Manual S Mane ?Q S C m Bence Report Job: 51 JOHN GLENDON DR p Date: Jun 22,2018 Entire House By: FOOTHILL, BUILDERS Plan: 1341 QUEENSBURY,NY 12804 ii a�-�;.7:1 ' `+#�q�'� '°'4'..'�i'+F.j+bt `#;.' ro ji• I• o For: JOE, FOOTHILL BUILDERS QUEENSBURY, NY 12804 — Design Conditions Outdoor design DB: 85.0°F Sensible gain: 18645 Btuh Entering coil DB: 75.3°F Outdoor design WB: 71.0°F Latent gain: 4660 Btuh Entering coil WB: 62.6°F Indoor design DB: 75.0°F Total gain: 23305 Btuh Indoor RH: 50% Estimated airflow: 892 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split AC Manufacturer: York Model: TCHD30S41S3+HD36A3XH1+TM8X060Al2MP11+S1-1TVM4G1 Actual airflow: 933 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load Total capacity: 0 Btuh 0% of load SHR: 0% > nar�si f xa 4 �x � qurne�f , ►� ' „�.�ttmbm+.iaca3a.d4. � ..:��3.s��au_.�`rr.;� ,�'..._..� .f•4._.,.::� Design Conditions Outdoor design DB: -4.0°F Heat loss: 82596 Btuh Entering coil DB: 65.4°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Gas furnace Manufacturer: York Model: TM9X060B12MP11 Actual airflow: 933 cfm Output capacity: 57000 Btuh 69% of load Temp. rise: 50 °F . CERWE TOWN OF QUEENSBURY Meets are all requirements of ACCA Manual S. BUILDING&CODES 2018-Jun-22 14:15:11 41- wrightsoft° Right-Suite®Universal 201717.0_16 RSU25116 Page 1 ACCK ....langeworthy\DocumentsWork\51 JOHN CLENDON.rup Cale=MJ7 Front Door faces: N , x t `.r�'F£^e, cyst ,P: 4401tS rz 11- ' -.•-- -'"' s�.a - „„ Re Idr�tlal Pans ��arnlner Revievrr orm RPER`1 ACCs ,.:_,_,„„,,,,..„,-„,,,,,_, „,.„,,,...-,,,,,,---a--,} V S Ir � Equipment, Ducts)Ada �� lU1ar09 ® r�N ;.14 ,1- z. ,.»..,,� -'-'4 l 3- M 3 yf1v,( KJ r r "iR 4'"4{«i' - -, ,v'7 Y. - PsGxrRixvigCai7mhcsoFPa�=i.:a ,. - . QUEENSBURY NY Header Information Contractor: FOOTHILL BUILDERS REQUIREDATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes El No El Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes 0 No D OEM performance data(heating,cooling,blower): Yes 0No D Building plan#: 1341 Manual D Friction Rate Worksheet: Yes 0 No [] Duct distribution sketch: Yes [] No El Home address(Street or Lot#,Block,Subdivision): , Entire House I'` ,� uvG` "C 'LA rr '�'t�C M1401 3),.., ' .�. .a C.... .» 0",,A.... .v,...... ...?'32.�..�r.2-�.4-:. -....�...,w�. to%a.....N.,..:�abaF.,..., .r._,.n,,,:t»...f s,1 .rtu� .�.i�:,,�.=, Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: -4 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 82596 Btuh Number of bedrooms: 3 Conditioned floor area: 4232 ft2 Summer Design Conditions Number of occupants: 0 Outdoor temperature: 85 °F Indoor temperature: 75 °F Windows Roof Grains difference: 27 gr/Ib @50% RH Eave overhang depth: 0 ft Sensible heat gain: 20716 Btuh Internal shade: none Eave Latent heat gain: 5178 Btuh Blinds,drapes,etc. Depth window - Total heat gain: 25894 Btuh Number of skylights: 0 'HVAC EQUIPMENT-SELECTION (II, C M1401 3) _ r , Heating Equipment Data Cooling Equipment Data Blower Data Equipment type: Gas furnace Equipment type: Split AC Heating cfm: 933 Furnace,Heatpump,Boiler,etc. AirConditioner,Heat pump,etc. Cooling cfm: 933 Model: York Model: York Static pressure: 0 in H2O TM9X060B12MP11 TCHD30S41S3 Fan's rated external static pressure for design airflow Heating output capacity:. 