Loading...
blower door reportTesting Company: Name:LoCascio Energy Solutions Address:20 Ogden Rd. Queensbury , NEW YORK 12804 Phone: 5188573144 Technician: Name:Anthony LoCascio Credentials:HERS Rater#4242961 Email:tony@locascioenergysolutions.com Building Information: Project ID:159 Assembly Address:159 Assembly Point Rd Queensbury, NY 12804 Geo-Tag Data:Latitude: 43.461430 Longitude: -73.652664 Timestamp: 2020-09-25 14:56:12 Customer Information: Name:Michaels Group Homes Address:1 Marions Way Mechanicville, NY 12118 Measured Leakage:1,006.1 CFM50 Test ID:159 Assembly Purpose of Test:RESNET Multi-Pt Env. Leakage Measured ACH50:1.45 (+/- 3.1%)Effective Leakage Area: 49.1 in² Building Volume:41,739.0 ft³Enclosure Surface Area: 4,451.0 ft² Coefficient (C):65.8 (+/- 14.3%)Exponent (n): 0.697 (+/- 0.041) Correlation Coefficient:0.99948 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 64 °F Altitude: 326.0 ft Outdoor Temp: 72 °F Time Average Period: 10 seconds Test Date and Time:2020-09-25 14:56:44 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline 0.2 -60.0 -58.7 -59.0 -36.5 1,097.7 Ring A -48.0 -46.9 -47.1 -27.1 950.4 Ring A -35.0 -34.2 -34.4 -170.5 774.1 Ring B -23.0 -23.2 -23.5 -100.5 595.8 Ring B -10.0 -11.5 -11.7 -35.5 355.8 Ring B Test Equipment: Flow Device:Model 3 110V Fan Serial #: 3173 Custom Calibration Date: 2020-02-10 Pressure Gauge:DG1000 Serial #: 3173 Calibration Date: 2019-02-18 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.7.2 (87), © 2020 The Energy Conservatory, Inc.