and 2(See Note 1). 3. Full wall stud cavity depth or less of Corbond III CC SPF applied using exterior gypsum sheathing of Base Wall System 3 as the substrate and covering the width of the cavity and the inside of the steel wall stud framing flange. 4. Fiberglass batt insulation(faced or unfaced) 5. Mineral wool insulation(faced or unfaced) 6. Hybrid Systems:spray foam and/or fiberglass insulation or mineral wool insulation (flash and bat insulation systems) Exterior sheathing 5/8-inch thick Type X exterior gypsum sheathing(for Base Wall System 3 above) Exterior Wall Covering2 Any non-combustible exterior wall covering material using any standard installation technique Window Closure Minimum 0.08-inch thick aluminum, or equivalent Flashing of window, door and other As an option, flash around window, door and other exterior penetrations with limited exterior wall penetrations amounts of maximum 12-inch wide flashing tape(acrylic, asphalt or butyl-based)or liquid applied membrane material with or without fiber mesh reinforcement. For SI:1 inch=25.4 mm;1.0 pcf=16 kg/m3 Notes: 'Fireblocking per IBC Section 718(2009 IBC Section 717)and thermal barrier material requirements must be met for Base Wall Systems 1 and 2,as required by specific wall construction details when combustible concealed space is created on interior side of exterior wall assembly. 2 Non-combustible exterior wall coverings shall be installed in accordance with manufacturer's installation requirements. Page 7 of 9 • ktto EVALUATION REPORT Number: ... 146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 TABLE 4: NFPA 285 COMPLYING WALL ASSEMBLIES WITH CORBOND III INSTALLED ON THE EXTERIOR WALL COMPONENTS MATERIALS Base Wall System' 1. Concrete wall (Use either 1,2 or 3) 2. Concrete masonry wall 3. 1 layer of 5/8-inch thick Type X gypsum wallboard installed on the interior side of minimum 35/8-inch deep, minimum 25-gauge equivalent thick steel studs spaced a maximum of 24 inches on center. Lateral bracing installed minimum every 4 feet vertically or as required. Wall stud cavities shall be filled at each floor line with minimum 4 lb/ft3 mineral wool(e.g. JM MinWool®Safing)friction fit between steel wall studs. Perimeter Fire Barrier System Perimeter fire barrier system complying with Section 715.4 of the 2015 IBC shall be installed, as applicable, to fill the void between the edge of the concrete floor slab and the interior surface of the exterior wall assembly(see note 1). Interior Insulation 1. None (Use either 1,2, 3,4, 5 or 6 2. Maximum 35/8-inch thickness of Corbond III CC SPF applied to interior surface of Base Wall System 1 and 2(See Note 2). 3. Full wall stud cavity depth or less of Corbond III CC SPF applied using exterior gypsum sheathing of Base Wall System 3 as the substrate and covering the width of the cavity ad the inside of the steel wall stud framing flange. 4. Fiberglass batt insulation(faced or unfaced) 5. Mineral wool insulation(faced or unfaced) 6. Hybrid Systems:spray foam and/or fiberglass insulation or mineral wool insulation (flash and bat insulation systems) Exterior Sheathing 1. None(for Base Wall Systems 1 or 2 above) (Use either 1, 2 or 3) 2. %-inch thick glass mat exterior gypsum sheathing complying with ASTM C1177 (for Base Wall System 3 above) 3. 5/8-inch thick Type X exterior gypsum sheathing(for Base Wall System 3 above) Exterior Insulation Maximum 3%-inch thickness of Corbond III CC SPF Exterior Wall Covering 1. Brick—Standard type brick veneer anchors, installed a maximum of 24 inches on (Use either 1,2, 3,4 or 5) center, vertically on each stud with maximum 1-inch air gap between exterior insulation and brick. Brick to be standard nominal 4-inch thck clay brick installed in a running bond pattern using Type S mortar. 2. Stucco— Minimum %-inch thick, exterior cement plaster and lath. A secondary water-resistive barrier(WRB)can be installed between the exterior insulation and the lath. The secondary WRB shall not be full-coverage asphalt or butyl-based self-adhered membranes. 3. Minimum 2-inch thick natural stone(granite, limestone, marble, sandstone). Any standard non-open jointed installation technique can be used. 4. Minimum 1%-inch thick concrete masonry unit (CMU), precast concrete, or artificial cast stone. Any standard non-open jointed installation technique can be used. 5. Minimum 1'/,-inch thick Terra Cotta non-opened jointed. Any standard non-open jointed installation technique can be used. Window Closure Minimum 1-gauge steel flashing, or equivalent Flashing of window, door and other As an option, flash around window, door and other exterior penetrations with limited exterior wall penetrations amounts of maximum 12-inch wide flashing tape (acrylic, asphalt or butyl-based)or liquid applied membrane material with or without fiber mesh reinforcement. For SI: 1 inch=25.4 mm; 1.0 pcf=16 kg/m3 Notes: 'Fireblocking per IBC Section 718(2009 IBC Section 717)and thermal barrier material requirements must be met for Base Wall Systems 1 and 2, as required by specific wall construction details when combustible concealed space is created on interior side of exterior wall assembly. Page 8 of 9 kit* EVALUATION REPORT Number: ,146 TM Originally Issued: 07/31/2015 Revised: 12/11/2018 Valid Through: 07/31/2019 TABLE 5: ALTERNATE IGNITION BARRIERS Coating/Cover Max.Insulation Max.Insulation Dry Film Wet Film Application Rate Thickness Thickness Thickness Thickness (nominal) Overhead Vertical Surfaces (nominal) Surfaces JM IC Ignition 5% inches 3%inches 3 mils 4 mils 345 ft2/gal Barrier Coating 140 mm 89 mm 0.08 mm 0.1 mm 8.3 m2/L (aka Fireshell®IB4) JM Spider® 10 inches 8 inches 2.5 inches NA NA 254 mm 203 mm 64 mm Notes: NA=Not Applicable Page 9 of 9