57000 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winterdesign outdoor conditions Sensible cooling capacity: 0 Btuh Aux heating output capacity: 0 Btuh Latent cooling capacity: 0 Btuh ,,K ` - ' .Nt1601 fit\ rr y ,.SE / DESIG (RMl , te k« .e. s.. x - �,:w�X,.e. . ... ,e21'F AGDUGTEDISTRIBUTIONSSY _T ' Ct_. ,_ .=.,. a ., 2 . ..Design airflow: 933 cfm Longest supply duct: 0 ft Duct Materials Used Equipment design ESP: 0 in H2O Longest return duct: 0 ft Trunk duct: Total device pressure losses: 0 in H2O Total effective length(TEL): 0 ft Available static pressure(ASP): 0 in H2O Friction rate: 0 in/100ft Branch duct: Sheet metal Friction Rate=ASP+(TELx 10 ) xe Sg;+ r fi -`7',.. "n`'z�< '?. , „'T7� ,m: cs1x�.,:s, �wt1^,*e > ti� s ,a'x'-t'N.ws .+r 1«t.F .j i+A ,t ,4 F '+ ,,, s' '�,s.sa ^n • r5t.-�Y;`a" It declare they road balcuPatren equiornent,egtriptinenif sefeotion an d duct desrgni where rigorously performed based On the huil'thn,gi p�$eu Nistedf above. I C nderstaat.cf the deigns made o theseforrns rwi;8ibe subpec,, revrew and verification. -- , Contractor's printed name: Contractor's signature: Date: Reserved far Ccfunty,Town MtrnicioaLi�ty orAuttlortty having jurisdiction use *Home qualifies for MJ 1AE Form based on Abridged Edition Checklist 41-wr[ghtsoll' ° Right-Suite®Universal 2017 17.0.16 RSU25116 Project StmEana Job: 51 JOHN CLENDON DR Date: Jun 22,2018 Entire House By: FOOTHILL BUILDERS Plan: 1341 QUEENSBURY,NY 12804 AL .„L ;-. ,? '.r k: Y n,,, '{ .s p-,-7 r ,Te• - -"'' _' �r t,t -:' k-,�C. 4 qr ,'+"tz . «4i kxti:,..t,-,:'Y,gy..e. r.:.;,;,.:4 ,; tatil.�c—i Anzac:3:Qt t0i 3.2rSdii.if v:3:4ai a,..- •..47'.: For: JOE, FOOTHILL BUILDERS QUEENSBURY, NY 12804 Notes: dza"6,,4x a:os.— :b .s 1: .,.6,s=x-,., '^D GS..i.ei J "* ik two. +r..1 G s. Z { �. , Weather: Glens Falls AP, NY, US Winter Design Conditions Summer Design Conditions Outside db -4 °F Outside db 85 °F Inside db 68 °F Inside db 75 °F Design TD 72 °F Design TD 10 °F Daily range M Relative humidity 50 % Moisture difference 27 gr./lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 77703 Btuh Structure 17775 Btuh Ducts 4894 Btuh Ducts 869 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) Huidification 0 Btuh Bl (none) 0 Btuh Pi in Equipment load 82596 Btuh Use manufacturer's data n Rate/swing multiplier 0.90 Infiltration Equipment sensible load 16780 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4660 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 4232 4232 Equipment latent load 4660 Btuh Volume(ft3) 38088 38088 Air changes/hour 0.70 0.40 Equipment total load 21440 Btuh Equiv.AVF(cfm) 444 254 Req. total capacity at 0.70 SHR 2.0 ton Heating Equipment Summary Cooling Equipment Summary Make York Make York 1 Trade YORK Trade HORIZONTAL DISCHARGE Model TM9X060B12MP11 Cond TCHD30S41S3 AHRI ref 2008693 Coil HD36A3XH1+TM8X060Al2MP11+S1-1TVM4G1 AHRI ref 3743063 Efficiency 95.5 AFUE Efficiency 12.5 EER, 14 SEER Heating input 60000 Btuh Sensible cooling 19600 Btuh Heating output 57000 Btuh Latent cooling 8400 Btuh Temperature rise 56 °F Total cooling 28000 Btuh Actual air flow 933 cfm Actual air flow 933 cfm Air flow factor 0.011 cfm/Btuh Air flow factor 0.050 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 7th Ed. 2018-Jun-22 14:15:11 wrightsoft° Right-Suite®Universal 2017 17.0.16 RSU25116 Page 1 ACCN ...langeworthy\DocumenfslYork\51 JOHN CLENDON.rup Calc=MJ7 Front Door faces: N EXHAUST SYSTEMS '`" TABLE M1507,3.3(1) CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS 4" DWELLING UNIT NUMBER OF BEDROOMS ii y:: FLOOR AREA 0-1 2-3 4-5 6-7 >7 ,. .;1,_.' (square feel} Airflow in CFM Atki:: 1!: <I,500 30 45 60 75 90 irPi;;?t:- 1,501-3,000 45 - 60 75 90 105 sk.4'f'` 3,001-4,500 60 75 90 105 21 Q L `` 4,501—6,000 75 pis�• 90 105 120 135 I'` ' - 51 0 t:��; 6,001-7,500 90 105 - 120 135 >7,500 105 120 135 150 165 ySE:=i+. For SE: I square foot=0.0929 m2,I cubic foot per minute=0.0004719 m3/s. .+tiys:7;Y : X.(F-_ TABLE M1507.3.3(2) 1A'�•':. INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSarb zits.` RUN-TIME PERCENTAGE IN EACH 4-HOUR 1d!,; SEGMENT 25% 33% 50% 66% 75% y •, Lri :_triA Factor' 4 _ 3 2 1.5 1.3 #n,i,. a. For ventilation system run time values between those given,the factors are permitted to be determined by interpolation. ''Y '=s`` b.Extrapolation beyond the table is prohibited. 6.Ri:zi a - TABLE M1507.4 ;`"'' .:i F4 s., M1507.4 Local exhaust rates. Local exhaust systems shall MINIMUM REQUIRED LOCAL EXHAUST RATES`I •i-4ut. =`:- be designed to have the capacity to exhaust the minimum air ONE-AND TWO-FAMILY DWELLINGS f° =.'• flow rate determined m accordance with Table M1507.4. AREA TO BE . _',,{ 1r I17 Fi x l!, ` EXHAUSTED EXHAUST RATES=-:3. �, >!:i,_ Kitchens 100 cfrn intermittent or 25 cfiu�co Ali=;: Bathrooms-Toilet Mechanical exhaust capacity o5( '�,.� ;,r Rooms intermittent or 20 cfm continuo X -iI f 1 For SI: I cubic foot per minute=0.0004719 m3/s. �:"l ,..-,5): , :t=- 6 (T 5-elL)f-r - 60 cf i Fmil of ad♦g" ohs' ' gal`!iy `tzz•"i''t. ": >„E:T fi`i is -- :`y^-f -- -- — 2015 INTERNATIOtdA ; ,:: L r 4 ,1d r, a ' ". :1 .av rr, rx.; i, `A .w ..Y.1:1: .x'c'_ r'' „" 1..,. -f z: 'ra - r sr` nf'�+i.-a-s r 1x 'i., . T 1 „ m 4 s . } �-155 : MAX h F J 1 .1H EAT=RECOVERY VENTILATOR p7--A I THERMALLY CONDUCTIVE,P",TENTE11i DEFROST LLU llNUM CORE Recirculating damper defrost system. The counter-flow heat recovery core transfers heat between the two airstreams.It is easily removed for cleaning or service. CASE Twenty gauge prepainted galvanized steel for superior corrosion resistance.Insulated to .`070115 AND BLOWERS prevent exterior condensation.Drain connections 2-1/2 in.(12 mm)OD.Balancing ports Each airstream has one centrifugal blower driven by a common PSC motor,with multiple are located on door. fan speed operations. ELECTRONICS FILTERS The DXPLO2 control included with the unit can be wall mounted in a central location of Washable air filters in exhaust and supply air streams. the home.3 wire 20 gauge(min.)100 ft length(max.). Four threaded inserts at corners of the cabinet designed to accept the"s"hooks and ; °;; r'WARR�AN '"' 0 ;.11.1• � hanging straps supplied with the unit. I Lutz irteti L 1 R��,.o e,and 4a�sy jrr y : .,eplace ' n pot warranty V�-w v ' - OPTIONAL ACCESSORIES: Weather Hood TechGrille Terminator Wireless 20/40/60 99 185 99-EAG4 FittingMin Timer 99186 99-FAGS 99-TM4li!liv 99-DET02 99-18799-EAG6 7w 99-EAGS k 99-TM5 99-TM6 \i� LIFEBREATH CONTROL OPTIINS TINIER OPTIONS 99-DET01-Lifebreath 20/40/60 Minute Timer FEATURES 99-DXPLO2 99-BCO2 99-BC03 95-13C04 Initiates high speed Ventilation for 20,40 or 60 5 speed fan operation on each mode I minutes.3 wire connection. 99-DETO2 2 speed fan operation(Low/High) ✓ ✓ Wireless Lifebreath 20/40/60 Minute Timer Continuous low speed fan operation ✓ Initiates high speed Ventilation for 20,40 or 60 minutes.Wirelessly connects to main control for Humidity control through adjustable Dehumidistat ✓ ✓ ✓ ease of installation.40'approximate range. Excusive to Lifebreath. Large digital LCD screen V 99-14%02-Wireless Lifebreath Repeater LED status indicator lights ✓ V V Extends range of 99-DET02 Wireless Timers.Plugs into 120V power outlet.Wirelessly connects to Continuous Ventilation V V. main control and 99-DET02.Install at halfway ✓ ✓ point between timer and main watt control if timer Continuous Recirculation is out of range. 20 ON/40 OFF V { K„,IIA,Ie:iu; S®a to oN/5o OFF ✓ r 2 µ 6,• , 20 ON/40 Recirculation k( 141* al-- 20/40/60 min.High speed override button ✓ 99-DXPLO2 .y. 99-11ET02 Compatible with 99-DET02 Wireless Timer ✓ ✓ ✓ V a 3 wire connection V ✓ ✓ ✓ L IF EBREFI T - M' Indoor Air Systems 155MAX(01-0118) www.lifebreath.com lifebreath.com 155MAX I , HEAT RECOVERY VENTILATOR F : 0.1(25) 0.2(50) 0.3(75) 0.4(100) -0.5(125) "-0.6(150) 0.7(175)1 - ELECTRICAL SPECIFICATIONS ` CFM(Lis) CFM'(LIs) CFM(L!s) CFM(L/s) CFM(Lfs) _CFM(L/5)_ CFM(IA) Z. VAC @ 60HZ Iffill Met Supply Airflow 184-(811 I 146(69) 132(62) 115(54) 92(43) 60(28) Watts/Low Speed NE Gross Supply Airflow 166(18) 149(70) 134(63) 117(55) 94(44) 61(29) Watts/High Speed ME 1 Gross Exhaust Airflow EN 228(107) 212(100) 193(91) EIMI 150(71) 126(60) Amp Rating 1.4 Sensible Effectiveness(ASE) 32°F(0°C) $4°° 180 WEIGHT: @ 59 GEM(28 Us) s 71 LBS(32 KO Sensible Efficiency(SRE) 160 SHIPPING WEIGHT: @ 59 GEM(28 Us) 32°F(0°C} 75% 73 IRS(33 KG) E 140 Sensible Efficiency(SRC) 32°F(6°C} 75°l° @ 64 CFM(30 Us) 120o Sensible Efficiency(SRC) 13°E(-25°C) 72% 00 NOTE: @ 64 CFM(30 Us) Zr- Front clearance of 25 in.(635 mm)is so recommended for servicing unit.All ducts euse 6 in.(152 mm)round collars.Balancing i 9®� `,h1? i 60 dampers are located in all air streams. " 6 .. 03 CERTIFIED 0Eelsreer3 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Static Pressure(in w.g.) • FRONT VIEW TOP VIEW Filter if i 143/4 in.(315 mm) ,f Recirculating Defrost !^+ r� l l I Damper . . r t 1,401.1111111111011111.11W � 1� N Blower Removable llk Heat 14/ �� 4,state air to outside Recovery — Motor E Care / /ii i. Fresh air from outside ®Q t airfrom inside III � "' � Sta Freseh air to inside 6 in.(152mm) I� 33 5/8 In.(854 min) ' ®I —o v Round Collars Gate: r oaf ` ,s. • lr bal ITANJW, Contractor: ,4gse —tlt I�ev a 4y ' Tag: r;-xrrn EW/E neta rtr}. 5 as r•'..r: "a1la -ear aaris• WI-- Project: my: Supplier ,' `t `4. ; i>`S'"''Y 'ra:`"is': Engineer: Quote*: Al(units conform.to CSA and UL standards SS Control: Submitted By: III $REp THE b �i Indoor Air�Systems Timer: Timer Qty: ISSMAX(O1-01-18) www.t'[febreath.com